22.1. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS (VERSION ° - SIZE FROM 0500 TO 0750)

NOTE

- The number of pumps refers to the quantity physically present on the machine.

- The weight difference between the types of configurator pumps (low head and high head) is negligible.

NOTE

Version with desuperheater (D)

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON SUPPORTS (%)

Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0800 ° 989 421 1224 23% 26% 24% 27% 310

NXW0800 ° + 1 pump 1105 415 1244 28% 30% 20% 21%

NXW0800 ° + 2 pumps 1165 412 1297 28% 29% 21% 22% 651

NXW0800 ° + 3 pumps 1226 410 1345 27% 28% 22% 23%

NXW0800 ° + 4 pumps 1286 407 1389 26% 27% 23% 24%

NXW0900 ° 1180 427 1217 23% 27% 23% 27% 314

NXW0900 ° + 1 pump 1296 421 1336 29% 32% 19% 21%

NXW0900 ° + 2 pumps 1356 419 1391 28% 31% 20% 21% 665

NXW0900 ° + 3 pumps 1417 416 1441 28% 30% 20% 22%

NXW0900 ° + 4 pumps 1477 414 1487 27% 29% 21% 23%

NXW1000 ° 1417 428 1309 21% 25% 25% 29% 316

NXW1000 ° + 1 pump 1558 422 1421 27% 31% 20% 22%

NXW1000 ° + 2 pumps 1644 419 1481 27% 30% 21% 23% 653

NXW1000 ° + 3 pumps 1730 416 1535 26% 29% 22% 23%

NXW1000 ° + 4 pumps 1765 415 1555 26% 28% 22% 24%

NXW1250 ° 1461 426 1304 22% 25% 25% 29% 316

NXW1250 ° + 1 pump 1602 421 1414 28% 31% 20% 22% 654

NXW1250 ° + 2 pumps 1688 418 1472 27% 30% 21% 23%

NXW1250 ° + 3 pumps 1774 415 1525 27% 29% 22% 23%

NXW1250 ° + 4 pumps 1809 414 1546 26% 28% 22% 24%

NXW1400 ° 1539 425 1326 21% 24% 26% 29% 315

NXW1400 ° + 1 pump 1680 420 1429 28% 30% 20% 22%

NXW1400 ° + 2 pumps 1765 417 1485 27% 29% 21% 23% 654

NXW1400 ° + 3 pumps 1851 415 1535 26% 28% 22% 23%

NXW1400 ° + 4 pumps 1886 414 1554 26% 28% 22% 24%

22.2. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS (VERSION ° - SIZES FROM 0800 TO 1400)

NOTE

- The number of pumps refers to the quantity physically present on the machine.

- The weight difference between the types of configurator pumps (low head and high head) is negligible.

NOTE

Version with desuperheater (D)

- use the same positions for antivibration pad fi xing as for the AVX of the standard version - desuperheater additional weight : 23 kg for all models from 500 to 800 size / 29 kg. for all models from 900 to 1400 size

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON SUPPORTS (%)

Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0500H H 628 401 849 27% 27% 23% 23% 319

