Table 60 Liebert XDH20 specifications
Models
XDH20BK1 XDH20SK1
(60Hz)
XDH20BS1 XDH20SS1 (50/60Hz)
Cooling Capacity
XDH20, 60Hz Nominal (98ºF [37°C] EAT): 22kW/6.3 Tons XDH20, 60Hz Maximum(105ºF [41°C] EAT): 25.3kW/7.2 Tons XDH20, 50Hz Nominal (98ºF [37°C] EAT): 21.6kW / 6.1 Tons XDH20, 50Hz Maximum(105ºF [41°C] EAT): 25.3kW/7.2 Tons Conditions
Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew point
Electrical Requirements
Input 120V-1ph-60Hz 220-240V-1ph-50Hz, CE /
208-240V-1ph-60Hz, CSA Input Power Connections Two IEC320-C14 power inlets and two IEC
power cords with NEMA 5-15P plugs
Two IEC320-C14 power inlets and two IEC power cords with IEC320-C14 plugs
Full Load Amps 5 2.5
Power Consumption,
Nominal, Watts 600 575
Dimensions, inches (mm)
Height—Module Only 78 (1981)
Height—Including
Pipe Connections 80 (2032)
Width 12 (305)
Depth 42 (1067)
Weight, lb (kg)
Module Only 233 (106) 233 (106)
Shipping Weight 317 (144) 317 (144)
Number of Fans 6
Airflow, Nominal, ft3/min
(m3/hr) 2500 (4248) 2428 (4125)
Audible Noise, Sound Power 81 dBa 81 dBa
Pipe Connections
Refrigerant Supply 1/2" OD, Cu
Refrigerant Return 7/8" OD, Cu
Serviceable Parts Fans and electrical components
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat Options
Smart Module control
board (factory-installed) Dry contact (24VAC - 1A maximum) Pre-Charged Refrigerant R-134a refrigerant, one-shot connections
Air Diffusers Uni-directional or bi-directional Agency
Approvals CSA 60Hz CE 50Hz, CSA 50/60Hz
1. Refer to Figure 137 for complete part number.
Table 61 Liebert XDH32 specifications
Models
XDH32BK1 XDH32SK1
(60Hz)
XDH32BS1 XDH32SS1 (50/60Hz)
Cooling Capacity
XDH32, 60Hz Nominal (98ºF [37°C] EAT): 30kW/8.5 Tons XDH32, 60Hz Maximum(105ºF [41°C] EAT): 34kW/9.7 Tons
XDH32, 50Hz Nominal (98ºF [37°C] EAT): 30kW / 8.5 Tons XDH32, 50Hz Maximum(103ºF [39°C] EAT): 34kW/9.7 Tons Conditions
Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew point
Electrical Requirements
Input 120V-1ph-60Hz 220-240V-1ph-50Hz, CE /
208-240V-1ph-60Hz, CSA Input Power Connections Two IEC320-C14 power inlets and two IEC
power cords with NEMA 5-15P plugs
Two IEC320-C14 power inlets and two IEC power cords with IEC320-C14 plugs
Full Load Amps 10 5
Power Consumption,
Nominal, Watts 1200 1150
Dimensions, inches (mm)
Height—Module Only 78 (1981)
Height—Including
Pipe Connections 80 (2032)
Width 12 (305)
Depth 42 (1067)
Weight, lb (kg)
Module Only 246 (112) 246 (112)
Shipping Weight 330 (150) 330 (150)
Number of Fans 6
Airflow, Nominal,
ft3/min (m3/hr) 4000 (6796) 3850 (6541)
Audible Noise,
Sound Power 86 dBa 86 dBa
Pipe Connections
Refrigerant Supply 1/2" OD, Cu
Refrigerant Return 7/8" OD, Cu
Serviceable Parts Fans and electrical components
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat Options
Smart Module control
board (factory-installed) Dry contact (24VAC - 1A maximum) Pre-Charged Refrigerant R-134a refrigerant, one-shot connections
