Self-diagnosis Method

In document Indoor Unit Outdoor Unit CS-HZ9RKE (сторінка 65-93)

16. Troubleshooting Guide

16.4 Self-diagnosis Method

16.4.1 H11 (Indoor/Outdoor Abnormal Communication)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal.

Malfunction Caused

 Faulty indoor unit PCB.

 Faulty outdoor unit PCB.

 Indoor unit-outdoor unit signal transmission error due to wiring error.

 Indoor unit-outdoor unit signal transmission error due to breaking of wire in the connection wires between the indoor and outdoor units.

Troubleshooting

YES

YES

YES

NO

Caution

When abnormality indication starts again

Measure the AC voltage at terminal 1 & 2 of outdoor unit terminal board

Is the measured voltage 230/240V? ● AC power supply abnormal fluctuation

NO ● Defect in communication circuitry

● Improper connection at terminals Measure the DC voltage at terminal 2 & 3 (communication

terminals) of outdoor unit terminal board

Is the measured DC voltage fluctuate between 18~25V?

NO

● Improper connection at terminals NO

Measure the AC voltage at terminal 1 & 2 of indoor unit terminal board

Is the measured voltage 230/240V?

● Defect in receiver/transmitter module of YES

Measure the DC voltage at terminal 2 & 3 of indoor unit terminal board

Is the measured DC voltage fluctuate between 18~25V?

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

● Replace the PCB of outdoor unit PCB

● Check indoor/outdoor connecting cable indoor/outdoor

indoor/outdoor

● Check indoor/outdoor connecting cable

the communication circuitry in indoor unit PCB

● Replace the indoor unit PCB

16.4.2 H12 (Indoor/Outdoor Capacity Rank Mismatched)

Malfunction Decision Conditions

 During startup, error code appears when different types of indoor and outdoor units are interconnected.

Malfunction Caused

 Wrong models interconnected.

 Wrong indoor unit or outdoor unit PCBs mounted.

 Indoor unit or outdoor unit PCBs defective.

 Indoor-outdoor unit signal transmission error due to wrong wiring.

 Indoor-outdoor unit signal transmission error due to breaking of wire 3 in the connection wires between the indoor and outdoor units.

Troubleshooting

When abnormality indication starts again

Is there any wiring error?

YES

Matched compatibility?

Correct the indoor-outdoor unit connection wires Check the indoor and outdoor unit connection wires

Check the spare part numbers of the indoor and outdoor unit PCBs and compare with their Part Lists

NO YES

NO

Is indoor unit and outdoor unit model numbers matched? NO Match the compatible model(s)

Change for the specified indoor or outdoor unit PCB

Replace the indoor and outdoor unit PCBs YES

Check indoor and outdoor units model number

Caution

For safety reason and to prevent

component breakdown, always switch

off the power before remove and

connect the component.

16.4.3 H14 (Indoor Intake Air Temperature Sensor Abnormality)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the temperatures detected by the indoor intake air temperature sensor are used to determine sensor errors.

Malfunction Caused

 Faulty connector connection.

 Faulty sensor.

 Faulty PCB.

Troubleshooting

Sensor (Thermistor) Characteristics

70 60 50

Resistance(kΩ)

Temperature (ºC) 40

30 20 10

-10 0 10 20 30 40 50

0

1 Pipe temp. Sensor 2 Intake Air Temp. Sensor

1 2

When abnormality indication starts again

Check the indoor intake air temperature sensor:

● Plug out connector from the indoor unit PCB

● Measure the resistance of the indoor intake air temperature sensor

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

Is the measured resistance of the indoor intake air temperature sensor matches the value specified in its characteristic chart?

● Defect in indoor intake air temperature sensor

● Replace the indoor intake air temperature sensor

Defect in indoor unit PCB Replace the indoor unit PCB Check the connector connection:

● Turn off the power

● Check the connector connection

Is the connector connection normal?

YES

● Connector poor contact

● Correct the connection NO

NO

YES

Caution

16.4.4 H15 (Compressor Temperature Sensor Abnormality)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the temperatures detected by the outdoor compressor temperature sensor are used to determine sensor errors.

