MAX REFRIGERANT PIPING LENGTH

In document SERVICE MANUAL (сторінка 35-44)

Outdoor unit union diameter For

Indoor unit A Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8)

36

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below.

UNIT: mm (inch) Piping length each indoor unit (a, b) 20m

Total piping length (a+b) 30m

Bending point for each unit 20

Total bending point 30

MAX REFRIGERANT PIPING LENGTH

a

b

Outdoor unit Indoor

units

15m

10m

15m Refrigerant piping length (one way, 2 unit total)

Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 20) Outdoor unit

precharged

(g) 30m

200 20m

1,300 0

Max.Height difference

Outdoor unit union diameter For

Indoor unit A Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8)

Stop valve

(with strainer #100) LEV A

LEV B

Compressor

Muffler

4-way valve Indoor unit

B

Indoor unit A

Indoor unit A

Indoor unit B

Capillary tube

Capillary tube

Stop valve (with strainer #100)

R.V. coil OFF

ON Refrigerant flow in cooling Refrigerant flow in heating

Discharge temperature thermistor RT62

Stop valve (with service port)

Stop valve (with service port)

Defrost thermistor RT61

Distributor Capillary tube Strainer

#100

Ambient temperature thermistor RT65 Outdoor heat

exchanger temperature thermistor

RT68 FAN-OUT

HEX-OUT

Sub muffler

It is irrelevant which unit is higher.

ADDITIONAL REFRIGERANT CHARGE

37

Stop valve

(with strainer #100) LEV A

LEV B

Compressor

Defrost thermistor RT61

Distributor Muffler

4-way valve Indoor unit

B

Indoor unit A

Indoor unit A

Indoor unit B

Capillary tube Capillary tube

Capillary tube

Strainer

#100

Stop valve (with strainer #100) R.V. coil

OFF

ON Refrigerant flow in cooling Refrigerant flow in heating

Ambient temperature thermistor RT65 Outdoor heat

exchanger temperature thermistor

RT68 FAN-OUT

HEX-OUT

Discharge temperature thermistor RT62

Stop valve (with service port)

Stop valve (with service port)

Sub muffler

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below.

UNIT: mm (inch) Piping length each indoor unit (a, b) 20m

Total piping length (a+b) 30m

Bending point for each unit 20

Total bending point 30

UNIT: mm

MXZ-2C52VA

MAX REFRIGERANT PIPING LENGTH

a

b

Outdoor unit Indoor

units

15m

10m

15m Refrigerant piping length (one way, 2 unit total)

Calculation : Xg = 20 g/m x (Refrigerant piping length(m) - 20) Outdoor unit

precharged

(g) 30m

200 20m

1,300 0

Max.Height difference

Outdoor unit union diameter For

Indoor unit A Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) It is irrelevant which unit is higher.

ADDITIONAL REFRIGERANT CHARGE

38

Strainer

#100

Power receiver LEV A

LEV B

LEV C

Oil separator Compressor

Defrost thermistor RT61

Distributor Muffler

4-way valve

LEV E Indoor unit

C Indoor unit

B Indoor unit

A

Indoor unit A

Indoor unit B

Indoor unit C

Capillary tube Capillary tube

Capillary tube

Capillary tube

Capillary tube

Discharge temperature thermistor RT62

Strainer

#100

Strainer

#100 Strainer

#100 R.V. coil

OFF

ON Refrigerant flow in cooling Refrigerant flow in heating

Ambient temperature thermistor RT65 Outdoor heat

exchanger temperature thermistor RT68

FAN-OUT

HEX-OUT

Strainer

#100 Stop valve with service port

Stop valve High-pressure switch (MXZ-3C68VA only)

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below.

When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.

For further information on Different-diameter pipe, refer to "PARTS CATALOG".

UNIT: mm (inch)

MAX REFRIGERANT PIPING LENGTH

Outdoor unit union diameter For

Indoor unit A Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit C Liquid 6.35(1/4) Gas 9.52(3/8) a

b

c

Outdoor unit Indoor

units

15m

10m 15m Refrigerant piping length (one way, 3 unit total)

Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 40)

Max.Height difference

Outdoor unit precharged

(g) 50m

200

60m 400 40m

2,700 0

It is irrelevant which unit is higher.

ADDITIONAL REFRIGERANT CHARGE

3C54 3C68

Piping length each indoor unit (a, b, c) 25m 25m

Total piping length (a+b+c) 50m 60m

Bending point for each unit 25 25

Total bending point 50 50

39

UNIT: mm

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below.

When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.

