• No results found

S PECIFICATIONS AND M ODEL N UMBER N OMENCLATURE

In document System Design Manual (сторінка 159-176)

Table 60 Liebert XDH20 specifications

Models

XDH20BK1 XDH20SK1

(60Hz)

XDH20BS1 XDH20SS1 (50/60Hz)

Cooling Capacity

XDH20, 60Hz Nominal (98ºF [37°C] EAT): 22kW/6.3 Tons XDH20, 60Hz Maximum(105ºF [41°C] EAT): 25.3kW/7.2 Tons XDH20, 50Hz Nominal (98ºF [37°C] EAT): 21.6kW / 6.1 Tons XDH20, 50Hz Maximum(105ºF [41°C] EAT): 25.3kW/7.2 Tons Conditions

Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew point

Electrical Requirements

Input 120V-1ph-60Hz 220-240V-1ph-50Hz, CE /

208-240V-1ph-60Hz, CSA Input Power Connections Two IEC320-C14 power inlets and two IEC

power cords with NEMA 5-15P plugs

Two IEC320-C14 power inlets and two IEC power cords with IEC320-C14 plugs

Full Load Amps 5 2.5

Power Consumption,

Nominal, Watts 600 575

Dimensions, inches (mm)

Height—Module Only 78 (1981)

Height—Including

Pipe Connections 80 (2032)

Width 12 (305)

Depth 42 (1067)

Weight, lb (kg)

Module Only 233 (106) 233 (106)

Shipping Weight 317 (144) 317 (144)

Number of Fans 6

Airflow, Nominal, ft3/min

(m3/hr) 2500 (4248) 2428 (4125)

Audible Noise, Sound Power 81 dBa 81 dBa

Pipe Connections

Refrigerant Supply 1/2" OD, Cu

Refrigerant Return 7/8" OD, Cu

Serviceable Parts Fans and electrical components

Cabinet Exterior Finish Black, matte finish, heat-fused powder coat Options

Smart Module control

board (factory-installed) Dry contact (24VAC - 1A maximum) Pre-Charged Refrigerant R-134a refrigerant, one-shot connections

Air Diffusers Uni-directional or bi-directional Agency

Approvals CSA 60Hz CE 50Hz, CSA 50/60Hz

1. Refer to Figure 137 for complete part number.

Table 61 Liebert XDH32 specifications

Models

XDH32BK1 XDH32SK1

(60Hz)

XDH32BS1 XDH32SS1 (50/60Hz)

Cooling Capacity

XDH32, 60Hz Nominal (98ºF [37°C] EAT): 30kW/8.5 Tons XDH32, 60Hz Maximum(105ºF [41°C] EAT): 34kW/9.7 Tons

XDH32, 50Hz Nominal (98ºF [37°C] EAT): 30kW / 8.5 Tons XDH32, 50Hz Maximum(103ºF [39°C] EAT): 34kW/9.7 Tons Conditions

Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew point

Electrical Requirements

Input 120V-1ph-60Hz 220-240V-1ph-50Hz, CE /

208-240V-1ph-60Hz, CSA Input Power Connections Two IEC320-C14 power inlets and two IEC

power cords with NEMA 5-15P plugs

Two IEC320-C14 power inlets and two IEC power cords with IEC320-C14 plugs

Full Load Amps 10 5

Power Consumption,

Nominal, Watts 1200 1150

Dimensions, inches (mm)

Height—Module Only 78 (1981)

Height—Including

Pipe Connections 80 (2032)

Width 12 (305)

Depth 42 (1067)

Weight, lb (kg)

Module Only 246 (112) 246 (112)

Shipping Weight 330 (150) 330 (150)

Number of Fans 6

Airflow, Nominal,

ft3/min (m3/hr) 4000 (6796) 3850 (6541)