Malfunction Caused

 Faulty connector connection.

 Faulty sensor.

 Faulty PCB.

Troubleshooting

Compr essor Temp. Sensor (Thermistor) Characteristics

70 60 50

Resistance(kΩ)

40 30 20 10 0

Temperature (ºC)

20 40 60 80 100 120 140

When abnormality indication starts again

Check the outdoor compressor temperature sensor:

● Plug out connector from the outdoor unit PCB

● Measure the resistance of the outdoor compressor temperature sensor

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

Is the measured resistance of the outdoor compressor temperature sensor matches the value specified in its characteristic chart?

Check the connector connection:

● Turn off the power

● Check the connector connection

Is the connector connection normal?

YES

NO NO

YES

● Connector poor contact

● Correct the connection

● Defect in outdoor compressor temperature sensor

● Replace the outdoor compressor temperature sensor

● Defect in outdoor unit PCB

● Replace the outdoor unit PCB Caution

16.4.5 H16 (Outdoor Current Transformer)

Malfunction Decision Conditions

 An input current, detected by Current Transformer CT, is below threshold value when the compressor is operating at certain frequency value for 3 minutes.

Malfunction Caused

 Lack of gas

 Broken CT (current transformer)

 Broken Outdoor PCB Troubleshooting

When abnormality indication starts again

Refer to Service Manual Technical Graph

In forced cooling, check suction ressure

Running current and suction pressure is ● Compressor Lack Compression

● Replace Compressor

● Check & replace defected CT

Running current is much too low and

● Check for gas leaking source; Repair

For safety reason and to prevent component

breakdown, always switch off the power before remove and connect the component.

normal

Suction pressure and running current is

for Temp vs Current and Pressure

versus running current

very low

blockage; Replace defected part(s)

● Capillary tube/expansion valve or replace defected part(s)

suction pressure is much too high Caution

16.4.6 H19 (Indoor Fan Motor – DC Motor Mechanism Locked)

Malfunction Decision Conditions

 The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm)

Malfunction Caused

 Operation stops due to short circuit inside the fan motor winding.

 Operation stops due to breaking of wire inside the fan motor.

 Operation stops due to breaking of fan motor lead wires.

 Operation stops due to Hall IC malfunction.

 Operation error due to faulty indoor unit PCB.

Troubleshooting

When abnormality indication starts again

Turn off power supply and rotate fan by hand

● Replace fan motor Does fan rotate smoothly?

Turn power supply on and operate fan

● Replace indoor PCB

● Replace fan motor

Turn off power supply and disconnect fan motor connector, then turn power on

NO YES

YES NO

Does it rotate? Check the rotation output from fan motor

Is the rotation feedback voltage 5 ~ 15Vdc (pin 6 & 4) generated?

Check the output of fan motor from indoor PCB

Is the motor power supply voltage 280 ~ 340Vdc (pin 1 & 4) generated?

Is the motor control voltage 15.8 ± 1.2Vdc (14.6 ~ 17Vdc) (pin 5 & 4) generated?

NO

YES

NO

Operate the fan, is the rotation command voltage 0.5 ~ 6Vdc (pin 7 & 4) generated?

NO

NO

YES

Caution

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

16.4.7 H23 (Indoor Pipe Temperature Sensor Abnormality)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the temperatures detected by the indoor heat exchanger temperature sensor are used to determine sensor errors.

Malfunction Caused

 Faulty connector connection.

 Faulty sensor.

 Faulty PCB.