NXW0500H H + 1 pump 730 396 923 33% 33% 17% 17%

NXW0500H H + 2 pumps 778 394 989 32% 31% 19% 18% 320

NXW0500H H + 3 pumps 825 392 1047 31% 30% 20% 19%

NXW0500H H + 4 pumps 872 390 1098 30% 29% 21% 20% 309

NXW0550H H 633 401 846 27% 27% 23% 23% 319

NXW0550H H + 1 pump 735 396 920 33% 33% 17% 17%

NXW0550H H + 2 pumps 782 394 985 32% 31% 19% 18% 320

NXW0550H H + 3 pumps 829 392 1043 31% 30% 20% 19%

NXW0550H H + 4 pumps 877 391 1095 30% 29% 21% 20% 309

NXW0600H H 734 406 911 25% 26% 24% 25% 301

NXW0600H H + 1 pump 836 401 968 32% 32% 18% 18% 320

NXW0600H H + 2 pumps 884 399 1023 31% 31% 19% 19%

NXW0600H H + 3 pumps 931 397 1073 30% 30% 20% 20% 309

NXW0600H H + 4 pumps 978 395 1118 30% 29% 21% 20% 312

NXW0650H H 743 407 910 25% 26% 24% 25% 301

NXW0650H H + 1 pump 848 401 970 32% 32% 18% 18%

NXW0650H H + 2 pumps 899 399 1028 31% 31% 19% 19% 309

NXW0650H H + 3 pumps 950 397 1080 30% 30% 20% 20% 311

NXW0650H H + 4 pumps 1000 396 1127 29% 29% 21% 21% 312

NXW0700H H 791 406 932 24% 25% 25% 26% 302

NXW0700H H + 1 pump 896 401 1048 31% 31% 19% 19% 309

NXW0700H H + 2 pumps 947 399 1099 30% 30% 20% 20% 311

NXW0700H H + 3 pumps 997 397 1145 29% 29% 21% 21% 312

NXW0700H H + 4 pumps 1048 395 1186 28% 28% 22% 22%

NXW0750H H 948 410 1103 24% 25% 25% 26% 310

NXW0750H H + 1 pump 1064 405 1223 27% 28% 22% 23%

NXW0750H H + 2 pumps 1124 403 1279 26% 26% 24% 24% 651

NXW0750H H + 3 pumps 1185 401 1330 25% 25% 25% 25%

NXW0750H H + 4 pumps 1225 399 1361 27% 27% 23% 23%

22.3. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS (VERSION H - SIZES FROM 0500 TO 0750)

NOTE

- The number of pumps refers to the quantity physically present on the machine.

- The weight difference between the types of configurator pumps (low head and high head) is negligible.

NOTE

Version with desuperheater (D)

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON SUPPORTS (%)

Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0800H H 1042 415 1227 24% 26% 24% 26% 310

NXW0800H H + 1 pump 1157 410 1244 29% 30% 20% 21%

NXW0800H H + 2 pumps 1218 408 1295 28% 29% 21% 22% 651

NXW0800H H + 3 pumps 1278 406 1341 27% 28% 22% 23%

NXW0800H H + 4 pumps 1339 404 1384 27% 27% 23% 23%

NXW0900H H 1275 415 1240 23% 25% 25% 27% 314

NXW0900H H + 1 pump 1391 411 1348 29% 31% 19% 20%

NXW0900H H + 2 pumps 1451 409 1399 29% 30% 20% 21% 665

NXW0900H H + 3 pumps 1512 407 1446 28% 29% 21% 22%

NXW0900H H + 4 pumps 1572 405 1489 28% 28% 22% 22%

NXW1000H H 1545 413 1333 22% 23% 27% 28% 316

NXW1000H H + 1 pump 1686 409 1435 28% 30% 21% 22%

NXW1000H H + 2 pumps 1771 407 1489 28% 29% 22% 22% 654

NXW1000H H + 3 pumps 1857 405 1539 27% 28% 22% 23%

NXW1000H H + 4 pumps 1892 404 1558 27% 27% 23% 23%

NXW1250H H 1577 414 1322 22% 23% 26% 28% 315

NXW1250H H + 1 pump 1718 410 1423 28% 30% 20% 21%

NXW1250H H + 2 pumps 1803 408 1477 28% 29% 21% 22% 654

NXW1250H H + 3 pumps 1889 406 1527 27% 28% 22% 23%

NXW1250H H + 4 pumps 1924 405 1546 27% 28% 22% 23%

NXW1400H H 1657 413 1342 22% 23% 27% 29% 317

NXW1400H H + 1 pump 1797 409 1437 28% 30% 21% 22%

NXW1400H H + 2 pumps 1883 407 1488 28% 29% 21% 22% 654

NXW1400H H + 3 pumps 1969 405 1535 27% 28% 22% 23%

NXW1400H H + 4 pumps 2004 404 1554 27% 27% 23% 23%

22.4. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS (VERSION H - SIZES FROM 0800 TO 1400)

NOTE

- The number of pumps refers to the quantity physically present on the machine.

- The weight difference between the types of configurator pumps (low head and high head) is negligible.

