• No results found

SPECIAL FUNCTION

In document No. OCH413 REVISED EDITION-D (сторінка 34-41)

10-1. HOW TO PERFORM THE UP/DOWN OPERATION OF THE AIR INTAKE GRILLE

10-1-1. Setting up the lowering distance of air intake grille

10-1-2. How to perform the up/down operation using wireless remote controller

F1 F2 F3 F4

F1 F2 F3 F4

All Auto descending panel

Auto descending panel Input display:

All

Cur. Address Check

Down/ Up

Cur. Address Check Down/ Up Ref. address

Unit No.

Operation

Keep clear, panel descending.

Press Check for Unit No.

Ref. address Unit No.

Operation

Panel will stop in 30 sec.

Keep clear, panel descending.

F1 F2 F3 F4

Maintenance menu

Main menu:

Cursor

Auto descending panel Manual vane angle

1

Select "Maintenance" from the Main menu, and press the button.

2

Move the cursor to "Ref. address", "Unit No." or "Operation" with the F1 button to select.

Select the refrigerant address and the unit number for the units to whose falls panel, with the F2 or F3 button, and press the button.

Navigating through the screens

• To go back to the Main menu ... button

• To return to the previous screen ... button

Select "Auto descending panel" with the F1 or F2 button, and press the button.

* When using the auto descending panel, always set the "Address" and "Unit No." with "Service" – "Function setting".

• Ref. address: Refrigerant address

• Unit No.: 1, 2, 3, 4, All

• Operation: Down / Up

Press the F4 button to confirm the unit.

<Confirmation of target unit>

If the unit being set is unknown, make the setting and then press the F4 but- ton to conf rm.

The air conditioner which is blowing downward is the target air conditioner.

10-1-3. How to perform the up/down operation using wired remote controller (PAR-30MAA / PAR-31MAA)

10-1-4. How to perform the up/down operation using wired remote controller (PAR-21MAA)

[ Note: ] NGeneral Operation

Operation status

display Button to exit the up/down

operation mode Down/Up

buttons

PAR-21MAA

ON/OFF

FILTER CHECK OPERATION CLEAR TEST TEMP.

MENU BACK MONITOR/SET DAY

CLOCK ON/OFF

"Stand by for lowering"

display

"Up/down operation mode" display

"Lowering" display (blinking)

"Stopped" display (when finished lowering)

Alternately

* Raise or lower all the air intake grilles managed by the remote controller at the same time.

Install the remote controller in a place where you can observe all the air-conditioners. Otherwise, the lowering grille may make contact with something and cause damage to it.

Alternately

[ Note: ]

Buttons to enter the up/down operation mode (Press them simultaneously for 2 seconds.)

• You cannot stop the operation while the air intake grille is lowering.

* If you press the ( ) button while the air intake grille is moving down, the air intake grille may stop lowering, but it will not stop immediately.

• By default, the air intake grille will automatically stop at the lowering distance of 1.6 m from the ceiling level.

* The distance can be changed to 1.2 m, 2.0 m, 2.4 m, 2.8 m, 3.2 m, 3.6 m, and 4.0 m.

These should be used only as a guide. You should lower the air intake grille yourself to check the exact distance.

• You cannot stop the operation while the air intake grille is rising.

* If you press the ( ) button while the air intake grille is moving up, the air intake grille maystop rising, but it will not stop immediately.

"Stand by for raising" display

"Raising" display (blinking)

"Stopped" display (when the air intake grille has been put back into place)

1) Ensure that the air-conditioner is not running.

* The up/down operation mode is only available when the air-conditioner is "OFF".

2) Press both the "FILTER" and "Ventilation" buttons simultaneously for 2 seconds or more to enter the up/down operation mode.

3) Press the TEMP. ( ) button. After a while, the air intake grille will begin lowering.

4) Remove the filter and/or air intake grille to clean them.

5) Press the TEMP. ( ) button. After a while, the air intake grille will begin to rise and then be put back into place.

6) Exit the up/down mode either by pressing the "ON/OFF" button or by pressing both the "FILTER" and "Ventilation"

buttons simultaneously for 2 seconds or more.

* After exiting the up/down mode, wait for about 30 seconds to perform the next operation. The remote controller will not accept any operation for that period.

Ensure that the air-conditioner is not running.

• Otherwise, it may cause an injury or a failure.

Warning:

[Remarks:]

[Remarks:]

Up/down operation mode

Up/down operation mode

Unit No. Refrigerant address No.

Individually-specified up/down operation mode

(a) "Unit No." selection

display (c) "Standby for up/down operation" display

(b) "Refrigerant address No." selection display

Operation status display

Mode selection

PAR-21MAA

ON/OFF

FILTER CHECK OPERATION CLEAR TEST TEMP.

MENU BACK MONITOR/SET DAY

CLOCK ON/OFF

If the number of the target air- conditioner is unknown, go to 4).