Air Diffusers Uni-directional or bi-directional Agency
Approvals CSA 60Hz CE 50Hz, CSA 50/60Hz
1. Refer to Figure 137 for complete part number.
Figure 137 Liebert XDH model number nomenclature
XD H 32 B K —
Horizontal row cooler
K = 120V-1ph-60Hz S = 208-240-1ph-60Hz
220-240-1ph-50Hz
— = Hard piped P = Pre-charged
One-Shot Coupling R = Removable Coupling Liebert
Xtreme heat density system
20 = Model size 32 = Model size
*
Revision level B = Basic module
S = Smart module
—
— = Domestic packaging E = Export packaging
Example: XDH32BK— —*
Table 62 Liebert XDO16 specifications
Models
XDO16BK1 XDO16SK1
(60Hz)
XDO16BS1 XDO16SS1
(60Hz)
XDO16BS1 XDO16SS1
(50Hz)
Cooling Capacity
Nominal (85°F [29.4°C] EAT): 16kW / 4.5 Tons Maximum (90°F [32°C] EAT): 17.3 kW / 4.9 Tons
Nominal (85°F [29.4°C]
EAT): 14kW/4.0Tons Maximum (93°F [34°C]
EAT): 17.3 kW / 4.9 Tons Conditions Capacity rating is @ 55°F (13°C) Entering Fluid Temperature and 50ºF or lower dew point Electrical Requirements
Input Voltage 1ph-60Hz-120V 1ph-60 Hz-220-240V 1ph-50 Hz-220-240V Input Power Connections Terminal blocks provided internal to module
Full Load Amps 2.7A @ 120V 1.50 @ 230V 1.50 @ 230V
Wire Size Amps 3.4 2.0 2.0
Overcurrent Protection Device 15 15 15
Power consumption,
nominal, watts 335 350 350
Dimensions, inches (mm)
Length 72-1/4 (1835)
Width 24-1/8 (613)
Height 22-1/2 (572) not including electrical and piping access Weight, lb (kg)
Module only 150 (68)
Shipping weight 238 (108) 296 (134)
Installed, with refrigerant,
without options 155 (70)
Number of Fans 1 1 1
Airflow, Nominal, ft3/ min
(m3/ hr) 2700 (4587) 2250 (3822)
Audible Noise 85 dBa sound power 83 dBa sound power
Pipe Connections
Refrigerant Supply
from Liebert XDP/Liebert XDC 1/2" OD, Copper
Refrigerant Return
to Liebert XDP/Liebert XDC 7/8" OD, Copper
Serviceable Parts Fan and electrical components
Exterior Finish – Bottom,
Sides, Front and Rear Black, matte finish, heat-fused powder coat
Exterior Finish - Top Hot-dipped galvanized steel
Agency
Approvals CSA 60 Hz CSA 60Hz CE 50Hz
1. Refer to Figure 138 for full part number.
Table 63 Liebert XDO20 specifications
Models
XDO20BK1 XDO20SK1
XDO20BS1 XDO20SS1
60Hz 60Hz 50Hz
Cooling Capacity
Nominal (92°F [33°C] EAT): 20kW / 5.7 Tons Maximum (100°F [38°C] EAT): 23.1kW / 6.6 Tons
Nominal (92°F [33°C] EAT):
17.7kW / 5 Tons Maximum (103°F [39°C]
EAT): 23.1kW / 6.6 Tons Conditions
Capacity rating is @ 55ºF (13°C) Entering Fluid Temperature and 50ºF (10°C) or lower dew point
Electrical Requirements
Input Voltage 1ph-60Hz-120V 1ph-60Hz-220-240V 1ph-50 Hz-220-240V Input Power Connections Terminal blocks provided internal to module
Full Load Amps 2.7A @ 120V 1.64A @ 230V 1.64A @ 230V
Wire Size Amps 3.4 2.0 2.0
Overcurrent Protection Device 15 15 15
Power consumption,
nominal, watts 335 350 350
Dimensions, inches (mm)
Length 72-1/4 (1835)
Width 24-1/8 (613)
Height 22-1/2 (572) not including electrical and piping access Weight, lb (kg)
Module only 150 (68)
Shipping weight 238 (108) 296 (134)
Installed, with refrigerant,
without options 155 (70)
Number of Fans 1 1 1
Airflow, Nominal, ft3/ min
(m3/ hr) 2700 (4590) 2250 (3820)
