9. STARTING AND USER INTERFACE 30
9.10 User menu
From the main screen press:
PROG to access the main menu;
•
ENTER to select and access the selected menu;
•
UP/DOWN to move between the submenus;
•
ENTER to enter the submenus
•
ENTER to select the parameter and move between the parameters;
•
UP/DOWN to modify the parameter;
•
ENTER to confi rm selected parameter and go to the next parameter;
•
ESC to return to the previous menu.
•
To navigate inside the screens:
UP or DOWN to modify the value (within the options/range),
•
ENTER to confi rm and move the cursor to the next value
•
ESC to return to the installer menu.
•
User menu screens:
1. User 1. Alarm threshold
2. Clock
3. Enable scheduler 4. Set scheduler 5. Weekly scheduler 6. Scheduled set point
Tab. 9.c
Submenu: 1. Alarm threshold
Display description range default unit
Main thresholds probe heading High alarm High humidity or
temperature alarm threshold
0 to 100 or -20 to 70
100 or 70 RH or °C
Low alarm Low humidity or temperature alarm threshold
0 to 100 or-20 to 70
0 or-20 RH or °C
Limit thresholds
probe Heading
Alarm threshold High limit humidity or temperature alarm threshold
0 to 100 or-20 to 70
100 or 70 RH or °C
Alarm delay Low limit humidity or temperature alarm threshold
0 to 100 or-20 to 70
0 or-20 RH or °C
Tab. 9.d
Submenu: 2. Clock
Display description range
Time Internal clock time
setting
Day Internal clock day
setting
Month Internal clock month setting
Year Internal clock year
setting
Format Date format setting dd/mm/yy - mm/dd/yy Weekday Day setting of the week Monday to Sunday
Tab. 9.e
Submenu: 3. Enable scheduler
Display description range default unit
Enable scheduler
Heading Scheduler on/
off
Enable scheduler ON/OFF off Variable set
point
Enable variable set point based on time of day
ON/OFF off Off and delay
time
Temporarily stop humiFog and automatically restart after __ hours
On / off off
Tab. 9.f
Submenu: 4. Set scheduler
Note: this screen is visible if “scheduler ON/OFF” has been enabled (see the enable scheduler screen).
Setting of the intervals for the operation of the humidifi er over one day (24h):
Display description ON time OFF time
P1-1 First interval of band P1 9:00 13:00
P1-2 Second interval of band P1 14:00 21:00
P2 Interval of band P2 8:00 18:00
P3 Band always ON Always ON
P4 Band always OFF Always OFF
Tab. 9.g Parameters P1 to P4 can be used set how many times atomised water production is enabled/disabled over a 24h period:
P1
P1-1 P1-2
P2 P2
P3
P4
0 OFF
ON ON
OFF OFF
ON ON
OFF OFF OFF
24 h
0 24 h
0 24 h
0 24 h
P1 Two daily ON time bands P2 Individual ON time band P3 Always ON
P4 Always OFF
installer user ser vic e
Submenu: 5. Weekly scheduler
Note: this screen is visible if “scheduler ON/OFF” has been enabled (see the enable scheduler screen).
Setting of the weekly operation of the humidifi er, using parameters P1 to P4 (confi gured in the previous screen)
Display range
Monday P1 to P4
Tuesday P1 to P4
Wednesday P1 to P4
Thursday P1 to P4
Friday P1 to P4
Saturday P1 to P4
Sunday P1 to P4
Tab. 9.h
Submenu: 6. Scheduled set points
Note: this screen is visible if “variable set point” has been enabled (see the enable scheduler screen).
Parameters Z1 to Z4 are used to confi gure up to 4 diff erent humidity set points that vary throughout the day (parameters Z1, Z2, Z3, Z4).
Display description Activation
time
Set point value Z1 Time setting for activating
the specifi ed set point
00:00 0 %rH
Z2 Time setting for activating the specifi ed set point
00:00 0 %rH
Z3 Time setting for activating the specifi ed set point
00:00 0 %rH
Z4 Time setting for activating the specifi ed set point
00:00 0 %rH
Tab. 9.i For example, the parameters described above can be set to change the set point throughout the day, as follows:
Z1 Z2 Z3 Z4
20% r.H 50% r.H
30% r.H
0 24 h
Note:
during the “OFF” time band, the humidifi er is NOT actually off , but
•
rather atomised water production is temporarily disabled, even when setting manually;
the “daily” time bands have priority over the “variable set point” bands.