In the upper right figure, the air-conditioner which the refrigerant address is "00" and

the unit No. is "1" is currently selected. If the number of the target air- conditioner is known, go to 5).

1) Ensure that the air-conditioner is not running.

* The up/down operation mode is only available when the air-conditioner is "OFF".

2) Press both the "FILTER" and "Ventilation" buttons simultaneously for 2 seconds or more to enter the up/down operation mode.

3) Press the "Ventilation" button. After a while, it will switch to the "individually-specified up/down operation mode".

4) If you press the "FILTER" button when the "Unit No." or "Refrigerant address No." is blinking,

the up/down airflow direction of the displayed air-conditioner will be switched downward after a while, and the airflow direction of the other vents will all be blocked.

5) Select the "Unit No." and "Refrigerant address No.".

"Unit No." and "Refrigerant address No." can be changed by using the "TEMP." buttons ( ) ( ) when the panel displays (a) or (b).

Every time you press the "Mode selection" button, the target of operation will change as illustrated below.

6) Continue to press the "Mode selection" button until "Waiting for up/down operation" is displayed.

The following steps are the same as steps 3) - 6) described in the "General Operation" section. Refer to that section.

In Step 5) described below, identify the target air-conditioner by changing the "Unit No." and

"Refrigerant address No." and by pressing the "FILTER"

button to check the up/down airflow direction.

Each pressing action changes the unit No. from "1 - 4" to "0".

(Unit No. "0" means that all of 1 - 4 are targeted.)

Each press changes the "Refrigerant address" from "0 to 15".

If "Err" is displayed when you press the "FILTER" button to check the target air-conditioner, the air-conditioner with that "Unit No." or "Refrigerant address" may not exist. Check and set that air-conditioner again.

Down/Up buttons (for selecting unit No. and refrigerant address)

Button to exit the up/down operation mode

Buttons to enter the up/down operation mode (Hold them down simultaneously for 2 seconds.)

Up/down operation with the individual specified air-conditioner (when used in combination with Mr. SLIM model)

* Raise or lower the air intake grille of the specific air-conditioner that you select from all that are managed by that remote controller.

"Waiting for up/down operation" display

Ensure that the air-conditioner is not running.

• Otherwise, it may cause an injury or a failure.

Warning:

10-2. OPERATION (AUTO DESCENDING PANEL: PLP-6BAJ)

UP/DOWN

Machine 1 UP/DOWN

Machine 2 Wire 1b

Wire 1a

Wire 2a Wire 2b

Fig.1 Detection

switch

(1) Normal operation

UP/DOWN

Air intake grille is raised/lowered by commands of UP and DOWN.

Air intake grille does not move under the state of no-load detection or obstacle detection.

Air intake grille stops automatically at the set lowering distance from the ceiling level.

STOP

It stops in the cases below :

• When it reaches at the set lowering distance from the ceiling level.

It automatically stops after a predetermined period of lowering.

• When it is stored in the panel.

The air intake grille is judged to be stored in the panel

when the storage detection switch is pressed for 3 seconds continuously.

• When receiving commands of STOP, DOWN while moving up or UP while moving down.

The STOP button is only available on the automatic filter elevation panel remote controller.

When the wired remote controller is used, there will be a slight delay in stopping due to transmission speed.

• When both wire 1b and wire 2b are not loaded.

Only the wire b in each UP/DOWN Machine has a tension detection switch.

(2) Special operation

Storage operation

Case : Obstruction of the raising grille before storage or malfunction of storage detection switch Storage operation will be performed when the intake grille has been raised the set distance but the storage detection switch is not engaged.

In this case, the operation below will be repeated up to 4 times.

10 cm down 30 cm up ···· 10 cm down 30 cm up No-load detection

Case : UP/DOWN commands with no grille suspended.

When both wire 1b and wire 2b are not loaded, the wires will not move.

Obstacle detection

Case : Making contact with something while lowering.

Should the loads on the wire 1b and wire 2b be removed due to the grille making contact with something while lowering, the lowering operation will stop. The grille will then be raised 10 cm and stop again.

[Emergency operation]

• When the wireless remote controller cannot be used (in the case of battery discharge, misplacing of the wireless remote controller, malfunctioning and so on), the emergency switch on the receiver can be used as an alternative.

* When doing this, particular caution must be taken not to fall.

To lower the air intake grille : Press the button once.

(For emergency heating operation, press and hold this button.) To raise the air intake grille : Press the button once.

(For emergency cooling operation, press and hold this button.)

• To stop the air intake grille from moving, use the opposite buttons to those used to initiate movement.

(To stop it from lowering, press the UP button; To stop it from rising, press the Down button.)

• If up/down machine is out of order, fix air intake grille temporarily and the indoor unit can be operated.

* For details, refer to installation manual for the attachment of grille.

