3-1 External Appearance and Refrigerant Circuit Components of Outdoor Unit... 67 3-1-1 External Appearance of Outdoor Unit ... 67 3-1-2 Outdoor Unit Refrigerant Circuits... 69 3-2 Outdoor Unit Refrigerant Circuit Diagrams... 75 3-3 Functions of the Major Components of Outdoor Unit... 78 3-4 Functions of the Major Components of Indoor Unit... 81 3-5 External Appearance and Refrigerant Circuit Components of BC Controller ... 82 3-6 BC Controller Refrigerant Circuit Diagrams... 85 3-7 Functions of the Major Components of BC Controller... 88

3 Major Components, Their Functions and Refrigerant Circuits

3 Major Components, Their Functions and Refrigerant Circuits

3-1 External Appearance and Refrigerant Circuit Components of Outdoor Unit

3-1-1 External Appearance of Outdoor Unit

(1) PURY-EP200, EP250, EP300, EP350YLM-A PURY-P200, P250, P300, P350, P400YLM-A(1)

Fan guards Fan guards

Fan Fan

Heat exchanger Heat exchanger

Front panels Front panels Fin guard

Fin guard

Side panel Side panel

Control box Control box

(2) PURY-EP400, EP450, EP500YLM-A PURY-P450, P500YLM-A(1)

Fan box Fan box Fan guards

Fan guards

Fans Fans

Control box Control box

Heat exchanger Heat exchanger

Front panels Front panels Fin guard

Fin guard

Side panel Side panel

Side panel Side panel

3 Major Components, Their Functions and Refrigerant Circuits

3-1-2 Outdoor Unit Refrigerant Circuits

(1) PURY-P200, P250YLM-A(1)

Check valve(CV5a)

Check valve(CV4a)

Check valve(CV6a) Check valve(CV3a) Check valve(CV9a)

Check valve(CV8a)

Check valve(CV2a) Check valve(CV7a)

4-way valve(21S4a) Solenoid valve(SV11)

Solenoid valve(SV10) Solenoid valve(SV9)

Solenoid valve (SV5b) Low-pressure check joint Low-pressure check joint(CJ2) High-pressure check joint High-pressure check joint(CJ1)

Refrigerant service valve on the high pressure side(BV2) Refrigerant service valve on the low pressure side(BV1)

Solenoid valve block (SV4a, SV4d, SV4b)

Linear expansion valve (LEV5a)

Low-pressure sensor (63LS)

High-pressure switch (63H1)

Compressor cover

Solenoid valve (SV1a) Oil separator Compressor

Accumulator

High-pressure sensor (63HS1)

(2) PURY-P300, P350, P400YLM-A(1)

4-way valve(21S4a)

Check valve(CV7a)

Solenoid valve(SV11) High-pressure check joint High-pressure check joint(CJ1) Low-pressure check joint Low-pressure check joint(CJ2)

Check valve(CV5a)

Solenoid valve (SV5b)

Refrigerant service valve on the high pressure side(BV2) Refrigerant service valve on the low pressure side(BV1)

Check valve(CV6a)

Check valve(CV3a)

Check valve(CV9a)

Check valve(CV8a)

Check valve(CV2a)

Check valve(CV4a) Solenoid valve block (SV4a, SV4d, SV4b) Linear expansion valve

(LEV5a) Accumulator Oil separator

Compressor Solenoid valve (SV1a) Compressor cover

High-pressure sensor(63HS1) High-pressure switch(63H1) Low-pressure sensor

(63LS) Solenoid valve(SV9)

Solenoid valve(SV10)

3 Major Components, Their Functions and Refrigerant Circuits (3) PURY-P450, P500YLM-A(1)

4-way valve (21S4b) Solenoid valve (SV10) Solenoid valve (SV11) Solenoid valve (SV4c) Check valve

(CV4a) Check valve (CV7b)

Check valve (CV7a)

Check valve (CV5a) Check valve (CV6b) Check valve (CV8a) Check valve (CV4b)