•
For example, setting P4 each Monday (humidifi er off ), parameters Z1, Z2, Z3, Z4 (diff erent set point values) will not be observed, as the humidifi er is not programmed to operate on that day.
9.11 Installer menu
From the main screen press:
PRG to access the main menu;
•
DOWN to move to the installer menu;
•
ENTER to move to the password;
•
UP/DOWN to enter the password “77“
•
ENTER to access the selected menu;
•
UP/DOWN to move between the submenus;
•
ENTER to select the parameter and move between the parameters;
•
UP/DOWN to modify the parameter;
•
ENTER to confi rm the selected parameter and go to the next
•
parameter;
ESC to return to the previous menu.
•
To navigate inside the screens:
• UP or DOWN to modify the value (within the options/range),
• ENTER to confi rm and move the cursor to the next value
• ESC to return to the installer menu.
The installer menu is divided into four submenus:
Installer menu screens:
Display description
1. Pump setting Contains the submenus with the installer parameters corresponding to the pumping unit
2. Zone Contains the submenus with the installer parameters corresponding to the controlled zone (rack or room distribution system)
3. Remote zone settings Contains the submenus with the installer parameters corresponding to the remote zones, controlled by the slaves. This is only displayed on the master humiFog
Tab. 9.j
Submenu 1. Pump setting - 1. Pump setting
Contains the submenus with the installer parameters corresponding to the pumping unit
One of the two following screens is displayed, depending on the setting of the “Operating mode” parameter between the two possible values.
Display description range def. unit
Pump setting heading Operating mode:
fl ow control
humiFog operating mode setting
“Flow-rate control”
or
“constant pressure”
High press. Value for activating the next branch on the rack
20 to 80 70 bar
Low press. Value for deactivating the branch on the rack
20 to 80 25 bar
Pump setting Operating mode:
constant pressure
humiFog operating mode setting
“Flow-rate control”
or
“constant pressure”
Pressure setting Pressure set point value
20 to 80 70 bar Tab. 9.k
36 “humiFog multizone pumping unit ” +030222081 rel. 1.0 - 12.05.2009
installer user ser vic e
Submenu 1. Pump setting - 2. Supply water
Contains the submenus with the installer parameters corresponding to the demineralised water supply
Display description range default unit
Supply water heading Low pressure
measurement
Heading
Delay at startup Low pressure alarm delay time when starting the pump
1 to 999 15 seconds
Delay in steady operation
Low pressure alarm delay time with pump operating
1 to 999 15 seconds
Conductivity setting
Heading Warning
threshold
Warning threshold (high conductivity warning)
1 to 2000
100 μS
Alarm threshold High conductivity alarm threshold
1 to 2000
200 μS
Tab. 9.l
Submenu 1. Pump setting - 3.FSpecial pump functions
Display description range default unit
Special pump functionsHeading
Filling Heading
Enable Enable the function for fi lling the system
On / off On
Duration Duration of the fi ll cycle 1 to 60 5 Min
Automatic washing Heading
Mode Enable automatic washing or emptying
Emptying only = emptying due to inactivity when the time indicated below has elapsed
Daily wash = wash every day at the time set below
Periodical wash = wash for period set below (irrespective of operation or inactivity of the system)
Periodical wash
Time of day / period Time or period of time, as described for the previous parameter
1 to 168 48 h
Duration Duration of the washing cycle
1 to 60 5 min
Tab. 9.m (*) setting wash to OFF, the system will simply be emptied the when
the “Timeout” has elapsed, during which time the system remains full of water without atomising.
installer user ser vic e
Submenu 2. Zone – 1. Confi g. inputs
This contains two screens with the following parameters:
Display description range default unit
Confi g. inputs 1/2 First screen heading
Type of operation Set type of operation Humidity control,
Humid+Limit Humid control, Humid+Limit Temp control, Temperature control, Temp+Limit Humid control, Temp+Limit Temp control, External signal,
Ext signal + Lim Humid, Ext signal + Lim Temp, External ON/OFF, Ext ON/OFF + Lim Humid, Ext ON/OFF + Lim Temp.