Troubleshooting

Sensor (Thermistor) Characteristics

70 60 50

Resistance(kΩ)

Temperature (ºC) 40

30 20 10

-10 0 10 20 30 40 50

0

1 Pipe temp. Sensor 2 Intake Air Temp. Sensor

1 2

When abnormality indication starts again

Check the outdoor air temperature sensor:

● Plug out connector from the outdoor unit PCB

● Measure the resistance of the outdoor intake air temperature sensor

● Defect in outdoor intake air temperature sensor

● Replace the outdoor intake air temperature sensor

● Detect in outdoor unit PCB

● Replace the outdoor unit PCB

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

Check the connector connection:

● Plug out connector from the indoor unit PCB

● Measure the resistance of the indoor pipe temperature sensor

Is the connector connection normal? ● Connector poor contact

● Correct the connection YES

NO

Is the measured resistance of the outdoor intake air temperature sensor matches the value specified in its characteristic chart?

NO

YES

Caution

16.4.8 H27 (Outdoor Air Temperature Sensor Abnormality)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor errors.

Malfunction Caused

 Faulty connector connection.

 Faulty sensor.

 Faulty PCB.

Troubleshooting

Sensor (Thermistor) Characteristics

70 60 50

Resistance(kΩ)

40 30 20 10 0

Temperature (ºC)

-10 0 10 20 30 40 50

1 Outdoor Air Sensor 2 Outdoor Heat Exchanger

Sensor

1

2

When abnormality indication starts again

Check the outdoor air temperature sensor:

● Plug out connector from the outdoor unit PCB

● Measure the resistance of the outdoor air temperature sensor

Is the measured resistance of the outdoor air temperature sensor matches the value specified in its characteristic chart?

● Defect in outdoor air temperature sensor

● Replace the outdoor air temperature sensor

● Defect in outdoor unit PCB

● Replace the outdoor unit PCB

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

Check the connector connection:

● Turn off the power

● Check the connector connection

Is the connector connection normal?

YES

● Connector poor contact

● Correct the connection NO

YES

NO

Caution

16.4.9 H28 (Outdoor Pipe Temperature Sensor Abnormality)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor errors.

Malfunction Caused

 Faulty connector connection.

 Faulty sensor.

 Faulty PCB.

Troubleshooting

Sensor (Therm istor) Characteristics

70 60 50

Resistance(kΩ)

40 30 20 10

0

Temperature (ºC)

-10 0 10 20 30 40 50

1 Outdoor Air Sensor 2 Outdoor Heat Exchanger

Sensor

1

2

Is the measured resistance of the outdoor heat exchanger temperature sensor matches the value specified in its characteristic chart?

YES When abnormality indicationstarts again

Check the outdoor heat exchanger temperature sensor:

● Plug out connector from the outdoor unit PCB

● Measure the resistance of the outdoor heat exchanger temperature sensor

● Defectin outdoor heat exchanger temperaturesensor

● Replace the outdoor heat exchanger temperaturesensor

● Defectin outdoor unit PCB

● Replace the outdoor unit PCB Checkthe connector connection:

● Turn off the power

● Check the connector connection

Is the connector connection normal? ● Connector poor contact

● Correctthe connection No

YES

No

Caution

For safety reason and to prevent

component breakdown, always switch

off the power before remove and

connect the component.

16.4.10 H30 (Compressor Discharge Temperature Sensor Abnormality)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor errors.

Malfunction Caused

 Faulty connector connection.

 Faulty sensor.

 Faulty PCB.

Troubleshooting

When abnormality indication starts again

Check the outdoor discharge pipe temperature sensor:

● Plug out connector from the outdoor unit PCB

● Measure the resistance of the outdoor discharge pipe temperature sensor

Is the measured resistance of the outdoor discharge pipe temperature sensor matches the value specified in its characteristic chart?

● Defect in outdoor discharge pipe

● Replace the outdoor discharge pipe temperature sensor

● Defect in outdoor unit PCB

● Replace the outdoor unit PCB Check the connector connection:

● Turn off the power

● Check the connector connection

Is the connector connection normal?

YES

● Connector poor contact

● Correct the connection NO

NO

YES

temperature sensor Caution

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

16.4.11 H32 (Outdoor Heat Exchanger Temperature Sensor 2 Abnormality)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the temperatures detected by the outdoor heat exchanger temperature sensor are used to determine sensor errors.

Malfunction Caused

 Faulty connector connection.

 Faulty sensor.