Audible Noise 85 dBa sound power 83 dBa sound power
Pipe Connections (without flex pipe) Refrigerant Supply
from Liebert XDP/Liebert XDC 1/2" OD, Copper
Refrigerant Return
to Liebert XDP/Liebert XDC 7/8" OD, Copper
Serviceable Parts Fan and electrical components
Exterior Finish – Bottom,
Sides, Front and Rear Black matte finish, heat-fused powder coat
Exterior Finish - Top Hot-dipped galvanized steel
Agency
Approvals CSA 60 Hz CE 50Hz
1. Refer to Figure 138 for full part number.
Figure 138 Liebert XDO model number nomenclature
Table 64 Options for Liebert XDO20 and Liebert XDO16
Option Liebert XDO - 60Hz Models Liebert XDO - 50Hz Models Lighting Fixtures (ship loose) 2 Liebert XDOs per lighting unit; 120V or 277V; 4’ standard fluorescent tubes (not
included) Power, optional lighting fixture 0.9A per 120V light fixture;
0.4A per 277V light fixture None
Smart Module control board
(factory-installed) Dry contact 24VAC - 1A maximum
Pre-Charged Refrigerant R-134a Refrigerant, one-shot connections Table 65 Liebert XDO dimensions—domestic and export
Model
Shipping Dimensions, inches (mm)
Module Dimension Unpacked, inches (mm)
Domestic Export
Length Width Height Length Width Height Length Width Height * All Models 84 (2134) 30 (762) 30 (762) 83 (2108) 30 (762) 30 (762) 72-1/4
(1835)
24-1/8 (613)
25-1/2 (648)
* Includes piping connections
XD 20 K *
16 = Model size 20 = Model size
Revision level Liebert Xtreme
heat density system
Example: XDO20BK– –*
O
Overhead cooling module
B
B = Basic module S = Smart module
–
- = Domestic Packaging E = Export Packaging
–
— = Hard-Piped P = Pre-charged
One-Shot Coupling R = Removable Coupling K = 120V-1ph-60Hz
S = 220-240V-1ph-60Hz, 220-240V-1ph- 50Hz
*
Revision level
Figure 139 Liebert XDR model number nomenclature Table 66 Liebert XDR20 specifications
Models XDR20B1- * XDR20B1P *
(Precharged R134a) XDR20B1R * Cooling Capacity, Nominal,
rated at 104ºF (40°C) EAT & 2400ft3/m (68m3/m) 20.5 kW (5.8 tons) Conditions
55°F (13°C) entering fluid temperature 50°F (10°C) or lower dew point Dimensions, inches (mm)
Height, Including Pipe Connections 82-3/8 (2093) 83-1/2 (2121) 80 (2032)
Width With Handles Attached 27-3/8 (695)
Handles Removed 23-1/2 (597)
Depth 6-1/2 (165)
Shipping Length 90 (2286)
Shipping Width 30-1/2 (775)
Shipping Depth 15-1/2 (394)
Max Shipping Depth (4 modules) 62 (1575)
Weight, lb (kg)
Module Only 130 (59) 133 (60) 130 (59)
Shipping 225 (103) 228 (104) 225 (103)
Pipe Connections
Refrigerant Supply 1/2" OD Type ACR Refrigerant Return 7/8" OD Type ACR
Exterior Finish Black Matte, Heat-Fused Powder Coat
Safety CSA, CE Approved
* Refer to Figure 139 for the complete part number.
Table 67 Liebert XDR rack mounting kit
Rack Part #
Knurr Miracel 198163G1
Dell PowerEdge 4210 199050G1
HP 10642 199051G1
APC AR3100 199054G1
XD 20 B
20 = Model Size Liebert
Xtreme heat density system
Example: XDR20B1R — *
R
Rear Cooling Module
—
- = Domestic Packaging E = Export Packaging
1
1 = Standard
B = Basic Module
*
Revision level
R
- = Hard-Piping
P = Pre-Charged One-Shot Coupling
R = Removable Coupling
Table 68 Liebert XDV8 specifications
Models
XDV8BK1 XDV8SK1
XDV8BT1 XDV8ST1
XDV8BS1 XDV8SS1
60 Hz 60 Hz 50 Hz 50 Hz
Cooling Capacity
Nominal (92°F [33°C] EAT): 8kW / 2.3 Tons Maximum (95°F [35°C] EAT): 8.7kW / 2.5 Tons
Nominal (92°F [33°C] EAT): 7kW/ 2.0 Tons Maximum (103°F [39°C] EAT): 8.7kW/2.5Tons Conditions
Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew point, rear air inlet.