Audible Noise,

Sound Power 86 dBa 86 dBa

Pipe Connections

Refrigerant Supply 1/2" OD, Cu

Refrigerant Return 7/8" OD, Cu

Serviceable Parts Fans and electrical components

Cabinet Exterior Finish Black, matte finish, heat-fused powder coat Options

Smart Module control

board (factory-installed) Dry contact (24VAC - 1A maximum) Pre-Charged Refrigerant R-134a refrigerant, one-shot connections

Air Diffusers Uni-directional or bi-directional Agency

Approvals CSA 60Hz CE 50Hz, CSA 50/60Hz

1. Refer to Figure 137 for complete part number.

Figure 137 Liebert XDH model number nomenclature

XD H 32 B K

Horizontal row cooler

K = 120V-1ph-60Hz S = 208-240-1ph-60Hz

220-240-1ph-50Hz

— = Hard piped P = Pre-charged

One-Shot Coupling R = Removable Coupling Liebert

Xtreme heat density system

20 = Model size 32 = Model size

*

Revision level B = Basic module

S = Smart module

— = Domestic packaging E = Export packaging

Example: XDH32BK— —*

Table 62 Liebert XDO16 specifications

Models

XDO16BK1 XDO16SK1

(60Hz)

XDO16BS1 XDO16SS1

(60Hz)

XDO16BS1 XDO16SS1

(50Hz)

Cooling Capacity

Nominal (85°F [29.4°C] EAT): 16kW / 4.5 Tons Maximum (90°F [32°C] EAT): 17.3 kW / 4.9 Tons

Nominal (85°F [29.4°C]

EAT): 14kW/4.0Tons Maximum (93°F [34°C]

EAT): 17.3 kW / 4.9 Tons Conditions Capacity rating is @ 55°F (13°C) Entering Fluid Temperature and 50ºF or lower dew point Electrical Requirements

Input Voltage 1ph-60Hz-120V 1ph-60 Hz-220-240V 1ph-50 Hz-220-240V Input Power Connections Terminal blocks provided internal to module

Full Load Amps 2.7A @ 120V 1.50 @ 230V 1.50 @ 230V

Wire Size Amps 3.4 2.0 2.0

Overcurrent Protection Device 15 15 15

Power consumption,

nominal, watts 335 350 350

Dimensions, inches (mm)

Length 72-1/4 (1835)

Width 24-1/8 (613)

Height 22-1/2 (572) not including electrical and piping access Weight, lb (kg)

Module only 150 (68)

Shipping weight 238 (108) 296 (134)

Installed, with refrigerant,

without options 155 (70)

Number of Fans 1 1 1

Airflow, Nominal, ft3/ min

(m3/ hr) 2700 (4587) 2250 (3822)

Audible Noise 85 dBa sound power 83 dBa sound power

Pipe Connections

Refrigerant Supply

from Liebert XDP/Liebert XDC 1/2" OD, Copper

Refrigerant Return

to Liebert XDP/Liebert XDC 7/8" OD, Copper

Serviceable Parts Fan and electrical components

Exterior Finish – Bottom,

Sides, Front and Rear Black, matte finish, heat-fused powder coat

Exterior Finish - Top Hot-dipped galvanized steel

Agency

Approvals CSA 60 Hz CSA 60Hz CE 50Hz

1. Refer to Figure 138 for full part number.

Table 63 Liebert XDO20 specifications

Models

XDO20BK1 XDO20SK1

XDO20BS1 XDO20SS1

60Hz 60Hz 50Hz

Cooling Capacity

Nominal (92°F [33°C] EAT): 20kW / 5.7 Tons Maximum (100°F [38°C] EAT): 23.1kW / 6.6 Tons

Nominal (92°F [33°C] EAT):

17.7kW / 5 Tons Maximum (103°F [39°C]

EAT): 23.1kW / 6.6 Tons Conditions

Capacity rating is @ 55ºF (13°C) Entering Fluid Temperature and 50ºF (10°C) or lower dew point

