User menu

In document pumping unit (сторінка 34-41)

9. STARTING AND USER INTERFACE 30

9.10 User menu

From the main screen press:

PROG to access the main menu;

ENTER to select and access the selected menu;

UP/DOWN to move between the submenus;

ENTER to enter the submenus

ENTER to select the parameter and move between the parameters;

UP/DOWN to modify the parameter;

ENTER to confi rm selected parameter and go to the next parameter;

ESC to return to the previous menu.

To navigate inside the screens:

UP or DOWN to modify the value (within the options/range),

ENTER to confi rm and move the cursor to the next value

ESC to return to the installer menu.

User menu screens:

1. User 1. Alarm threshold

2. Clock

3. Enable scheduler 4. Set scheduler 5. Weekly scheduler 6. Scheduled set point

Tab. 9.c

Submenu: 1. Alarm threshold

Display description range default unit

Main thresholds probe heading High alarm High humidity or

temperature alarm threshold

0 to 100 or -20 to 70

100 or 70 RH or °C

Low alarm Low humidity or temperature alarm threshold

0 to 100 or-20 to 70

0 or-20 RH or °C

Limit thresholds

probe Heading

Alarm threshold High limit humidity or temperature alarm threshold

0 to 100 or-20 to 70

100 or 70 RH or °C

Alarm delay Low limit humidity or temperature alarm threshold

0 to 100 or-20 to 70

0 or-20 RH or °C

Tab. 9.d

Submenu: 2. Clock

Display description range

Time Internal clock time

setting

Day Internal clock day

setting

Month Internal clock month setting

Year Internal clock year

setting

Format Date format setting dd/mm/yy - mm/dd/yy Weekday Day setting of the week Monday to Sunday

Tab. 9.e

Submenu: 3. Enable scheduler

Display description range default unit

Enable scheduler

Heading Scheduler on/

off

Enable scheduler ON/OFF off Variable set

point

Enable variable set point based on time of day

ON/OFF off Off and delay

time

Temporarily stop humiFog and automatically restart after __ hours

On / off off

Tab. 9.f

Submenu: 4. Set scheduler

Note: this screen is visible if “scheduler ON/OFF” has been enabled (see the enable scheduler screen).

Setting of the intervals for the operation of the humidifi er over one day (24h):

Display description ON time OFF time

P1-1 First interval of band P1 9:00 13:00

P1-2 Second interval of band P1 14:00 21:00

P2 Interval of band P2 8:00 18:00

P3 Band always ON Always ON

P4 Band always OFF Always OFF

Tab. 9.g Parameters P1 to P4 can be used set how many times atomised water production is enabled/disabled over a 24h period:

P1

P1-1 P1-2

P2 P2

P3

P4

0 OFF

ON ON

OFF OFF

ON ON

OFF OFF OFF

24 h

0 24 h

0 24 h

0 24 h

P1 Two daily ON time bands P2 Individual ON time band P3 Always ON

P4 Always OFF

installer user ser vic e

Submenu: 5. Weekly scheduler

Note: this screen is visible if “scheduler ON/OFF” has been enabled (see the enable scheduler screen).

Setting of the weekly operation of the humidifi er, using parameters P1 to P4 (confi gured in the previous screen)

Display range

Monday P1 to P4

Tuesday P1 to P4

Wednesday P1 to P4

Thursday P1 to P4

Friday P1 to P4

Saturday P1 to P4

Sunday P1 to P4

Tab. 9.h

Submenu: 6. Scheduled set points

Note: this screen is visible if “variable set point” has been enabled (see the enable scheduler screen).

Parameters Z1 to Z4 are used to confi gure up to 4 diff erent humidity set points that vary throughout the day (parameters Z1, Z2, Z3, Z4).

Display description Activation

time

Set point value Z1 Time setting for activating

the specifi ed set point

00:00 0 %rH

Z2 Time setting for activating the specifi ed set point

00:00 0 %rH

Z3 Time setting for activating the specifi ed set point

00:00 0 %rH

Z4 Time setting for activating the specifi ed set point

00:00 0 %rH

Tab. 9.i For example, the parameters described above can be set to change the set point throughout the day, as follows:

Z1 Z2 Z3 Z4

20% r.H 50% r.H

30% r.H

0 24 h

Note:

during the “OFF” time band, the humidifi er is NOT actually off , but

rather atomised water production is temporarily disabled, even when setting manually;

the “daily” time bands have priority over the “variable set point” bands.