Electrical Requirements
Input 120V model: 1ph-60 Hz 230V model: 1ph-60
Hz 230V model: 1ph-50 Hz
Input power connections 2 power connections, each model
Full Load Amps 120V model: 2.0A 230V model: 1.0A
Power consumption,
nominal, watts 180 190 190 190
Dimensions, in. (mm)
Height – module only 14 (355) not including pipe connections Height – including pipe
connections 18-5/8 (473)
Width 22-7/8 (581)
Depth – Top 39-1/2 (1003)
Depth – Bottom 29-5/8 (752)
Weight, lb (kg)
Module only 77 (35)
Shipping weight 125 (57)
Installed, with
refrigerant 79 (36)
Number of Fans 2 2 2 2
Airflow, Nominal, ft3/ min (m3/ hr)
1000 (1699) with rear inlet.
Bottom inlet airflow may be less, depending on restrictions inside cabinet
833 (1415) with rear inlet.
Bottom inlet airflow may be less, depending on restrictions inside cabinet
Audible noise 78 dBa sound power 73 dBa sound power
Pipe Connections (without Liebert Flex Pipe) Refrigerant Supply
from Liebert XDP/Liebert XDC
1/2" OD Cu, (optional 1/2" threaded coupler flex piping) Refrigerant Return
to Liebert XDP/Liebert XDC
5/8" OD Cu, (optional 3/4" threaded coupler flex piping)
Serviceable Parts Fans and electrical components
Cabinet Exterior
Finish Black, matte finish, heat-fused powder coat
Options
Smart Module control
board (factory-installed) Dry contact, 24VAC, 1A maximum
Pre-Charged
Refrigerant R-134a refrigerant, one-shot connections Agency
Approvals CSA 60Hz CSA 50Hz CE 50Hz
1. Refer to Figure 140 for complete part number.
Table 69 Liebert XDV10 specifications
Models
XDV10BK1 XDV10SK1
XDV10BT1 XDV10ST1
XDV10BS1 XDV10SS1
60 Hz 60 Hz 50 Hz 50 Hz
Cooling Capacity
Nominal (98ºF [37ºC] EAT: 10kW / 2.8 Tons Maximum (106ºF [41ºC] EAT): 11.7kW/3.3 Tons
Nominal (98ºF [37ºC] EAT): 8.3kW / 2.4 Tons Maximum (116ºF [47ºC] EAT): 11.7kW/3.3 Tons Conditions
Capacity Rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew point, rear air inlet.
Electrical Requirements
Input 120V model: 1ph-60 Hz 230V model: 1ph-60 Hz 230V model: 1ph-50 Hz
Input power connections 2 power connections, each model
Full Load Amps 120V model: 2.0A 230V model: 1.0A
Power consumption,
nominal, watts 180 190 190 190
Dimensions, in. (mm)
Height – module only 14 (355) not including pipe connections Height – including hard
pipe connections 18-5/8 (473)
Height – including one-
shot connections 19-5/8 (498)
Width 22-7/8 (581)
Depth – Top 39-1/2 (1003)
Depth – Bottom 29-5/8 (752)
Weight, lb (kg)
Module only 77 (35)
Shipping weight 125 (57)
Installed, with refrigerant 79 (36)
Number of fans 2 2 2 2
Airflow, Nominal, ft3/ min (m3/ hr)
1000 (1699) with rear inlet.
Bottom inlet airflow may be less, depending on restrictions inside cabinet
833 (1415) with rear inlet.
Bottom inlet airflow may be less, depending on restrictions inside cabinet
Audible noise 78 dBa sound power 73 dBa sound power
Pipe Connections (without Liebert Flex Pipe) Refrigerant supply
from Liebert XDP/ XDC 1/2" OD, Cu, (optional 1/2" threaded coupler flex piping) Refrigerant return
to Liebert XDP/ XDC 5/8" OD, Cu, (optional 3/4" threaded coupler flex piping)
Serviceable Parts Fans and electrical components
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat Options
Smart Module control
board (factory-installed) Dry contact, 24VAC, 1A maximum Pre-Charged Refrigerant R-134a refrigerant, one-shot connections Agency