NOTE

Version with desuperheater (D)

- use the same positions for antivibration pad fi xing as for the AVX of the standard version - desuperheater additional weight : 23 kg for all models from 500 to 800 size / 29 kg. for all models from 900 to 1400 size

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON SUPPORTS (%)

Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0500L L 750 399 834 28% 27% 23% 22% 309

NXW0500L L + 1 pump 932 392 895 34% 33% 17% 16% 321

NXW0500L L + 2 pumps 979 391 948 33% 32% 18% 17%

NXW0500L L + 3 pumps 1026 389 996 32% 31% 19% 18% 311

NXW0500L L + 4 pumps 1074 388 1183 29% 27% 23% 21% 312

NXW0550L L 755 399 832 28% 27% 23% 22% 309

NXW0550L L + 1 pump 936 392 892 34% 33% 17% 16% 321

NXW0550L L + 2 pumps 983 391 946 33% 32% 18% 17%

NXW0550L L + 3 pumps 1031 390 994 32% 31% 19% 18% 311

NXW0550L L + 4 pumps 1078 389 1180 29% 27% 22% 21% 312

NXW0600L L 854 404 888 26% 26% 24% 24% 310

NXW0600L L + 1 pump 1036 397 933 33% 32% 17% 17%

NXW0600L L + 2 pumps 1083 395 979 32% 32% 18% 18% 311

NXW0600L L + 3 pumps 1130 394 1022 32% 31% 19% 19% 312

NXW0600L L + 4 pumps 1178 393 1191 28% 27% 22% 22%

NXW0650L L 863 405 887 26% 26% 24% 24% 303

NXW0650L L + 1 pump 1048 397 935 33% 32% 17% 17%

NXW0650L L + 2 pumps 1098 396 984 32% 31% 18% 18% 311

NXW0650L L + 3 pumps 1149 394 1029 31% 31% 19% 19% 312

NXW0650L L + 4 pumps 1200 393 1197 28% 27% 23% 22% 310

NXW0700L L 900 407 901 25% 26% 24% 25% 303

NXW0700L L + 1 pump 1084 400 1085 30% 30% 20% 20%

NXW0700L L + 2 pumps 1135 398 1126 29% 29% 21% 21% 651

NXW0700L L + 3 pumps 1186 396 1164 29% 28% 22% 21%

NXW0700L L + 4 pumps 1236 395 1198 28% 27% 22% 22%

NXW0750L L 1054 410 1087 24% 25% 25% 26% 310

NXW0750L L + 1 pump 1249 403 1271 29% 29% 21% 21%

NXW0750L L + 2 pumps 1310 401 1318 28% 28% 22% 22% 651

NXW0750L L + 3 pumps 1370 399 1360 27% 27% 23% 23%

NXW0750L L + 4 pumps 1411 398 1386 27% 27% 23% 23%

22.5. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS (VERSION L - SIZES FROM 0500 TO 0750)

NOTE

- The number of pumps refers to the quantity physically present on the machine.

- The weight difference between the types of configurator pumps (low head and high head) is negligible.

NOTE

Version with desuperheater (D)

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON SUPPORTS (%)

Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0800L L 1187 411 1226 24% 25% 25% 26% 314

NXW0800L L + 1 pump 1357 405 1292 28% 29% 21% 22%

NXW0800L L + 2 pumps 1417 403 1334 28% 28% 22% 22% 652

NXW0800L L + 3 pumps 1478 402 1373 27% 27% 23% 23%

NXW0800L L + 4 pumps 1538 400 1408 27% 27% 23% 23%

NXW0900L L 1378 418 1220 24% 26% 24% 26% 314

NXW0900L L + 1 pump 1585 411 1399 29% 30% 20% 21%

NXW0900L L + 2 pumps 1646 409 1442 28% 29% 21% 22% 653

NXW0900L L + 3 pumps 1706 407 1482 28% 29% 21% 22%

NXW0900L L + 4 pumps 1767 406 1519 27% 28% 22% 23%

NXW1000L L 1615 420 1300 22% 24% 26% 28% 315

NXW1000L L + 1 pump 1847 413 1462 28% 29% 21% 22%

NXW1000L L + 2 pumps 1933 411 1511 27% 29% 22% 23% 654

NXW1000L L + 3 pumps 2019 409 1556 27% 28% 22% 23%

NXW1000L L + 4 pumps 2054 408 1573 26% 27% 23% 24%

NXW1250L L 1659 419 1296 22% 24% 26% 28% 315

NXW1250L L + 1 pump 1891 412 1455 28% 29% 21% 22%

NXW1250L L + 2 pumps 1977 410 1503 27% 29% 22% 23% 659

NXW1250L L + 3 pumps 2063 408 1547 27% 28% 22% 23%

NXW1250L L + 4 pumps 2098 407 1564 27% 27% 23% 23%

NXW1400L L 1737 418 1316 22% 24% 26% 28% 317

NXW1400L L + 1 pump 1969 411 1466 28% 29% 21% 22%

NXW1400L L + 2 pumps 2055 409 1512 27% 28% 22% 23% 659

NXW1400L L + 3 pumps 2140 407 1555 27% 28% 22% 23%

NXW1400L L + 4 pumps 2176 407 1571 26% 27% 23% 24%

22.6. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS (VERSION L - SIZES FROM 0800 TO 1400)

NOTE

- The number of pumps refers to the quantity physically present on the machine.