For further information on Different-diameter pipe, refer to "PARTS CATALOG". UNIT: mm (inch) Piping length each indoor unit (a, b, c, d) 25m

Total piping length (a+b+c+d) 60m

Bending point for each unit 25

Total bending point 60

MXZ-4C71VA

MAX REFRIGERANT PIPING LENGTH

Outdoor unit union diameter For

Indoor unit A Liquid 6.35(1/4) Gas 12.7(1/2) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit C Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit D Liquid 6.35(1/4) Gas 9.52(3/8)

Indoor unit D

Power receiver LEV A

LEV B

LEV C

LEV D

Oil separator Compressor

Muffler

4-way valve

LEV E Indoor unit

C Indoor unit

B Indoor unit

A

Indoor unit A Indoor unit

B Indoor unit

C Indoor unit

D

Capillary tube

Capillary tube

Discharge temperature thermistor RT62

Strainer

#100 Strainer

#100

Strainer

#100 Strainer

#100

Strainer

#100 R.V. coil

OFF

ON Refrigerant flow in cooling Refrigerant flow in heating

Distributor

HEX-OUT

Outdoor heat exchanger temperature thermistor RT68

Defrost thermistor RT61 Capillary tube

Ambient temperature thermistor RT65 FAN-OUT

Strainer

#100 Stop valve with service port

Stop valve High-pressure switch

a

b

c

d

Outdoor unit Indoor

units

15m

10m 15m Refrigerant piping length (one way, 4 unit total)

Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 40)

Max.Height difference

Outdoor unit precharged

(g) 50m

200 40m

2,700 0

60m 400 It is irrelevant which unit is higher.

ADDITIONAL REFRIGERANT CHARGE

40

a

b

c

d

Outdoor unit Indoor

units

15m 15m

10m Refrigerant piping length (one way, 4 unit total)

Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 40)

Max.Height difference

Outdoor unit precharged

(g) 50m

200 40m

3,500 0

60m 400

70m 600

Indoor unit

D Stop valve

(with service port)

Stop valve

Power receiver LEV A

LEV B

LEV C

LEV D

Oil separator Compressor

Muffler

4-way valve

LEV F Indoor unit

C Indoor unit

B Indoor unit

A

Indoor unit A Indoor unit

B Indoor unit

C Indoor unit

D

Capillary tube

Capillary tube

Discharge temperature thermistor RT62 High-pressure

switch

Strainer

#100 Strainer

#100

Strainer

#100 Strainer

#100

Strainer

#100 R.V. coil

OFF

ON Refrigerant flow in cooling Refrigerant flow in heating

Strainer

#100 Distributor

Outdoor heatexchanger

Capillary tube Defrost thermistor RT61

Outdoor heat exchanger temperature thermistor RT68

Ambient temperature thermistor RT65

HEX-OUT

FAN-OUT

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below.

When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.

For further information on Different-diameter pipe, refer to "PARTS CATALOG". UNIT: mm (inch) Piping length each indoor unit (a, b, c, d) 25m

Total piping length (a+b+c+d) 70m

Bending point for each unit 25

Total bending point 70

MAX REFRIGERANT PIPING LENGTH

Outdoor unit union diameter For

Indoor unit A Liquid 6.35(1/4) Gas 12.7(1/2) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit C Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit D Liquid 6.35(1/4) Gas 9.52(3/8) It is irrelevant which unit is higher.

ADDITIONAL REFRIGERANT CHARGE

41

a

b c

d

Outdoor unit Indoor

units

15m

10m 15m Refrigerant piping length (one way, 5 unit total)

Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 40)

e

Max.Height difference

Outdoor unit precharged

(g) 50m

200 40m

4,000 0

60m 400

70m 600

80m 800

Indoor unit

E Stop valve

(with service port)

Stop valve

Power receiver LEV A

LEV B

LEV C

LEV D

Oil separator Compressor

Muffler

4-way valve

LEV F Indoor unit

D Indoor unit

C Indoor unit

B

Indoor unit A Indoor unit

B Indoor unit

C Indoor unit

D Indoor unit

A

Capillary tube

Capillary tube

Discharge temperature thermistor RT62

Strainer

#100 Strainer

#100

Strainer

#100 Strainer

#100

Strainer

#100

LEV E Indoor unit

E Strainer

#100 R.V. coil

OFF

ON Refrigerant flow in cooling Refrigerant flow in heating

Strainer

#100 Distributor

Outdoor heatexchanger

Capillary tube Defrost thermistor RT61

Outdoor heat exchanger temperature thermistor RT68

Ambient temperature thermistor RT65 High-pressure

switch

HEX-OUT

FAN-OUT

MXZ-5C100VA MXZ-5C100VA2

UNIT: mm

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the tables below.

When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.

For further information on Different-diameter pipe, refer to "PARTS CATALOG". UNIT: mm (inch) Piping length each indoor unit (a, b, c, d,e) 25m

Total piping length (a+b+c+d+e) 80m

Bending point for each unit 25

Total bending point 80

MAX REFRIGERANT PIPING LENGTH

Outdoor unit union diameter For

Indoor unit A Liquid 6.35(1/4) Gas 12.7(1/2) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit C Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit D Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit E Liquid 6.35(1/4) Gas 9.52(3/8) It is irrelevant which unit is higher.