Electrical Requirements

Input Voltage 1ph-60Hz-120V 1ph-60Hz-220-240V 1ph-50 Hz-220-240V Input Power Connections Terminal blocks provided internal to module

Full Load Amps 2.7A @ 120V 1.64A @ 230V 1.64A @ 230V

Wire Size Amps 3.4 2.0 2.0

Overcurrent Protection Device 15 15 15

Power consumption,

nominal, watts 335 350 350

Dimensions, inches (mm)

Length 72-1/4 (1835)

Width 24-1/8 (613)

Height 22-1/2 (572) not including electrical and piping access Weight, lb (kg)

Module only 150 (68)

Shipping weight 238 (108) 296 (134)

Installed, with refrigerant,

without options 155 (70)

Number of Fans 1 1 1

Airflow, Nominal, ft3/ min

(m3/ hr) 2700 (4590) 2250 (3820)

Audible Noise 85 dBa sound power 83 dBa sound power

Pipe Connections (without flex pipe) Refrigerant Supply

from Liebert XDP/Liebert XDC 1/2" OD, Copper

Refrigerant Return

to Liebert XDP/Liebert XDC 7/8" OD, Copper

Serviceable Parts Fan and electrical components

Exterior Finish – Bottom,

Sides, Front and Rear Black matte finish, heat-fused powder coat

Exterior Finish - Top Hot-dipped galvanized steel

Agency

Approvals CSA 60 Hz CE 50Hz

1. Refer to Figure 138 for full part number.

Figure 138 Liebert XDO model number nomenclature

Table 64 Options for Liebert XDO20 and Liebert XDO16

Option Liebert XDO - 60Hz Models Liebert XDO - 50Hz Models Lighting Fixtures (ship loose) 2 Liebert XDOs per lighting unit; 120V or 277V; 4’ standard fluorescent tubes (not

included) Power, optional lighting fixture 0.9A per 120V light fixture;

0.4A per 277V light fixture None

Smart Module control board

(factory-installed) Dry contact 24VAC - 1A maximum

Pre-Charged Refrigerant R-134a Refrigerant, one-shot connections Table 65 Liebert XDO dimensions—domestic and export

Model

Shipping Dimensions, inches (mm)

Module Dimension Unpacked, inches (mm)

Domestic Export

Length Width Height Length Width Height Length Width Height * All Models 84 (2134) 30 (762) 30 (762) 83 (2108) 30 (762) 30 (762) 72-1/4

(1835)

24-1/8 (613)

25-1/2 (648)

* Includes piping connections

XD 20 K *

16 = Model size 20 = Model size

Revision level Liebert Xtreme

heat density system

Example: XDO20BK– –*

O

Overhead cooling module

B

B = Basic module S = Smart module

- = Domestic Packaging E = Export Packaging

— = Hard-Piped P = Pre-charged

One-Shot Coupling R = Removable Coupling K = 120V-1ph-60Hz

S = 220-240V-1ph-60Hz, 220-240V-1ph- 50Hz

*

Revision level

Figure 139 Liebert XDR model number nomenclature Table 66 Liebert XDR20 specifications

Models XDR20B1- * XDR20B1P *

(Precharged R134a) XDR20B1R * Cooling Capacity, Nominal,

rated at 104ºF (40°C) EAT & 2400ft3/m (68m3/m) 20.5 kW (5.8 tons) Conditions

55°F (13°C) entering fluid temperature 50°F (10°C) or lower dew point Dimensions, inches (mm)

Height, Including Pipe Connections 82-3/8 (2093) 83-1/2 (2121) 80 (2032)

Width With Handles Attached 27-3/8 (695)

Handles Removed 23-1/2 (597)

Depth 6-1/2 (165)

Shipping Length 90 (2286)

Shipping Width 30-1/2 (775)

Shipping Depth 15-1/2 (394)

Max Shipping Depth (4 modules) 62 (1575)

Weight, lb (kg)

Module Only 130 (59) 133 (60) 130 (59)

Shipping 225 (103) 228 (104) 225 (103)

Pipe Connections

Refrigerant Supply 1/2" OD Type ACR Refrigerant Return 7/8" OD Type ACR

Exterior Finish Black Matte, Heat-Fused Powder Coat

Safety CSA, CE Approved

* Refer to Figure 139 for the complete part number.