Approvals CSA 60Hz CSA 50Hz CE 50Hz
1. Refer to Figure 140 for complete part number.
Figure 140 Liebert XDV model number nomenclature Table 70 Liebert XDV dimensions—domestic and export
Model
Shipping Dimensions Length x Width x Height
inches (mm)
Module Dimensions Unpacked Length x Width x Height
inches (mm)
Domestic Export Module Only
All Models 48 x 40 x 24-1/4 (1219 x 1016 x 616)
45-4/5 x 30-3/4 x 33 (1163 x 781 x 839mm)
39-1/2 x 22-7/8 x 14 (1003 x 581 x 356)
XD V B K —
Vertical top cooler
K = 120V-1ph-60Hz S = 230V, 1ph-50Hz T = 208-240V-1ph-60Hz,
220-240-1ph-50Hz
— = Hard piped P = Pre-charged
One-Shot Coupling R = Removable coupling Liebert Xtreme
heat density system
*
Revision level B = Basic module
S = Smart module
—
— = Domestic Packaging E = Export
Packaging
Example: XDV10BK– –*
10
8 = Model size 10 = Model Size
Table 71 Liebert XDC160 specifications
Models
XDC160 Air XDC160 Water / Glycol
XDC160AA XDC160AM
189192G3 (90-100°F) 189192G5 (65-85°F)
Cooling Capacity, tons (kW)
46 (160) 37 (130)
See Tables 72,73 and74 for Water/Glycol
performance data Minimum Load 40% of system nominal capacity (64 kW for 60Hz unit)
Electrical Requirements
Input 460V-3ph-60Hz 380/415V-3ph-50Hz 460V-3ph-60Hz
Full Load Amps 79A
Minimum supply wire sizing ampacity 84A
Maximum fuse or circuit breaker size 100A
Dimensions, inches (mm)
Height - Main unit only 78 (1981)
Height - Main unit only, as shipped 83 (2108)
Width - Main unit 74 (1879)
Depth - Main unit 34-5/8 (879)
Height - Water/Glycol-Cooled Condenser Stand N/A 24 (607)
Width - Water/Glycol-Cooled Condenser Stand N/A 72 (1829)
Depth - Water/Glycol-Cooled Condenser Stand N/A 33 (839)
Weight, lb (kg)
Main unit only 1800 (817)
Main unit only, as shipped Domestic: 1945 (882); Export: 2093 (949)
Water/Glycol-Cooled Condenser Stand N/A 1075 (488)
Water/Glycol-Cooled Condenser Stand, as shipped N/A 1150 (521)
Pipe Connections, inches, O.D., Cu
Liebert XD Coolant supply to Liebert XD cooling
modules 1-1/8
Liebert XD Coolant return from Liebert XD cooling
modules 2-1/8
Liquid line, DX circuit 7/8
Hot gas line, DX circuit 1-3/8
Heat Rejection Equipment
95°F (35°C) ambient air-cooled condenser 2-DCSL415 N/A
105°F (41°C) ambient air-cooled condenser 2 -DCSL616 N/A
Number of Liebert XD Cooling Modules Connected, Maximum (Minimum)
Liebert XDCF10 16 (6)
Liebert XDH20 8 (4)
Liebert XDH32 5 (2)
Liebert XDO16 10 (4)
Liebert XDO20 8 (4)
Liebert XDV8 20 (8)
Liebert XDV10 16 (7)
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat Maximum Ambient Operating Temperature °F (°C) 86 (30)
Agency
Approvals CSA CE CSA
Table 72 Floor stand specifications—water-cooled Liebert XDC
XDC160 Water Floor Stand - 60Hz
189192G5 189192G3
Entering Fluid Temp °F (°C) 65 (18) 70 (21) 75 (24) 85 (29) 95 (35) Performance Data
Cooling capacity, tons (kW) 46.1(162.3) 46.1(162.3) 46.1(162.3) 46.1(162.3) 44.5(156.5)
Flow, GPM 50 58 70 110 142
Pressure Drop, psi (Ft Water) 2.7 (6.2) 4.9 (11.3) 5.4 (12.5) 20.7 (47.8) 27.3 (63.1) Heat Rejection Equipment
Water regulating valve size 1" 1" 1" 1" 1"
Piping Connections
Water / glycol supply and return lines 2-1/8" 2-1/8" 2-1/8" 2-1/8" 2-1/8"
Table 73 Floor stand specifications—Liebert XDC with 40% propylene glycol
XDC160 Glycol Floor Stand - 60Hz - 40% PG 189192G3
Outside Ambient °F (°C) 95 (35) 100 (38) 105 (41)
Max Entering Fluid Temp °F (°C) 110 (43) 110 (43) 110 (43) Performance Data
Cooling capacity, tons (kW) 42.5 (149.4)
Total Heat Rejection, (kW) 192.6
Flow, GPM 206
Pressure Drop, psi (ft water) 37.2 (85.9)
Heat Rejection Equipment
Drycooler DDNT 940A 2 x DDNT 880A*
Drycooler Pressure Drop, psi (ft water) 6.7 (15.8) 2.9 (6.6) Glycol pump package - 10hp 460V - D10ANTS1317; 208V - D10YNTS1317
Pump Control Package - 208V RP020HY04S0758
Pump Control Package - 460V RP020HA08S0758
Pump Total Head @ 206 GPM, ft water 145
Water regulating valve size 1-1/4"
Piping Connections
Water / glycol supply and return lines 2-5/8"
* When multiple drycoolers are used, ensure flow is balanced.