 Faulty PCB.

Troubleshooting

When abnormality indication starts again

Check the outdoor discharge pipe temperature sensor:

● Plug out connector from the outdoor unit PCB

● Measure the resistance of the outdoor discharge pipe temperature sensor

Is the measured resistance of the outdoor heat exchanger temperature sensor matches the value specified in its characteristic chart?

● Defect in outdoor discharge pipe

● Replace the outdoor discharge pipe temperature sensor

● Defect in outdoor unit PCB

● Replace the outdoor unit PCB Check the connector connection:

● Turn off the power

● Check the connector connection

Is the connector connection normal?

YES

● Connector poor contact

● Correct the connection NO

NO

YES

temperature sensor Caution

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

16.4.12 H33 (Unspecified Voltage between Indoor and Outdoor)

Malfunction Decision Conditions

 The supply power is detected for its requirement by the indoor/outdoor transmission.

Malfunction Caused

 Wrong models interconnected.

 Wrong indoor unit and outdoor unit PCBs used.

 Indoor unit or outdoor unit PCB defective.

Troubleshooting

When abnormality indication starts again

Is indoor unit and outdoor unit model numbers matched?

NO

Match the compatible model (follow specification) Check indoor and outdoor units model number

Check the indoor and outdoor PCB part number and compare if they matched part list

Change for the specified indoor or outdoor unit PCB

NO

YES Replace the indoor and outdoor unit PCB Caution

For safety reason and to prevent

component breakdown, always switch

off the power before remove and

connect the component.

16.4.13 H34 (Outdoor Heat Sink Temperature Sensor Abnormality)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the temperatures detected by the outdoor heat sink temperature sensor are used to determine sensor errors.

Malfunction Caused

 Faulty connector connection.

 Faulty sensor.

 Faulty PCB.

Troubleshooting

When abnormality indication starts again

Check the outdoor discharge pipe temperature sensor:

● Plug out connector from the outdoor unit PCB

● Measure the resistance of the outdoor discharge pipe temperature sensor

Is the measured resistance of the outdoor gas pipe temperature sensor matches the value specified in its characteristic chart?

● Defect in outdoor discharge pipe

● Replace the outdoor discharge pipe temperature sensor

● Defect in outdoor unit PCB

● Replace the outdoor unit PCB Check the connector connection:

● Turn off the power

● Check the connector connection

Is the connector connection normal?

YES

● Connector poor contact

● Correct the connection NO

NO

YES

temperature sensor Caution

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

16.4.14 H36 (Outdoor Gas Pipe Sensor Abnormality)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the temperatures detected by the outdoor gas pipe temperature sensor are used to determine sensor errors.

Malfunction Caused

 Faulty connector connection.

 Faulty sensor.

 Faulty PCB.

Troubleshooting

When abnormality indication starts again

Check the outdoor discharge pipe temperature sensor:

● Plug out connector from the outdoor unit PCB

● Measure the resistance of the outdoor discharge pipe temperature sensor

Is the measured resistance of the outdoor gas pipe temperature sensor matches the value specified in its characteristic chart?

● Defect in outdoor discharge pipe

● Replace the outdoor discharge pipe temperature sensor

● Defect in outdoor unit PCB

● Replace the outdoor unit PCB Check the connector connection:

● Turn off the power

● Check the connector connection

Is the connector connection normal?

YES

● Connector poor contact

● Correct the connection NO

NO

YES

temperature sensor Caution

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

16.4.15 H37 (Outdoor Liquid Pipe Temperature Sensor Abnormality)

Malfunction Decision Conditions

 During startup and operation of cooling and heating, the temperatures detected by the outdoor liquid pipe temperature sensor are used to determine sensor errors.

Malfunction Caused

 Faulty connector connection.

 Faulty sensor.

 Faulty PCB.

Troubleshooting

When abnormality indication starts again

Check the outdoor discharge pipe temperature sensor:

● Plug out connector from the outdoor unit PCB

● Measure the resistance of the outdoor discharge pipe temperature sensor

Is the measured resistance of the outdoor liquid pipe temperature sensor matches the value specified in its characteristic chart?