- The weight difference between the types of configurator pumps (low head and high head) is negligible.

NOTE

Version with desuperheater (D)

- use the same positions for antivibration pad fi xing as for the AVX of the standard version - desuperheater additional weight : 23 kg for all models from 500 to 800 size / 29 kg. for all models from 900 to 1400 size

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON SUPPORTS (%)

Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0500HL HL 801 393 847 28% 27% 23% 22% 309

NXW0500HL HL + 1 pump 982 387 902 34% 32% 17% 16%

NXW0500HL HL + 2 pumps 1030 386 952 33% 31% 18% 17% 311

NXW0500HL HL + 3 pumps 1077 385 998 33% 30% 19% 18%

NXW0500HL HL + 4 pumps 1124 384 1041 32% 30% 20% 19% 312

NXW0550HL HL 805 393 845 28% 27% 23% 22% 309

NXW0550HL HL + 1 pump 987 388 900 34% 32% 17% 16%

NXW0550HL HL + 2 pumps 1034 387 950 33% 31% 18% 17% 311

NXW0550HL HL + 3 pumps 1081 386 996 33% 30% 19% 18%

NXW0550HL HL + 4 pumps 1129 385 1038 32% 30% 20% 18% 312

NXW0600HL HL 907 398 897 26% 26% 24% 24% 310

NXW0600HL HL + 1 pump 1088 392 938 33% 32% 18% 17% 311

NXW0600HL HL + 2 pumps 1135 391 983 33% 31% 19% 18%

312

NXW0600HL HL + 3 pumps 1183 390 1023 32% 30% 19% 18%

NXW0600HL HL + 4 pumps 1230 389 1061 31% 30% 20% 19%

NXW0650HL HL 915 399 897 26% 26% 24% 24% 303

NXW0650HL HL + 1 pump 1100 393 941 33% 32% 18% 17% 311

NXW0650HL HL + 2 pumps 1151 391 987 32% 31% 19% 18%

313

NXW0650HL HL + 3 pumps 1201 390 1030 32% 30% 20% 19%

NXW0650HL HL + 4 pumps 1252 389 1069 31% 29% 20% 19%

NXW0700HL HL 963 398 916 25% 25% 25% 25% 304

NXW0700HL HL + 1 pump 1148 393 1088 30% 29% 21% 20%

NXW0700HL HL + 2 pumps 1199 392 1126 30% 29% 21% 20% 651

NXW0700HL HL + 3 pumps 1249 390 1162 29% 28% 22% 21%

NXW0700HL HL + 4 pumps 1300 389 1194 29% 27% 23% 22%

NXW0750HL HL 1121 403 1105 24% 24% 26% 26% 314

NXW0750HL HL + 1 pump 1316 397 1277 27% 26% 24% 23%

NXW0750HL HL + 2 pumps 1376 395 1321 26% 25% 25% 24% 652

NXW0750HL HL + 3 pumps 1437 394 1361 25% 24% 26% 25%

NXW0750HL HL + 4 pumps 1477 393 1386 27% 27% 23% 23%

22.7. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS (VERSION HL - SIZES FROM 0500 TO 750)

NOTE

- The number of pumps refers to the quantity physically present on the machine.

- The weight difference between the types of configurator pumps (low head and high head) is negligible.