Table 67 Liebert XDR rack mounting kit

Rack Part #

Knurr Miracel 198163G1

Dell PowerEdge 4210 199050G1

HP 10642 199051G1

APC AR3100 199054G1

XD 20 B

20 = Model Size Liebert

Xtreme heat density system

Example: XDR20B1R — *

R

Rear Cooling Module

- = Domestic Packaging E = Export Packaging

1

1 = Standard

B = Basic Module

*

Revision level

R

- = Hard-Piping

P = Pre-Charged One-Shot Coupling

R = Removable Coupling

Table 68 Liebert XDV8 specifications

Models

XDV8BK1 XDV8SK1

XDV8BT1 XDV8ST1

XDV8BS1 XDV8SS1

60 Hz 60 Hz 50 Hz 50 Hz

Cooling Capacity

Nominal (92°F [33°C] EAT): 8kW / 2.3 Tons Maximum (95°F [35°C] EAT): 8.7kW / 2.5 Tons

Nominal (92°F [33°C] EAT): 7kW/ 2.0 Tons Maximum (103°F [39°C] EAT): 8.7kW/2.5Tons Conditions

Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew point, rear air inlet.

Electrical Requirements

Input 120V model: 1ph-60 Hz 230V model: 1ph-60

Hz 230V model: 1ph-50 Hz

Input power connections 2 power connections, each model

Full Load Amps 120V model: 2.0A 230V model: 1.0A

Power consumption,

nominal, watts 180 190 190 190

Dimensions, in. (mm)

Height – module only 14 (355) not including pipe connections Height – including pipe

connections 18-5/8 (473)

Width 22-7/8 (581)

Depth – Top 39-1/2 (1003)

Depth – Bottom 29-5/8 (752)

Weight, lb (kg)

Module only 77 (35)

Shipping weight 125 (57)

Installed, with

refrigerant 79 (36)

Number of Fans 2 2 2 2

Airflow, Nominal, ft3/ min (m3/ hr)

1000 (1699) with rear inlet.

Bottom inlet airflow may be less, depending on restrictions inside cabinet

833 (1415) with rear inlet.

Bottom inlet airflow may be less, depending on restrictions inside cabinet

Audible noise 78 dBa sound power 73 dBa sound power

Pipe Connections (without Liebert Flex Pipe) Refrigerant Supply

from Liebert XDP/Liebert XDC

1/2" OD Cu, (optional 1/2" threaded coupler flex piping) Refrigerant Return

to Liebert XDP/Liebert XDC

5/8" OD Cu, (optional 3/4" threaded coupler flex piping)

Serviceable Parts Fans and electrical components

Cabinet Exterior

Finish Black, matte finish, heat-fused powder coat

Options

Smart Module control

board (factory-installed) Dry contact, 24VAC, 1A maximum

Pre-Charged

Refrigerant R-134a refrigerant, one-shot connections Agency

Approvals CSA 60Hz CSA 50Hz CE 50Hz

1. Refer to Figure 140 for complete part number.

Table 69 Liebert XDV10 specifications

Models

XDV10BK1 XDV10SK1

XDV10BT1 XDV10ST1

XDV10BS1 XDV10SS1

60 Hz 60 Hz 50 Hz 50 Hz

Cooling Capacity

Nominal (98ºF [37ºC] EAT: 10kW / 2.8 Tons Maximum (106ºF [41ºC] EAT): 11.7kW/3.3 Tons

Nominal (98ºF [37ºC] EAT): 8.3kW / 2.4 Tons Maximum (116ºF [47ºC] EAT): 11.7kW/3.3 Tons Conditions

Capacity Rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew point, rear air inlet.