Check valve (CV6a)

Check valve(CV2a) Check valve(CV2b) Check valve(CV3a) Check valve(CV5b) Refrigerant service

valve on the high pressure side(BV2)

Refrigerant service valve on the low pressure side(BV1)

Solenoid valve block (SV4a, SV4d, SV4b)

Linear expansion

valve(LEV5a) Linear expansion

valve(LEV5b) Accumulator

Solenoid valve(SV1a) Solenoid valve(SV5b)

Oil separator Compressor Compressor cover Low-pressure

check joint Low-pressure

check joint(CJ2) High-pressure check joint High-pressure check joint(CJ1) High-pressure

sensor(63HS1) High-pressure

switch(63H1) Low-pressure

sensor(63LS) Solenoid valve

(SV9) 4-way valve (21S4a)

(4) PURY-EP200, EP250YLM-A

4-way valve(21S4a)

Solenoid valve(SV11)

Solenoid valve(SV7) Solenoid valve(SV9)

Solenoid valve(SV10)

Solenoid valve (SV1a) Check valve(CV7a)

Check valve(CV5a)

Check valve(CV4a) gas-liguid separator

(L/S)

Check valve(CV6a) Check valve(CV3a) Check valve(CV9a) Check valve(CV8a)

Check valve(CV2a) Low-pressure sensor (63LS)

High-pressure check joint High-pressure check joint(CJ1) Low-pressure check joint Low-pressure check joint(CJ2)

Solenoid valve (SV5b)

Refrigerant service valve on the high pressure side(BV2)

Refrigerant service valve on the low pressure side(BV1) Refrigerant service valve on the low pressure side for separately sold unit(BV3)

Accumulator

Linear expansion valve (LEV5a)

Solenoid valve block (SV4a, SV4d, SV4b)

Compressor Oil separator Compressor cover High-pressure sensor (63HS1)

High-pressure switch (63H1)

3 Major Components, Their Functions and Refrigerant Circuits (5) PURY-EP300, EP350YLM-A

4-way valve(21S4a)

Check valve(CV7a)

Check valve(CV6a)

Check valve(CV3a)

Check valve(CV9a)

Check valve(CV2a) Check valve(CV8a)

Check valve(CV4a) Check valve(CV5a) Solenoid valve

(SV11) High-pressure check joint High-pressure check joint(CJ1) Low-pressure check joint Low-pressure check joint(CJ2)

Solenoid valve

(SV5b) Solenoid valve

(SV1a) Solenoid valve (SV7) Solenoid valve(SV9)

Solenoid valve(SV10)

Refrigerant service valve on the high pressure side(BV2)

Refrigerant service valve on the low pressure side for separately sold unit(BV3)

Refrigerant service valve on the low pressure side(BV1)

Solenoid valve block (SV4b)

Solenoid valve block (SV4d)

Solenoid valve block(SV4a)

Linear expansion valve(LEV5a) gas-liguid separator(L/S)

Accumulator

Oil separator Compressor Compressor cover High-pressure sensor(63HS1) High-pressure switch

(63H1) Low-pressure sensor

(63LS)

(6) PURY-EP400, EP450, EP500YLM-A

4-way valve(21S4a) 4-way valve(21S4b)

Solenoid valve (SV11) Solenoid valve (SV9) Solenoid valve (SV10)

Solenoid valve (SV5b)

Solenoid valve (SV1a) Check valve

(CV5a)

Check valve (CV7a)

Check valve (CV6a) Check valve (CV5b) Check valve (CV7b) gas-liguid separator (L/S) Check valve (CV4b)

Check valve(CV6b)

Check valve(CV2b) Check valve(CV2a) Check valve(CV8a) Check valve(CV3a) Check valve(CV4a) Refrigerant service

valve on the high pressure side(BV2)

Linear expansion valve(LEV5a) Linear expansion valve(LEV5b)

Refrigerant service valve on the low pressure side for separately sold unit(BV3)