NOTE

Version with desuperheater (D)

- use the same positions for antivibration pad fi xing as for the AVX of the standard version - desuperheater additional weight : 23 kg for all models from 500 to 800 size / 29 kg. for all

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON SUPPORTS (%)

Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0800HL HL 1240 407 1228 24% 25% 25% 26% 314

NXW0800HL HL + 1 pump 1409 402 1291 28% 29% 21% 22%

NXW0800HL HL + 2 pumps 1470 400 1331 28% 28% 22% 22% 665

NXW0800HL HL + 3 pumps 1530 399 1368 27% 27% 23% 23%

NXW0800HL HL + 4 pumps 1591 397 1403 27% 27% 23% 23%

NXW0900HL HL 1473 408 1239 24% 25% 25% 26% 315

NXW0900HL HL + 1 pump 1680 402 1406 29% 30% 21% 21%

NXW0900HL HL + 2 pumps 1740 401 1446 29% 29% 21% 21% 653

NXW0900HL HL + 3 pumps 1801 400 1484 28% 28% 22% 22%

NXW0900HL HL + 4 pumps 1861 399 1519 28% 28% 22% 22%

NXW1000HL HL 1743 408 1322 22% 23% 27% 28% 317

NXW1000HL HL + 1 pump 1975 402 1471 28% 29% 22% 22%

NXW1000HL HL + 2 pumps 2061 401 1516 28% 28% 22% 22% 659

NXW1000HL HL + 3 pumps 2147 399 1558 27% 27% 23% 23%

NXW1000HL HL + 4 pumps 2182 399 1575 27% 27% 23% 23%

NXW1250HL HL 1775 408 1313 22% 23% 27% 28% 317

NXW1250HL HL + 1 pump 2007 403 1460 28% 29% 21% 22%

NXW1250HL HL + 2 pumps 2093 402 1506 28% 28% 22% 22% 659

NXW1250HL HL + 3 pumps 2178 400 1548 27% 27% 23% 23%

NXW1250HL HL + 4 pumps 2214 399 1564 27% 27% 23% 23%

NXW1400HL HL 1855 408 1331 22% 23% 27% 28% 318

NXW1400HL HL + 1 pump 2087 403 1471 28% 29% 21% 22%

NXW1400HL HL + 2 pumps 2173 401 1514 28% 28% 22% 22% 659

NXW1400HL HL + 3 pumps 2258 400 1554 27% 27% 23% 23%

NXW1400HL HL + 4 pumps 2294 399 1570 27% 27% 23% 23%

22.8. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS (VERSION HL - SIZES FROM 0800 TO 1400)

NOTE

- The number of pumps refers to the quantity physically present on the machine.

- The weight difference between the types of configurator pumps (low head and high head) is negligible.

NOTE

Version with desuperheater (D)

- use the same positions for antivibration pad fi xing as for the AVX of the standard version - desuperheater additional weight : 23 kg for all models from 500 to 800 size / 29 kg. for all models from 900 to 1400 size

22.9. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS VERSION TOTAL RECOVERY (T) ALL SIZE

22.10. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS VERSION SILENCED MODE WITH TOTAL RECOVERY (T) ALL SIZE

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON SUPPORTS (%)

Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0500

T

728 419 1200 26% 29% 21% 23% 303

NXW0550 733 419 1195 27% 29% 21% 23% 303

NXW0600 852 424 1269 25% 28% 22% 25% 310

NXW0650 860 4045 1235 27% 27% 23% 23% 310

NXW0700 914 428 1303 24% 28% 22% 26% 310

NXW0750 1060 431 1477 23% 27% 23% 26% 314

NXW0800 1190 430 1487 23% 27% 23% 27% 652

NXW0900 1443 437 1658 23% 28% 22% 27% 315

NXW1000 1756 442 1801 21% 26% 24% 29% 322

NXW1250 1805 440 1790 21% 26% 24% 29% 322

NXW1400 1912 440 1824 21% 25% 24% 29% 322

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON SUPPORTS (%)

Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0500

LT

980 404 1207 27% 28% 22% 23% 312

NXW0550 985 405 1204 27% 28% 22% 23% 312

NXW0600 1104 410 1259 26% 27% 23% 24% 651

NXW0650 1112 395 1233 27% 27% 23% 23% 651

NXW0700 1166 414 1287 25% 27% 23% 25% 652

NXW0750 1312 418 1482 24% 27% 23% 26% 652

NXW0800 1441 418 1490 24% 26% 24% 26% 652

NXW0900 1732 425 1662 24% 27% 23% 26% 323

NXW1000 2045 431 1784 22% 26% 24% 28% 324

NXW1250 2094 430 1775 22% 26% 24% 28% 324

NXW1400 2202 430 1805 22% 25% 25% 29% 324

22.11. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS VERSION CONDESERLESS (E)-ALL SIZE