● Defect in outdoor discharge pipe

● Replace the outdoor discharge pipe temperature sensor

● Defect in outdoor unit PCB

● Replace the outdoor unit PCB Check the connector connection:

● Turn off the power

● Check the connector connection

Is the connector connection normal?

YES

● Connector poor contact

● Correct the connection NO

NO

YES

temperature sensor Caution

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

16.4.16 H97 (Outdoor Fan Motor – DC Motor Mechanism Locked)

Malfunction Decision Conditions

 The rotation speed detected by the Hall IC during fan motor operation is used to determine abnormal fan motor.

Malfunction Caused

 Operation stops due to short circuit inside the fan motor winding.

 Operation stops due to breaking of wire inside the fan motor.

 Operation stops due to breaking of fan motor lead wires.

 Operation stops due to Hall IC malfunction.

 Operation error due to faulty outdoor unit PCB.

Troubleshooting

YES

NO When abnormality indication starts again

Turn power supply on and operate fan.

Replace fan motor

For safety reason and to prevent component breakdown, always switch off the power before remove and connect the component.

Caution

Does fan rotate smoothly?

NO Replace outdoor PCB Turn off power supply and rotate fan by

hand

Does it rotate ?

CN-MTR2 (WHT)

IC19 3

5

1 10

14 16 W U V FAN MOTOR

MS3 ~

CN-MTR1

PCB BOARD 5

4 3 2 1

C173 5V

R105 1k

C1760.01µ 50V G5 R111

1k

C1770.01µ 50V G5 R120

1k

C1750.01µ 50V G5 G5 +

YES

NO

YES Turn off power supply and disconnect fan motor CN-MRT2

Check resistance of the motor.

Measure at fan motor connector CN-MRT1 (1-2, 1-3, 2-3).

Replace outdoor PCB NO Replace fan motor

YES

NO Replace fan motor

Replace fan motor NO Replace outdoor PCB Stop the fan motor

YES

YES Is the resistance normal?

Check the rotation feedback output from fan motor’s CN-MTR1 output.

Rotate the fan motor manually (by hand) while measure the voltage at PCB’s CN-MRT1

- Between 1(+) and 5(-) - Between 2(+) and 5(-) - Between 3(+) and 5(-)

Use an inverter check to check on the power transistor on board.

Do all 6 LED light turn ON and turn OFF periodically?

Measure CN-MRT1 (pin 4 & 5) Is the DC voltage ~5Vdc?

Does the voltage at each terminal becomes 5 and 0Vdc repeatedly?

Connect it to PCB’s CN-MRT2 port.

Turn power ON and run the unit connector

16.4.17 H98 (Error Code Stored in Memory and no alarm is triggered / no TIMER LED flashing)

Malfunction Decision Conditions

 Indoor high pressure is detected when indoor heat exchanger is detecting very high temperature when the unit is operating in heating operation.

 Phenomena: unit is stopping and re-starting very often in heating mode Malfunction Caused

 Indoor heat exchanger thermistor

 Clogged air filter or heat exchanger

 Over-bent pipe (liquid side) Troubleshooting

NO

NO

YES

When abnormality indication starts again

Check the indoor unit intake air filter

Is the air filter dirty? ● Clean the air filter

● Clean the indoor unit heat exchanger YES

Check the dust accumulation on the indoor unit heat exchanger

Is the indoor unit heat exchanger dirty?

● Defect in indoor pipe temperature NO

Check the indoor pipe temperature thermistor:

● Check the piping & installation condition YES

Is the measured resistance of the indoor pipe temperature

● Plug out connector (CN-TH) from the indoor unit PCB

● Measure the resistance of the indoor heat exchanger temperature thermistor

thermistor matches the value specified in its characteristic chart?

thermistor

● Replace the indoor pipe temperature thermistor

● Replace piping / reinstall the unit if necessary

Caution

For safety reason and to prevent

component breakdown, always switch

off the power before remove and

connect the component.