For example, setting P4 each Monday (humidifi er off ), parameters Z1, Z2, Z3, Z4 (diff erent set point values) will not be observed, as the humidifi er is not programmed to operate on that day.

9.11 Installer menu

From the main screen press:

PRG to access the main menu;

DOWN to move to the installer menu;

ENTER to move to the password;

UP/DOWN to enter the password “77“

ENTER to access the selected menu;

UP/DOWN to move between the submenus;

ENTER to select the parameter and move between the parameters;

UP/DOWN to modify the parameter;

ENTER to confi rm the selected parameter and go to the next

parameter;

ESC to return to the previous menu.

To navigate inside the screens:

• UP or DOWN to modify the value (within the options/range),

• ENTER to confi rm and move the cursor to the next value

• ESC to return to the installer menu.

The installer menu is divided into four submenus:

Installer menu screens:

Display description

1. Pump setting Contains the submenus with the installer parameters corresponding to the pumping unit

2. Zone Contains the submenus with the installer parameters corresponding to the controlled zone (rack or room distribution system)

3. Remote zone settings Contains the submenus with the installer parameters corresponding to the remote zones, controlled by the slaves. This is only displayed on the master humiFog

Tab. 9.j

Submenu 1. Pump setting - 1. Pump setting

Contains the submenus with the installer parameters corresponding to the pumping unit

One of the two following screens is displayed, depending on the setting of the “Operating mode” parameter between the two possible values.

Display description range def. unit

Pump setting heading Operating mode:

fl ow control

humiFog operating mode setting

“Flow-rate control”

or

“constant pressure”

High press. Value for activating the next branch on the rack

20 to 80 70 bar

Low press. Value for deactivating the branch on the rack

20 to 80 25 bar

Pump setting Operating mode:

constant pressure

humiFog operating mode setting

“Flow-rate control”

or

“constant pressure”

Pressure setting Pressure set point value

20 to 80 70 bar Tab. 9.k

36 “humiFog multizone pumping unit ” +030222081 rel. 1.0 - 12.05.2009

installer user ser vic e

Submenu 1. Pump setting - 2. Supply water

Contains the submenus with the installer parameters corresponding to the demineralised water supply

Display description range default unit

Supply water heading Low pressure

measurement

Heading

Delay at startup Low pressure alarm delay time when starting the pump

1 to 999 15 seconds

Delay in steady operation

Low pressure alarm delay time with pump operating

1 to 999 15 seconds

Conductivity setting

Heading Warning

threshold

Warning threshold (high conductivity warning)

1 to 2000

100 μS

Alarm threshold High conductivity alarm threshold

1 to 2000

200 μS

Tab. 9.l

Submenu 1. Pump setting - 3.FSpecial pump functions

Display description range default unit

Special pump functionsHeading

Filling Heading

Enable Enable the function for fi lling the system

On / off On

Duration Duration of the fi ll cycle 1 to 60 5 Min

Automatic washing Heading

Mode Enable automatic washing or emptying

Emptying only = emptying due to inactivity when the time indicated below has elapsed

Daily wash = wash every day at the time set below

Periodical wash = wash for period set below (irrespective of operation or inactivity of the system)

Periodical wash

Time of day / period Time or period of time, as described for the previous parameter

1 to 168 48 h

Duration Duration of the washing cycle

1 to 60 5 min

Tab. 9.m (*) setting wash to OFF, the system will simply be emptied the when

the “Timeout” has elapsed, during which time the system remains full of water without atomising.

installer user ser vic e

Submenu 2. Zone – 1. Confi g. inputs

This contains two screens with the following parameters:

Display description range default unit

Confi g. inputs 1/2 First screen heading

Type of operation Set type of operation Humidity control,

Humid+Limit Humid control, Humid+Limit Temp control, Temperature control, Temp+Limit Humid control, Temp+Limit Temp control, External signal,

Ext signal + Lim Humid, Ext signal + Lim Temp, External ON/OFF, Ext ON/OFF + Lim Humid, Ext ON/OFF + Lim Temp.