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON

SUPPORTS (%) Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0500

E

525 396 771 29% 29% 21% 21% 319

NXW0550 530 397 768 29% 29% 21% 21% 319

NXW0600 610 399 835 28% 27% 23% 22% 301

NXW0650 619 400 834 27% 27% 23% 23% 301

NXW0700 638 400 840 27% 27% 23% 23% 301

NXW0750 796 406 1013 26% 27% 23% 24% 303

NXW0800 904 409 1161 25% 27% 23% 25% 310

C D

A B

800 mm Yg

Xg DIAGRAM DISTRIBUTION OF WEIGHTS ON SUPPORTS

22.12. PERCENTAGE DISTRIBUTION OF WEIGHTS ON SUPPORTS VERSION CONDENSERLESS - SILENCED MODE (E)-ALL SIZE

MODEL

EMPTY PERCENTAGE WEIGHT DISTRIBUTION ON

SUPPORTS (%) Weight CENTRE OF GRAVITY AVX

Xg Yg A B C D

NXW0500

LE

697 388 787 30% 28% 22% 21% 309

NXW0550 702 389 786 30% 28% 22% 21% 309

NXW0600 782 391 835 28% 27% 23% 22% 310

NXW0650 791 392 836 28% 27% 23% 22% 303

NXW0700 810 392 839 28% 27% 23% 22% 303

NXW0750 968 399 1030 26% 26% 24% 24% 310

NXW0800 1104 400 1176 26% 26% 24% 24% 314

NXW0900 1244 404 1148 26% 27% 23% 24% 314

NXW1000 1460 407 1238 24% 25% 25% 26% 315

NXW1250 1504 406 1235 24% 25% 25% 26% 315

NXW1400 1558 403 1251 24% 24% 26% 26% 317

23. ELECTRICAL WIRINGS

NXW chillers are completely wired in the factory and only need the connection to the electricity mains supply, down- stream from a group switch, according to the regulations in force in the coun- try where the machine is installed.

It is also suggested to check:

− the mains supply characteristics, to ensure it is suitable for the levels indicated in the electrical data table, also taking into considera- tion any other equipment that may be operating at the same time.

− The unit is only powered after the last (hydraulic and electric) instal- lations.

− Follow the connections instructions of the phase conductors, and earth.

− The power supply line will have a special protection upstream against short circuits and earth losses that sections the system ac- cording to other users.

− The voltage should be within a tolerance of ± 10% of the rated supply voltage of the machine (for Three-phase units displacement max 3% between the phases). If these pa- rameters are not respected, contact the energy supplier. For electrical wirings use isolated double cables according to the standards in force in the different countries.

− It is necessary to use a omnipolar thermomagnetic switch, in compli- ance with the CEI-EN standards (contact opening of at least 3 mm), with adequate switch capa- bility and differential protection based on the followed electrical data table, installed as close as possible to the machine.

− It is necessary to carry out an effi- cient earth connection. The manu- facturer can not be held responsi- ble for any damage caused by the failure and ineffective earthing of the machine.

− For units with Three-phase power

check the correct connection of the phases.

WARNING:

It is forbidden to use water pipes for the earthing of the machine.

23.1. RECOMMENDED SECTION OF ELECTRIC CABLES

The cable sections indicated in the ta- ble are advised for a maximum length of 50 m.

All electrical operations must be carried out BY QUALIFIED PERSONNEL, IN ACCORDANCE WITH THE CORRESPONDING REGULATIONS, trained and in- formed about the risks related to such operations.

The characteristics of electric lines and related components must be estab- lished by PERSONNEL AUTHORISED TO DESIGN ELECTRIC INSTALLATIONS, fol- lowing international regulations and the national regulations of the country in which the unit is installed, in compliance with the legislative regulations in force at the moment of installation.

For installation requirements, the wiring layout supplied with the unit must be compulsory referred to. The wiring layout together with the manuals must be kept in good conditions and readily ACCESSIBLE FOR FUTURE OP- ERATIONS ON THE UNIT.

IT is compulsory to check the machine sealing before connecting the elec- trical wirings. The machine should only be powered once the hydraulic and electric operations are completed.