Humidity control
Aux probe (%rH, °C/°F, No)Enable display on Info screen of the value measured by the Aux probe
On/off Off Control signal Heading
Type of signal Type of signal generated by the probe
NTC, 0 to 135oh, 0-1V, 0-10V, 4-20mA, 0-20mA
0-1V Various
Min Max Min. and max. probe values 0 to 100 0 , 100 %
Offset Probe off set 0 to 100 0, 100 %
Confi g. inputs 2/2 Second screen heading Limit signal Heading
Type of signal Type of signal generated by the probe
NTC, 0 to 135oh, 0-1V, 0-10V, 4-20mA, 0-20mA
0-1V Various
Min Max Min. and max. probe values 0 to 100 0, 100 %
Offset Probe off set 0 to 100 0 , 100 %
Aux signal Heading
Type of signal Type of signal generated by the probe
NTC, 0 to 135oh, 0-1V, 0-10V, 4-20mA, 0-20mA
0-1V Various
Min Max Min. and max. probe values 0 to 100 0 , 100 %
Offset Probe off set 0 to 100 0 , 100 %
Tab. 9.n Only the parameters corresponding to the probes used for the type of
operation set will be displayed.
Submenu 2. Zone – 2. Special functions
This contains two screens with the following parameters:
Display description range default unit
Special zone functions 1/2 Heading
Alarm relay logic Cumulative alarm relay logic setting N.O. = (normally open) when connecting as described in the previous paragraphs, the output will be open when no alarms are active or
N.C. = (normally closed) when connecting as described in the previous paragraphs, the output will be closed when no alarms are active Flow switch logic Flow switch input logic setting N.O. = (normally open) when connecting as
described in the previous paragraphs, humiFog is activated only if the fl ow switch is closed or
N.C. = (normally closed) when connecting as described in the previous paragraphs, humiFog is activated only if the fl ow switch is open Language User interface language setting Italian, English, French, German, Spanish (if
available)
Italian Show language selection at
start-up
Activation of prompt to set the language whenever starting humiFog
Enabled / disabled Enabled
Min value of prop control signal
Minimum value of proportional control signal.
Input signals less than this threshold do not generate the production of atomised water
5 to 80 5 %
Special zone functions 2/2 Heading Pressure relief Heading
Enable Enable pressure relief Enabled / disabled Disabled
Duration Pressure relief duration 1 to 999 3 Seconds
Rotation Heading
38 “humiFog multizone pumping unit ” +030222081 rel. 1.0 - 12.05.2009
installer user ser vic e
Display description range default unit
Time Atomising line/manifold activation
time
1 to 999 30 seconds
Tab. 9.o (*) humiFog is supplied with the fl ow switch input jumpered, consequently
the unit is enabled.
Submenu 2. Zone – 3. Distribution system
One of the two following screens is displayed, depending on the setting of the “Operating mode” parameter to “Flow control” or “Constant pressure
“ in the “Pump setting” menu.
“Operating mode” set to “Flow control”
Display Description range default unit
Distribution system heading
Number of branches Number branches on the rack 1 to 4 4 Rating Rated setting of the RACK (not to be confused
with the rating of the pumping unit!). This value is shown in the documents supplied with the rack.
10 to 600 10 kg/h
Minimum fl ow-rate Minimum fl ow-rate setting for the RACK (not to be confused with the fl ow-rate of the pumping unit!). This value is shown in the documents supplied with the rack and ensures that, at the minimum fl ow-rate, the water pressure does not fall below 20 bars and cause a shutdown alarm.
From the theoretical minimum calculated based on the “Rating” and the
“Number of branches” up to 80% of the “Rating”
Theoretical minimum calculated based on the
“Rating” and the “Number of branches”
kg/h
Tab. 9.p
“Operating mode” set to “Constant pressure”
Display Description range default unit
Distribution system heading
Step 1: xxx.x kg/h Capacity setting for the fi rst step of the system 0 to 120 0 kg/h Step 2: xxx.x kg/h Capacity setting for the second step of the system 0 to 120 0 kg/h Step 3: xxx.x kg/h Capacity setting for the third step of the system 0 to 120 0 kg/h Step 4: xxx.x kg/h Capacity setting for the fourth step of the system 0 to 120 0 kg/h Step 5: xxx.x kg/h Capacity setting for the fi fth step of the system 0 to 120 0 kg/h Step 6: xxx.x kg/h Capacity setting for the sixth step of the system 0 to 120 0 kg/h
Tab. 9.q
Submenu 2. Zone – 4. Supervisor
Display description range default unit
Supervisor Heading
BMS address Identifi er for BMS network 0 to 200 1
Com speed Communication speed 1200, 2400, 4800, 9600, 19200 19200 bps
Type of protocol Communication protocol setting Carel, Modbus, RS232, to Modbus
On/off from supervisor Enable ON/OFF from BMS Yes, No No
Tab. 9.r
Submenu 2. Zone – 5. External alarms
Display description range default unit
External alarms Heading
Water treatment alarm logic External water treatment alarm logic setting
N.O. = (normally open) when connecting as described in the previous paragraphs, humiFog will show the Water treatment alarm if the connection is interrupted or
N.C. = (normally closed) when connecting as described in the previous paragraphs, humiFog will show the Water treatment alarm if the connection is not interrupted (contact closed)
Tab. 9.s (*) humiFog is supplied with the water treatment alarm input jumpered,
consequently the unit is enabled.