10-3. ELECTRICAL CIRCUIT (Controller board and wiring diagram (Panel))

10-3-1. Dip SW 22 type

ON 1

1

3 2

5 3

1 1 1 1 1

2 2 2 2

2 CN3G

(BLK)

CN3G (BLK) CN90(WHT)

CN2B (WHT)

FUSE

CNAC(WHT) CN22(BLU)

SW22

CN2C (WHT)

CN3A (RED)

U.B R.B

TB5 1 TB61

2 2

I.B

Panel Indoor unit

CN2G(BLK)

CN2F(BLK)

CN2E(RED)

SW1

SW2 RU

BZ 1 2 3 4 5 6 7 8 9 (WHT)CNB W.B

MU1 MU1 LS21

LS1

LS21 UK1 UK1

2

2 1

1

3

9

WHT BLK

GRN/YLW BLK

WHT

WHT WHT

1 2 3 4 5 6 7 8 910

BR N OR N YL W

BL K RE D

BL K RE D

BL K RE D RE D

Symbol Name Symbol Name

U.B Auto grille controller board W.B Wireless remote controller board

FUSE Fuse (3.15A) BZ Buzzer

RU Receiver

SW22 Switch (Lowering distance set up) SW1 Emergency switch (heating/down)

UK1 Up/down machine SW2 Emergency switch (cooling/up)

MU1 Motor (Up/down) LS1 Limit switch (storage detection)

LS21 Limit switch (tension detection) R.B Wired remote controller I.B Indoor controller board

SW22

10-3-2. Dip SW 2 type

SW2

SYMBOL NAME SYMBOL NAME

U.B CONTROLLER BOARD I.B UK1

W.B

UP/DOWN MACHINE

FUSE FUSE (T3.15AL250V) M MOTOR (FOR GRILLE UP/DOWN)

LS21 LIMIT SWITCH (TENSION DETECTION) LIMIT SWITCH (STORAGE DETECTION) WIRED REMOTE CONTROLLER SW1

SW2 SW2

SW1 SWITCH (MODEL SELECTION)

INDOOR UNIT CONTROLLER BOARD WIRELESS SIGNAL RECEIVER BOARD

SWITCH (LOWERING DISTANCE) BZ

LS1 SW3 R.B.

LED1

LED2

SWITCH (SYSTEM SELECTION)

BUZZER RU RECEIVING UNIT LED RED

(MICROCOMPUTER POWER) LED RED

EMERGENCY HEATING LONG PRESS FOR OVER 2 SEC) EMERGENCY COOLING LONG PRESS FOR OVER 2 SEC)

SYMBOL NAME

GRILLE / DOWN (SHORT PRESS) GRILLE / UP (SHORT PRESS)

10-3-3. Check point of trouble

<LED (SW22 type) /LED2 (SW2 type) display>

Turn OFF : No power supply

Blink : Storage detection switch ON (short) One blink : Storage detection switch OFF (open) Two blinks : Tension detection switch OFF (open)

<controller board>

Check item Check point Normal Remarks

Up/down controller P.C. board supply voltage

CN3A(between 3-5) AC 198~264 V Up/down machine

supply voltage CN2B, CN2C DC 10~12 V Check when instructing up/down with LED blinking once.

<Up/down machine>

Check item Check point Normal Check contents

Storage detection

switch CN2E open or short Check if it is short when pressing push switch.

Tension detection

switch CN2F, CN2G open or short Check if it is short when wire b is tensioned.

Motor CN2B, CN2C 5~20 Check if it is not open or short.

Entwining wires Pull wire Retension:

about 2 kgf Check if wire is drawn out by pulling with 3 kgf.

•Check the following points.

Problem Possible Reason Corrective Action

Air-conditioner is running. Stop running the air-conditioner and try again.

After recovering from power failure, try again.

Insert or replace the battery.

Remove the objects or obstacles from the air intake grille.

Or, remove the stuck object.

Remove the objects or obstacles from the air intake grille.

Lower the air intake grille again and check whether the filter is installed in the correct position.

Lower the air intake grille again and hook on the air intake grille.

This is normal.

This is normal.

Power failure

Batteries are not inserted into the wireless remote controller.

Or battery power is running low.

There is something on the air intake grille.

Or something is stuck in the air intake grille.

There is something on the air intake grille.

Filter is not properly installed.

Air intake grille is not hung with all 4 hooks.

The air intake grille has finished lowering to the auto-stop position.

This is the noise made when the wire is wound and unwound.

This is the operational noise for putting the air intake grille into place.

This is the operation for putting the air intake grille into place.

The speeds of winding/unwinding wires are slightly different for each wire.

Air intake grille does not function with operation of the wireless remote controller.

Air intake grille cannot be fixed in place.

Air intake grille stops lowering.

(Air intake grille would not lower any further.) Noises are made during up/down operation.

(While air intake grille is moving up/down.)

Noises are made while putting the air intake grille into place.

Air intake grille repeats rising and lowering several times while being put into place.

Air intake grille leans toward one side during the up/down operation.

10-4. TROUBLESHOOTING

In document No. OCH413 REVISED EDITION-D (сторінка 34-41)

СУПУТНІ ДОКУМЕНТИ