Humidity control

Aux probe (%rH, °C/°F, No)Enable display on Info screen of the value measured by the Aux probe

On/off Off Control signal Heading

Type of signal Type of signal generated by the probe

NTC, 0 to 135oh, 0-1V, 0-10V, 4-20mA, 0-20mA

0-1V Various

Min Max Min. and max. probe values 0 to 100 0 , 100 %

Offset Probe off set 0 to 100 0, 100 %

Confi g. inputs 2/2 Second screen heading Limit signal Heading

Type of signal Type of signal generated by the probe

NTC, 0 to 135oh, 0-1V, 0-10V, 4-20mA, 0-20mA

0-1V Various

Min Max Min. and max. probe values 0 to 100 0, 100 %

Offset Probe off set 0 to 100 0 , 100 %

Aux signal Heading

Type of signal Type of signal generated by the probe

NTC, 0 to 135oh, 0-1V, 0-10V, 4-20mA, 0-20mA

0-1V Various

Min Max Min. and max. probe values 0 to 100 0 , 100 %

Offset Probe off set 0 to 100 0 , 100 %

Tab. 9.n Only the parameters corresponding to the probes used for the type of

operation set will be displayed.

Submenu 2. Zone – 2. Special functions

This contains two screens with the following parameters:

Display description range default unit

Special zone functions 1/2 Heading

Alarm relay logic Cumulative alarm relay logic setting N.O. = (normally open) when connecting as described in the previous paragraphs, the output will be open when no alarms are active or

N.C. = (normally closed) when connecting as described in the previous paragraphs, the output will be closed when no alarms are active Flow switch logic Flow switch input logic setting N.O. = (normally open) when connecting as

described in the previous paragraphs, humiFog is activated only if the fl ow switch is closed or

N.C. = (normally closed) when connecting as described in the previous paragraphs, humiFog is activated only if the fl ow switch is open Language User interface language setting Italian, English, French, German, Spanish (if

available)

Italian Show language selection at

start-up

Activation of prompt to set the language whenever starting humiFog

Enabled / disabled Enabled

Min value of prop control signal

Minimum value of proportional control signal.

Input signals less than this threshold do not generate the production of atomised water

5 to 80 5 %

Special zone functions 2/2 Heading Pressure relief Heading

Enable Enable pressure relief Enabled / disabled Disabled

Duration Pressure relief duration 1 to 999 3 Seconds

Rotation Heading

38 “humiFog multizone pumping unit ” +030222081 rel. 1.0 - 12.05.2009

installer user ser vic e

Display description range default unit

Time Atomising line/manifold activation

time

1 to 999 30 seconds

Tab. 9.o (*) humiFog is supplied with the fl ow switch input jumpered, consequently

the unit is enabled.

Submenu 2. Zone – 3. Distribution system

One of the two following screens is displayed, depending on the setting of the “Operating mode” parameter to “Flow control” or “Constant pressure

“ in the “Pump setting” menu.

“Operating mode” set to “Flow control”

Display Description range default unit

Distribution system heading

Number of branches Number branches on the rack 1 to 4 4 Rating Rated setting of the RACK (not to be confused

with the rating of the pumping unit!). This value is shown in the documents supplied with the rack.

10 to 600 10 kg/h

Minimum fl ow-rate Minimum fl ow-rate setting for the RACK (not to be confused with the fl ow-rate of the pumping unit!). This value is shown in the documents supplied with the rack and ensures that, at the minimum fl ow-rate, the water pressure does not fall below 20 bars and cause a shutdown alarm.

From the theoretical minimum calculated based on the “Rating” and the

“Number of branches” up to 80% of the “Rating”

Theoretical minimum calculated based on the

“Rating” and the “Number of branches”

kg/h

Tab. 9.p

“Operating mode” set to “Constant pressure”

Display Description range default unit

Distribution system heading

Step 1: xxx.x kg/h Capacity setting for the fi rst step of the system 0 to 120 0 kg/h Step 2: xxx.x kg/h Capacity setting for the second step of the system 0 to 120 0 kg/h Step 3: xxx.x kg/h Capacity setting for the third step of the system 0 to 120 0 kg/h Step 4: xxx.x kg/h Capacity setting for the fourth step of the system 0 to 120 0 kg/h Step 5: xxx.x kg/h Capacity setting for the fi fth step of the system 0 to 120 0 kg/h Step 6: xxx.x kg/h Capacity setting for the sixth step of the system 0 to 120 0 kg/h

Tab. 9.q

Submenu 2. Zone – 4. Supervisor

Display description range default unit

Supervisor Heading

BMS address Identifi er for BMS network 0 to 200 1

Com speed Communication speed 1200, 2400, 4800, 9600, 19200 19200 bps

Type of protocol Communication protocol setting Carel, Modbus, RS232, to Modbus

On/off from supervisor Enable ON/OFF from BMS Yes, No No

Tab. 9.r

Submenu 2. Zone – 5. External alarms

Display description range default unit

External alarms Heading

Water treatment alarm logic External water treatment alarm logic setting

N.O. = (normally open) when connecting as described in the previous paragraphs, humiFog will show the Water treatment alarm if the connection is interrupted or