Electrical Requirements

Input 120V model: 1ph-60 Hz 230V model: 1ph-60 Hz 230V model: 1ph-50 Hz

Input power connections 2 power connections, each model

Full Load Amps 120V model: 2.0A 230V model: 1.0A

Power consumption,

nominal, watts 180 190 190 190

Dimensions, in. (mm)

Height – module only 14 (355) not including pipe connections Height – including hard

pipe connections 18-5/8 (473)

Height – including one-

shot connections 19-5/8 (498)

Width 22-7/8 (581)

Depth – Top 39-1/2 (1003)

Depth – Bottom 29-5/8 (752)

Weight, lb (kg)

Module only 77 (35)

Shipping weight 125 (57)

Installed, with refrigerant 79 (36)

Number of fans 2 2 2 2

Airflow, Nominal, ft3/ min (m3/ hr)

1000 (1699) with rear inlet.

Bottom inlet airflow may be less, depending on restrictions inside cabinet

833 (1415) with rear inlet.

Bottom inlet airflow may be less, depending on restrictions inside cabinet

Audible noise 78 dBa sound power 73 dBa sound power

Pipe Connections (without Liebert Flex Pipe) Refrigerant supply

from Liebert XDP/ XDC 1/2" OD, Cu, (optional 1/2" threaded coupler flex piping) Refrigerant return

to Liebert XDP/ XDC 5/8" OD, Cu, (optional 3/4" threaded coupler flex piping)

Serviceable Parts Fans and electrical components

Cabinet Exterior Finish Black, matte finish, heat-fused powder coat Options

Smart Module control

board (factory-installed) Dry contact, 24VAC, 1A maximum Pre-Charged Refrigerant R-134a refrigerant, one-shot connections Agency

Approvals CSA 60Hz CSA 50Hz CE 50Hz

1. Refer to Figure 140 for complete part number.

Figure 140 Liebert XDV model number nomenclature Table 70 Liebert XDV dimensions—domestic and export

Model

Shipping Dimensions Length x Width x Height

inches (mm)

Module Dimensions Unpacked Length x Width x Height

inches (mm)

Domestic Export Module Only

All Models 48 x 40 x 24-1/4 (1219 x 1016 x 616)

45-4/5 x 30-3/4 x 33 (1163 x 781 x 839mm)

39-1/2 x 22-7/8 x 14 (1003 x 581 x 356)

XD V B K

Vertical top cooler

K = 120V-1ph-60Hz S = 230V, 1ph-50Hz T = 208-240V-1ph-60Hz,

220-240-1ph-50Hz

— = Hard piped P = Pre-charged

One-Shot Coupling R = Removable coupling Liebert Xtreme

heat density system

*

Revision level B = Basic module

S = Smart module

— = Domestic Packaging E = Export

Packaging

Example: XDV10BK– –*

10

8 = Model size 10 = Model Size

Table 71 Liebert XDC160 specifications

Models

XDC160 Air XDC160 Water / Glycol

XDC160AA XDC160AM

189192G3 (90-100°F) 189192G5 (65-85°F)

Cooling Capacity, tons (kW)

46 (160) 37 (130)

See Tables 72,73 and74 for Water/Glycol

performance data Minimum Load 40% of system nominal capacity (64 kW for 60Hz unit)

Electrical Requirements

Input 460V-3ph-60Hz 380/415V-3ph-50Hz 460V-3ph-60Hz

Full Load Amps 79A

Minimum supply wire sizing ampacity 84A

Maximum fuse or circuit breaker size 100A

Dimensions, inches (mm)

Height - Main unit only 78 (1981)

Height - Main unit only, as shipped 83 (2108)

Width - Main unit 74 (1879)

Depth - Main unit 34-5/8 (879)