Solenoid valve block (SV4a, SV4b, SV4d) Refrigerant service valve on the low pressure side(BV1)

Low-pressure

sensor(63LS) Accumulator

Oil separator Compressor Compressor cover

High-pressure check joint High-pressure check joint(CJ1) Low-pressure

check joint Low-pressure check joint(CJ2) High-pressure

sensor(63HS1) High-pressure

switch(63H1) Solenoid valve

(SV4c) Solenoid valve

(SV7)

3 Major Components, Their Functions and Refrigerant Circuits

3-2 Outdoor Unit Refrigerant Circuit Diagrams

(1) PURY-P200, P250YLM-A(1)(-BS)

(2) PURY-P300, P350, P400YLM-A(1)(-BS)

O/S

TH4

CJ2

BV2 COMP

21S4a

ST1 63LS

BV1 CV8a

CV6a TH7 TH9

TH11

TH3 SV4a SV4b

SV4d Solenoid valve block

ACC

ST6 ST7 ST17

TH5

TH6

CV9a SV9

SV11 SV10

CV4a

CV2a CV7a

CV3a CV5

CJ1

SV5b ST18 HEX 63HS163H1

ST3

CP1

SV1a

LEV5a

*1

*1 CP2 CP3

CP4

CP5

O/S

TH4

CJ2

BV2 COMP

21S4a

ST1 63LS

BV1 CV8a

CV6a TH7 TH9

TH11

TH3 SV4a SV4b

SV4d Solenoid valve block

ACC

ST6 ST7 ST17

TH5

TH6

CV9a SV9

SV11 SV10

CV4a

CV2a CV7a

CV3a CV5

CJ1

SV5b ST18 HEX 63HS163H1

ST3

CP1

SV1a

LEV5a

*1

*1 CP2 CP3

CP4

CP5

(3) PURY-P450, P500YLM-A(1)(-BS)

(4) PURY-EP200, EP250YLM-A(-BS)

O/S

TH4

BV2 COMP

21S4a 21S4b

ST1BV1 CV8

CV5a

CV4a

CV3a CV2a CV6a

CV7a

TH3 TH12

SV4a SV4b

SV4c CV7b

CV4b CV5b CV6b ACC

ST7 ST6 CJ2 63LS

TH5 ST17

63HS163H1 SV9

SV10 CP4

CP2 SV4d

CV2b TH7

TH9 TH11

TH6 HEX

HEX ST3

CP1

SV1a

LEV5a LEV5b

*1

*1

CP3

SV5b CJ1

ST18 SV11

Solenoid valve block

O/S L/S

TH4

CJ2

BV2 COMP

21S4a

ST1 63LS

BV1 CV8a

CV6a TH7 TH9

TH11

TH3 SV4a SV4b

SV4d

ACC

ST7 ST6 ST17

TH5

TH6

CV9a

CV4a

CV2a CV7a

CV3a

CV5a BV3

SV5b ST18 HEX 63HS163H1

CJ1

ST3

CP1 CP5

CP4 CP2

SV1a

LEV5a

*1

*1

CP3 SV11

SV10

SV7

SV9

ST8 Solenoid valve block

3 Major Components, Their Functions and Refrigerant Circuits (5) PURY-EP300, EP350YLM-A(-BS)

(6) PURY-EP400, EP450, EP500YLM-A(-BS)