Figure 141 Liebert XDC model number nomenclature
Table 74 Floor stand specifications—Liebert XDC with 40% ethylene glycol
XDC160 Glycol Floor Stand - 60Hz - 40% EG 189192G3
Outside Ambient °F (°C) 95 (35) 100 (38) 105 (41)
Max Entering Fluid Temp °F (°C) 110 (43) 110 (43) 110 (43) Performance Data
Cooling capacity, tons (kW) 42.5 (149.4)
Total Heat Rejection, (kW) 192.6
Flow, GPM 204
Pressure Drop, psi (ft water) 35.9 (82.9)
Heat Rejection Equipment
Drycooler DDNT 940A 2 x DDNT 880A*
Drycooler Pressure Drop, psi (ft water) 6.5 (15.1) 2.7 (6.3) Glycol pump package - 10HP 460V - D10ANTS1317; 208V - D10YNTS1317
Pump Control Package - 208V RP020HY04S0758
Pump Control Package - 460V RP020HA08S0758
Pump Total Head @ 204 GPM, ft water 145
Water regulating valve size 1-1/4"
Piping Connections
Water / glycol supply and return lines 2-5/8"
* When multiple drycoolers are used ensure flow is balanced.
A
Place holder
XD C 160 – *
Chiller unit
Revision level Liebert
Xtreme heat Density system
Place holder
Example: XDC160AA– –*
A
Voltage-phase-frequency A = 460V-3ph-60Hz M = 380/415-3ph-50Hz
–
Place holder Model size
Table 75 Liebert XDP160 specifications
Models XDP160RC--3 XDP160RA--3 XDP160RM--3
Cooling Capacity, Nominal
160kW / 46 Tons, 60Hz 140kW / 40 Tons, 50Hz Each capacity is based on 45ºF (7ºC) entering water temperature and 140gpm (530lpm) water flow rate. Capacity is reduced when glycol mixtures
are used in place of 100% water.
Minimum Load 30% of nominal system capacity or 48kW (163,800BTU/H) Electrical Requirements
Input 208V/3ph/60Hz 460V/3/ph60Hz 380/415V/3ph/50Hz
Full Load Amps 4A 2.1A 2.3A
Dimensions, inches (mm)
Height – Unit only 78 (1981)
Height – As shipped 83 (2108)
Width 38 (965)
Depth 34 (864)
Weight, lb (kg)
Unit only 821 (372)
Shipping weight Domestic: 990 (449); Export: 1067 (484) Installed, with refrigerant and chilled water 1038 (471)
Pipe Connections
Refrigerant supply to Liebert XD cooling
module 1-1/8" OD, Cu
Refrigerant return from Liebert XD cooling
module 2-1/8" OD, Cu
Chilled water supply and return 2-5/8" OD, Cu Control valve
2-way, 2" nominal; 35 PSIG close-off pressure rating;
150 PSIG maximum allowable pressure Pressure Drop – Chilled Water Side
20 psig (137kPa, 1.38bar), with 140 gpm (530lpm) water flow rate, control valve fully open
Temperature Rise – Chilled Water Side
at rated flow, °F (°C) 8.0 (4.4) 6.9 (3.8)
Number of Liebert XD Cooling Modules Connected, Maximum (Minimum)
Liebert XDCF10 16 (5)
Liebert XDH20 8 (3)
Liebert XDH32 5 (2)
Liebert XDV8 20 (6)
Liebert XDV10 16 (5)
Liebert XDO16 10 (3)
Liebert XDO20 8 (3)
Cabinet Exterior Finish Black, matte finish, heat-fused powder coat Operating Ambient
Temperature, Maximum, °F (°C) 86 (30)
Agency
Approvals CSA 60Hz CE 50Hz
Figure 142 Liebert XDP model number nomenclature
R
Pump Redundancy
XD P 160 – *
Pumping unit
Revision level
Model size Place holder
Example: XDP160RA– –*
A
Voltage-phase-frequency A = 460V-3ph-60Hz C = 208V-3ph-60Hz M = 380/415-3ph-50Hz
–
Place holder
Liebert Xtreme heat Density system