Height - Water/Glycol-Cooled Condenser Stand N/A 24 (607)

Width - Water/Glycol-Cooled Condenser Stand N/A 72 (1829)

Depth - Water/Glycol-Cooled Condenser Stand N/A 33 (839)

Weight, lb (kg)

Main unit only 1800 (817)

Main unit only, as shipped Domestic: 1945 (882); Export: 2093 (949)

Water/Glycol-Cooled Condenser Stand N/A 1075 (488)

Water/Glycol-Cooled Condenser Stand, as shipped N/A 1150 (521)

Pipe Connections, inches, O.D., Cu

Liebert XD Coolant supply to Liebert XD cooling

modules 1-1/8

Liebert XD Coolant return from Liebert XD cooling

modules 2-1/8

Liquid line, DX circuit 7/8

Hot gas line, DX circuit 1-3/8

Heat Rejection Equipment

95°F (35°C) ambient air-cooled condenser 2-DCSL415 N/A

105°F (41°C) ambient air-cooled condenser 2 -DCSL616 N/A

Number of Liebert XD Cooling Modules Connected, Maximum (Minimum)

Liebert XDCF10 16 (6)

Liebert XDH20 8 (4)

Liebert XDH32 5 (2)

Liebert XDO16 10 (4)

Liebert XDO20 8 (4)

Liebert XDV8 20 (8)

Liebert XDV10 16 (7)

Cabinet Exterior Finish Black, matte finish, heat-fused powder coat Maximum Ambient Operating Temperature °F (°C) 86 (30)

Agency

Approvals CSA CE CSA

Table 72 Floor stand specifications—water-cooled Liebert XDC

XDC160 Water Floor Stand - 60Hz

189192G5 189192G3

Entering Fluid Temp °F (°C) 65 (18) 70 (21) 75 (24) 85 (29) 95 (35) Performance Data

Cooling capacity, tons (kW) 46.1(162.3) 46.1(162.3) 46.1(162.3) 46.1(162.3) 44.5(156.5)

Flow, GPM 50 58 70 110 142

Pressure Drop, psi (Ft Water) 2.7 (6.2) 4.9 (11.3) 5.4 (12.5) 20.7 (47.8) 27.3 (63.1) Heat Rejection Equipment

Water regulating valve size 1" 1" 1" 1" 1"

Piping Connections

Water / glycol supply and return lines 2-1/8" 2-1/8" 2-1/8" 2-1/8" 2-1/8"

Table 73 Floor stand specifications—Liebert XDC with 40% propylene glycol

XDC160 Glycol Floor Stand - 60Hz - 40% PG 189192G3

Outside Ambient °F (°C) 95 (35) 100 (38) 105 (41)

Max Entering Fluid Temp °F (°C) 110 (43) 110 (43) 110 (43) Performance Data

Cooling capacity, tons (kW) 42.5 (149.4)

Total Heat Rejection, (kW) 192.6

Flow, GPM 206

Pressure Drop, psi (ft water) 37.2 (85.9)

Heat Rejection Equipment

Drycooler DDNT 940A 2 x DDNT 880A*

Drycooler Pressure Drop, psi (ft water) 6.7 (15.8) 2.9 (6.6) Glycol pump package - 10hp 460V - D10ANTS1317; 208V - D10YNTS1317

Pump Control Package - 208V RP020HY04S0758

Pump Control Package - 460V RP020HA08S0758

Pump Total Head @ 206 GPM, ft water 145

Water regulating valve size 1-1/4"

Piping Connections

Water / glycol supply and return lines 2-5/8"

* When multiple drycoolers are used, ensure flow is balanced.