installer user ser vic e
Submenu 3. Remote zone setting
Display description range default
Remote zone setting Heading
Zone 2: Yes/no add: remote zone activation and network address setting Yes / no 1 to 32
no Zone 3: Yes/no add: remote zone activation and network address setting Yes / no
1 to 32
no Zone 4: Yes/no add: remote zone activation and network address setting Yes / no
1 to 32
no Zone 5: Yes/no add: remote zone activation and network address setting Yes / no
1 to 32
no Zone 6: Yes/no add: remote zone activation and network address setting Yes / no
1 to 32
no
Tab. 9.t
9.12 Maintenance menu
Important: the operations described in this menu must only be carried out by qualifi ed personnel.
From the main screen press:
PRG to access the main menu;
DOWN to move to the maintenance menu;
ENTER to move to the password;
UP/DOWN to enter the password “77“
ENTER to access the selected menu;
UP or DOWN to move between the submenus;
ENTER to select the parameter and move between the parameters;
UP/DOWN to modify the parameter;
ENTER to confi rm the selected parameter and go to the next parameter;
ESC to return to the previous menu.
Maintenance menu screens:
Display 1. Reset conf 2. System info 3. Instant readings 4. Manual procedure 5. System status info 6. Hour counter 7. Alarm log
Submenu 1. Reset conf
Display description range default
Reset conf Heading Save
confi guration
Save a copy of the current parameter confi guration
Yes / No No Load
confi guration
Load the copy of the parameter confi guration saved previously using the above parameter
Yes / No No
Reset default Reset all parameters to the default values
Yes / No No Set model Set the model of humiFog All models
available
Tab. 9.u
Submenu 2. System info
Display description
System info heading
Model Display humiFog model
SW code Software code loaded Version Software version loaded
Date Software date loaded
Bios System BIOS version
Boot System BOOT version
Tab. 9.v
Submenu 3 . Instant readings
Display description range unit
Instant readingsheading
External signal Display value of external proportional control signal
0 to 100 % On/off input Display status of on/off control
input (not to be confused with the remote on/off enabling signal!)
On / off
Main signal Display value of the signal read by the main probe
Ohm, mA or Volt Limit signal Display value of the signal read
by the limit probe
Ohm, mA or Volt Aux probe Display value of the signal read
by the Aux probe
Ohm, mA or Volt
Tab. 9.w The signals that are not connected are highlighted by the message “not present” on the screen.
Submenu 4. Manual procedure
Used to manually set the humiFog outputs, one at a time. The parameters displayed correspond to the humiFog terminal labels. In addition, the capacity to be generated can be set for a zone or the entire system.
Display description range unit
Manual procedure heading System prod
request
Capacity that the system must generate. e.g. setting this to 30%, all the zones will generate 30% of maximum capacity.
0 to 100 %
Zone prod request Capacity that the zone must generate. e.g. setting this to 30%, the zone will generate 30% of maximum capacity.
0 to 100 %
Manual control all I/O
Manual setting of all the humiFog inputs and outputs
Tab. 9.x
40 “humiFog multizone pumping unit ” +030222081 rel. 1.0 - 12.05.2009
installer user ser vic e
Submenu 5. System status info Displays detailed information on the humiFog
Display description range
System status info
heading System status Display system
status
StandbyEmpty / StandbyFull / Filling / Washing / Emptying / Production
Pump status Display pump status
Standby / Increase prod / Close bypass / Pressure for fi lling / Pressure for wash / Drain reduce (decrease prod ramp to reach fl ow-rate of just one drain SV) / Close drain cycles / steady operation (production and emptying)
Tab. 9.y
Submenu 6. Hour counter
Display description range
Hour counter heading
Pump hours Display the value of the hour counter since the last reset
Reset hours Reset hour counter Yes / No Reset data Display date of last reset
Submenu 7. Alarm log
Display description
Alarm log heading
No. xxx time date Sequence of screens that contain the two rows displayed on the left: alarm message number, alarm time, alarm date and alarm message.
Alarm message
Tab. 9.z
The log contains 200 alarms, after which the next alarms overwrite the oldest ones.