N.C. = (normally closed) when connecting as described in the previous paragraphs, humiFog will show the Water treatment alarm if the connection is not interrupted (contact closed)

Tab. 9.s (*) humiFog is supplied with the water treatment alarm input jumpered,

consequently the unit is enabled.

installer user ser vic e

Submenu 3. Remote zone setting

Display description range default

Remote zone setting Heading

Zone 2: Yes/no add: remote zone activation and network address setting Yes / no 1 to 32

no Zone 3: Yes/no add: remote zone activation and network address setting Yes / no

1 to 32

no Zone 4: Yes/no add: remote zone activation and network address setting Yes / no

1 to 32

no Zone 5: Yes/no add: remote zone activation and network address setting Yes / no

1 to 32

no Zone 6: Yes/no add: remote zone activation and network address setting Yes / no

1 to 32

no

Tab. 9.t

9.12 Maintenance menu

Important: the operations described in this menu must only be carried out by qualifi ed personnel.

From the main screen press:

PRG to access the main menu;

DOWN to move to the maintenance menu;

ENTER to move to the password;

UP/DOWN to enter the password “77“

ENTER to access the selected menu;

UP or DOWN to move between the submenus;

ENTER to select the parameter and move between the parameters;

UP/DOWN to modify the parameter;

ENTER to confi rm the selected parameter and go to the next parameter;

ESC to return to the previous menu.

Maintenance menu screens:

Display 1. Reset conf 2. System info 3. Instant readings 4. Manual procedure 5. System status info 6. Hour counter 7. Alarm log

Submenu 1. Reset conf

Display description range default

Reset conf Heading Save

confi guration

Save a copy of the current parameter confi guration

Yes / No No Load

confi guration

Load the copy of the parameter confi guration saved previously using the above parameter

Yes / No No

Reset default Reset all parameters to the default values

Yes / No No Set model Set the model of humiFog All models

available

Tab. 9.u

Submenu 2. System info

Display description

System info heading

Model Display humiFog model

SW code Software code loaded Version Software version loaded

Date Software date loaded

Bios System BIOS version

Boot System BOOT version

Tab. 9.v

Submenu 3 . Instant readings

Display description range unit

Instant readingsheading

External signal Display value of external proportional control signal

0 to 100 % On/off input Display status of on/off control

input (not to be confused with the remote on/off enabling signal!)

On / off

Main signal Display value of the signal read by the main probe

Ohm, mA or Volt Limit signal Display value of the signal read

by the limit probe

Ohm, mA or Volt Aux probe Display value of the signal read

by the Aux probe

Ohm, mA or Volt

Tab. 9.w The signals that are not connected are highlighted by the message “not present” on the screen.

Submenu 4. Manual procedure

Used to manually set the humiFog outputs, one at a time. The parameters displayed correspond to the humiFog terminal labels. In addition, the capacity to be generated can be set for a zone or the entire system.

Display description range unit

Manual procedure heading System prod

request

Capacity that the system must generate. e.g. setting this to 30%, all the zones will generate 30% of maximum capacity.

0 to 100 %

Zone prod request Capacity that the zone must generate. e.g. setting this to 30%, the zone will generate 30% of maximum capacity.

0 to 100 %

Manual control all I/O

Manual setting of all the humiFog inputs and outputs

Tab. 9.x

40 “humiFog multizone pumping unit ” +030222081 rel. 1.0 - 12.05.2009

installer user ser vic e

Submenu 5. System status info Displays detailed information on the humiFog

Display description range

System status info

heading System status Display system

status

StandbyEmpty / StandbyFull / Filling / Washing / Emptying / Production

Pump status Display pump status

Standby / Increase prod / Close bypass / Pressure for fi lling / Pressure for wash / Drain reduce (decrease prod ramp to reach fl ow-rate of just one drain SV) / Close drain cycles / steady operation (production and emptying)

Tab. 9.y

Submenu 6. Hour counter

Display description range

Hour counter heading

Pump hours Display the value of the hour counter since the last reset

Reset hours Reset hour counter Yes / No Reset data Display date of last reset

Submenu 7. Alarm log

Display description

Alarm log heading

No. xxx time date Sequence of screens that contain the two rows displayed on the left: alarm message number, alarm time, alarm date and alarm message.

Alarm message

Tab. 9.z

The log contains 200 alarms, after which the next alarms overwrite the oldest ones.

installer user ser vic e