Figure 141 Liebert XDC model number nomenclature

Table 74 Floor stand specifications—Liebert XDC with 40% ethylene glycol

XDC160 Glycol Floor Stand - 60Hz - 40% EG 189192G3

Outside Ambient °F (°C) 95 (35) 100 (38) 105 (41)

Max Entering Fluid Temp °F (°C) 110 (43) 110 (43) 110 (43) Performance Data

Cooling capacity, tons (kW) 42.5 (149.4)

Total Heat Rejection, (kW) 192.6

Flow, GPM 204

Pressure Drop, psi (ft water) 35.9 (82.9)

Heat Rejection Equipment

Drycooler DDNT 940A 2 x DDNT 880A*

Drycooler Pressure Drop, psi (ft water) 6.5 (15.1) 2.7 (6.3) Glycol pump package - 10HP 460V - D10ANTS1317; 208V - D10YNTS1317

Pump Control Package - 208V RP020HY04S0758

Pump Control Package - 460V RP020HA08S0758

Pump Total Head @ 204 GPM, ft water 145

Water regulating valve size 1-1/4"

Piping Connections

Water / glycol supply and return lines 2-5/8"

* When multiple drycoolers are used ensure flow is balanced.

A

Place holder

XD C 160 *

Chiller unit

Revision level Liebert

Xtreme heat Density system

Place holder

Example: XDC160AA– –*

A

Voltage-phase-frequency A = 460V-3ph-60Hz M = 380/415-3ph-50Hz

Place holder Model size

Table 75 Liebert XDP160 specifications

Models XDP160RC--3 XDP160RA--3 XDP160RM--3

Cooling Capacity, Nominal

160kW / 46 Tons, 60Hz 140kW / 40 Tons, 50Hz Each capacity is based on 45ºF (7ºC) entering water temperature and 140gpm (530lpm) water flow rate. Capacity is reduced when glycol mixtures

are used in place of 100% water.

Minimum Load 30% of nominal system capacity or 48kW (163,800BTU/H) Electrical Requirements

Input 208V/3ph/60Hz 460V/3/ph60Hz 380/415V/3ph/50Hz

Full Load Amps 4A 2.1A 2.3A

Dimensions, inches (mm)

Height – Unit only 78 (1981)

Height – As shipped 83 (2108)

Width 38 (965)

Depth 34 (864)

Weight, lb (kg)

Unit only 821 (372)

Shipping weight Domestic: 990 (449); Export: 1067 (484) Installed, with refrigerant and chilled water 1038 (471)

Pipe Connections

Refrigerant supply to Liebert XD cooling

module 1-1/8" OD, Cu

Refrigerant return from Liebert XD cooling

module 2-1/8" OD, Cu

Chilled water supply and return 2-5/8" OD, Cu Control valve

2-way, 2" nominal; 35 PSIG close-off pressure rating;

150 PSIG maximum allowable pressure Pressure Drop – Chilled Water Side

20 psig (137kPa, 1.38bar), with 140 gpm (530lpm) water flow rate, control valve fully open

Temperature Rise – Chilled Water Side

at rated flow, °F (°C) 8.0 (4.4) 6.9 (3.8)

Number of Liebert XD Cooling Modules Connected, Maximum (Minimum)

Liebert XDCF10 16 (5)

Liebert XDH20 8 (3)

Liebert XDH32 5 (2)

Liebert XDV8 20 (6)

Liebert XDV10 16 (5)

Liebert XDO16 10 (3)

Liebert XDO20 8 (3)

Cabinet Exterior Finish Black, matte finish, heat-fused powder coat Operating Ambient

Temperature, Maximum, °F (°C) 86 (30)

Agency

Approvals CSA 60Hz CE 50Hz

Figure 142 Liebert XDP model number nomenclature

R

Pump Redundancy

XD P 160 *

Pumping unit

Revision level

Model size Place holder

Example: XDP160RA– –*

A

Voltage-phase-frequency A = 460V-3ph-60Hz C = 208V-3ph-60Hz M = 380/415-3ph-50Hz

Place holder

Liebert Xtreme heat Density system

NOTES

In document System Design Manual (сторінка 159-176)