ELECTRICAL DATA VERSION ° WITHOUT PUMPING GROUP (ALL VERSIONS)

Model

MAX RECOMMENDED

LENGTH (metres)

SECT. A

(400V-3) SECT.B EARTH

(400V-3) IL (400V-3)

U.M. U.M. U.M. U.M.

mm2 mm2 mm2 A

NXW 0500

50

16

1.5

16 80

NXW 0550 16 16 100

NXW 0600 25 16 100

NXW 0650 25 16 125

NXW 0700 35 16 160

NXW 0750 50 25 160

NXW 0800 70 35 200

NXW 0900 70 35 200

NXW 1000 70 35 250

NXW 1250 95 50 250

NXW 1400 95 50 250

KEY

Sec. A: Power supply

Sec. B: Controls and safety connection Earth

IL: Main switch Model

MAX RECOMMENDED

LENGTH

SECT. A

(400V-3) SECT.B EARTH

(400V-3) IL (400V-3)

U.M. U.M. U.M. U.M. U.M.

MT mm2 mm2 mm2 A

NXW 0500

50

16

1.5

16 100

NXW 0550 25 16 100

NXW 0600 25 16 125

NXW 0650 35 16 125

NXW 0700 50 25 160

NXW 0750 50 25 160

NXW 0800 70 35 200

NXW 0900 70 35 200

NXW 1000 95 50 250

NXW 1250 95 50 250

NXW 1400 95 50 250

ELECTRICAL DATA VERSION WITH PUMPING GROUP (ALL VERSIONS)

For higher lengths or differ- ent types of cable installa- tion, it will be the DESIGNERS responsibility to carefully measure the line main switch, the supply power line and the earthing protection connection, and the work- ing connection cables:

− the length

− the type of cable

− Absorption of the unit and its physical position, and room temperature.

WARNING:

Check that all power cables are correctly secured to the terminals when switched on for the fi rst time and after 30 days of use. Afterwards, check the connection of the power cables every six months.

Slack terminals could cause the cables and components to overheat.

23.2. CONNECTION TO THE POWER SUPPLY

− Check there is no voltage on the electric line you want to use.

23.2.1. To access the elec- tric box:

− Turn the electrical panel screws ¼ in counter- clockwise direction

− Turn the handle of the door-block disconnecting switch to OFF (see figure).

In this way, the electrical panel can be accessed

23.3. ELECTRICAL POWER CONNECTION

− For the functional connection of the unit, run the power supply cable to the electrical panel inside the unit fi g. 1 and connect it to the disconnecting switch terminals ob- serving the phase and the earth. fi g. 2

23.4. AUXILIARY CON- NECTIONS AT THE USER/INSTALLER EXPENSE

For installation requirements, refer to the wiring diagram supplied with the unit. The wiring diagram together with the manuals must be kept in good conditions and readily ACCESSIBLE FOR FUTURE OP-

ERATIONS ON THE UNIT. Key fig. 2

L1 Line 1 L2 Line 2 L3 Line 3 PE Earth

Fig.2

Fig.1

24. CONTROL AND FIRST START-UP

24.1. PREPARATION FOR COMMISSIONING

Bear in mind that a free start-up service is offered by the Aermec Technical Service for the unit of this series, at the request of Aermec customers or legitimate owners and in ITALY only.

The start-up must be previously agreed on the basis of the system implementation times. Before the intervention of the AERMEC After Sales Service, all the operations (electrical and hydraulic hook ups, loading and breather from the system) must be completed.

Before starting the unit make sure that:

− All the safety conditions have been respected

− The unit has been properly fixed to the support base

− The minimum technical spaces have been observed;

− Water connections have been performed respecting the input and output

− The hydraulic system has been loaded and vented.

− The hydraulic circuit taps are open

− The electrical wirings have been properly carried out;

− The voltage is within a tolerance of 10% of the unit rated voltage

− The earthing has been carried out correctly

− Tightening of all electrical and hydraulic connections have been well carried out.

24.2. FIRST COMMISSIONING OF THE MACHINE Before activating the unit:

- Close the electric panel lid.

- Position the door-block disconnecting switch of the machine on ON, turning the handle down. (fig.3)

- The display on (fig.4) indicates that the unit is ready for operation.

For more information see the USER'S MANUAL 24.3. SEASON CHANGEOVER

For the season changeover, see the user's manual.

WARNING

The fi rst start-up has to be carried out with the standard settings, only when the test is fi nished the values of the opera- tion Set Point vary.

Before starting up, power the unit for at least 12-24 hours

by positioning the pro- tection thermomagnetic switch and the door-block disconnecting switch on ON fi g.1

Make sure that the control panel is turned off until it allows the oil heater system the compressor casing.

Fig.4 Fig.3

Display on on

25. OPERATION