ADDITIONAL REFRIGERANT CHARGE

42

a

b c

d

Outdoor unit Indoor

units

15m

10m 15m Refrigerant piping length (one way, 6 unit total)

Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 60)

e

Max.Height difference

f Outdoor unit

precharged

(g) 50m

0 40m

5,000 0

60m 0

70m 200

80m 400

Indoor unit

E Stop valve

(with service port)

Stop valve

Power receiver LEV A

LEV B

LEV C

LEV D

Oil separator Compressor

Muffler 4-way valve

LEV M Indoor unit

D Indoor unit

F

Indoor unit C Indoor unit

B

Indoor unit A Indoor unit

B Indoor unit

C Indoor unit

D Indoor unit

A

Solenoid valve

Capillary tube

Discharge temperature thermistor RT62

Strainer

#100

Strainer

#100 Strainer

#100

Strainer

#100

LEV E Indoor unit

E Strainer

#100

LEV F Indoor unit

F Strainer

#100 R.V. coil

OFF

ON Refrigerant flow in cooling Refrigerant flow in heating

Strainer

#100 Distributor

Outdoor heatexchanger

Capillary tube Defrost thermistor RT61

2.4

3.6 500

Outdoor heat exchanger temperature thermistor RT68

Ambient temperature thermistor RT65 High-pressure

switch

Capillary tube 2.4

3.6 600

HEX-OUT

FAN-OUT Capillary tube

Strainer #50

Refrigerant pipe diameter is different according to indoor unit to be connected.

For the diameter of connection pipe of the indoor unit, refer to the indoor unit installation manual.

When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.

For further information on Different-diameter pipe, refer to "PARTS CATALOG".

Piping length each indoor unit (a, b, c, d, e, f) 25m

Total piping length (a+b+c+d+e+f) 80m

Bending point for each unit 25

Total bending point 80

MAX REFRIGERANT PIPING LENGTH

It is irrelevant which unit is higher.

ADDITIONAL REFRIGERANT CHARGE

UNIT: mm (inch) Outdoor unit union diameter

For

Indoor unit D Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit E Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit F Liquid 6.35(1/4) Gas 9.52(3/8) UNIT: mm (inch)

Outdoor unit union diameter For

Indoor unit A Liquid 6.35(1/4) Gas 12.7(1/2) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit C Liquid 6.35(1/4) Gas 9.52(3/8)

43

a

b c

d

Outdoor unit Indoor

units

15m

10m 15m Refrigerant piping length (one way, 6 unit total)

Calculation : Xg = 20 g/m x (Refrigerant piping length (m) - 60)

e

Max.Height difference

f Outdoor unit

precharged

(g) 50m

0 40m

4,800 0

60m 0

70m 200

80m 400

Indoor unit

E Stop valve

(with service port)

Stop valve LEV A

LEV B

LEV C

LEV D

Oil separator Compressor

Muffler 4-way valve

LEV M Indoor unit

D Indoor unit

F

Indoor unit C Indoor unit

B

Indoor unit A Indoor unit

B Indoor unit

C Indoor unit

D Indoor unit

A

Solenoid valve

Capillary tube

Discharge temperature thermistor RT62

Strainer

#100

Strainer

#100 Strainer

#100

Strainer

#100

LEV E Indoor unit

E Strainer

#100

LEV F Indoor unit

F Strainer

#100 R.V. coil

OFF

ON Refrigerant flow in cooling Refrigerant flow in heating

Strainer

#100 Distributor

Strainer #50 Outdoor heatexchanger

Defrost thermistor RT61 Outdoor heat exchanger temperature thermistor RT68

Ambient temperature thermistor RT65 High-pressure

switch

Capillary tube 2.4

3.6 500

HEX-OUT

FAN-OUT Capillary tube

Accumulator

Capillary tube 2.4

3.6 300

Capillary tube 2.4

3.6 600

MXZ-6C120VA -

E2

MXZ-6C122VA

UNIT: mm

Refrigerant pipe diameter is different according to indoor unit to be connected.

For the diameter of connection pipe of the indoor unit, refer to the indoor unit installation manual.

When diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.

For further information on Different-diameter pipe, refer to "PARTS CATALOG".

Piping length each indoor unit (a, b, c, d, e, f) 25m

Total piping length (a+b+c+d+e+f) 80m

Bending point for each unit 25

Total bending point 80

MAX REFRIGERANT PIPING LENGTH

It is irrelevant which unit is higher.

ADDITIONAL REFRIGERANT CHARGE

UNIT: mm (inch) Outdoor unit union diameter

For

Indoor unit D Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit E Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit F Liquid 6.35(1/4) Gas 9.52(3/8) UNIT: mm (inch)

Outdoor unit union diameter For

Indoor unit A Liquid 6.35(1/4) Gas 12.7(1/2) Indoor unit B Liquid 6.35(1/4) Gas 9.52(3/8) Indoor unit C Liquid 6.35(1/4) Gas 9.52(3/8)

44