O/S L/S

TH4

CJ2

BV2 COMP

21S4a

ST1 63LS

BV1 CV8a

CV6a TH7 TH9

TH11

TH3 SV4a SV4b

SV4d

ACC

ST7 ST6 ST17

TH5

TH6

CV9a

CV4a

CV2a CV7a

CV3a

CV5a BV3

SV5b ST18HEX 63HS163H1

CJ1

ST3

CP1 CP5

CP4 CP2

SV1a

LEV5a

*1

*1

CP3 SV11

SV10

SV7

SV9

ST8 Solenoid valve block

O/S

TH4

BV2 COMP

21S4a 21S4b

ST1 BV1 BV3

CV8

CV5a

CV4a

CV3a

CV2a CV6a

CV7a

TH3 TH12

SV4a

SV7

SV4b

SV4c CV7b

CV4b CV5b CV6b ACC

ST7 ST6 CJ2 63LS

TH5 ST17

63HS163H1 SV9

SV10 CP4

CP2 SV4d

CV2b TH7

TH9 TH11

TH6 HEX

HEX ST3

CP1

SV1a

LEV5a LEV5b

*1

*1

CP3

SV5b CJ1

ST18

ST8 SV11

L/S

Solenoid valve block

3-3 Functions of the Major Components of Outdoor Unit

Part

name Symbols

(functions) Notes Usage Specifications Check method

Com-pressor MC1

(Comp1) Adjusts the amount of circulating refrigerant by adjusting the operat- ing frequency based on the oper- ating pressure data

(E)200 - (E)250 models Low-pressure shell scroll compressor

wirewound resistance 20°C [68°F] : 0.72Ω (E)300 - (E)350 models Low-pressure shell scroll compressor

wirewound resistance 20°C [68°F] : 0.32Ω (E)P400 - (E)P450, P500 models

Low-pressure shell scroll compressor

wirewound resistance 20°C [68°F] : 0.3Ω EP500 models

Low-pressure shell scroll compressor

wirewound resistance 20°C [68°F] : 0.43Ω High

pres- sure sensor

63HS1 1) Detects high pressure

2) Regulates frequency and pro- vides high-pressure protec- tion

Low pres- sure sensor

63LS 1) Detects low pressure

2) Provides low-pressure pro- tection

Pres- sure switch

63H1 1) Detects high pressure

2) Provides high-pressure pro- tection

4.15MPa[601psi] OFF set- ting

Thermis-

tor TH4

(Discharge) 1) Detects discharge air temper- ature

2) Provides high-pressure pro- tection

Degrees Celsius Resistance check

0°C[32°F] :698 kΩ 10°C[50°F] :413 kΩ 20°C[68°F] :250 kΩ 30°C[86°F] :160 kΩ 40°C[104°F] :104 kΩ 50°C[122°F] : 70 kΩ 60°C[140°F] : 48 kΩ 70°C[158°F] : 34 kΩ 80°C[176°F] : 24 kΩ 90°C[194°F] :17.5 kΩ 100°C[212°F] :13.0 kΩ 110°C[230°F] : 9.8 kΩ

Pressure 0~4.15 MPa [601psi]

Vout 0.5~3.5V 0.071V/0.098 MPa [14psi]

Pressure [MPa]

=1.38 x Vout [V]-0.69 Pressure [psi]

=(1.38 x Vout [V] - 0.69) x 145 GND (Black) Vout (White) Vcc (DC5V) (Red) Con-nector

63HS1

1 1 2 3

2 3

Pressure 0~1.7 MPa [247psi]

Vout 0.5~3.5V 0.173V/0.098 MPa [14psi]

Pressure [MPa]

=0.566 x Vout [V] - 0.283 Pressure [psi]

=(0.566 x Vout [V] - 0.283) x 145 GND (Black) Vout (White) Vcc (DC5V) (Red) Con-nector

63LS

1 1 2 3

2 3

R = 7.465k120

R = 4057 R = 7.465

25/120 t

4057 273 t1 3931 exp

[3-3 Functions of the Major Components of Outdoor Unit ]

3 Major Components, Their Functions and Refrigerant Circuits

Thermis-

tor TH3

(Pipe temperature)

Controls defrosting during heating

operation Degrees Celsius

0°C[32°F] :15 kΩ 10°C[50°F] :9.7 kΩ 20°C[68°F] :6.4 kΩ 25°C[77°F] :5.3 kΩ 30°C[86°F] :4.3 kΩ 40°C[104°F] :3.1 kΩ

Resistance check

TH7(Outdoor tem- perature)

1) Detects outdoor air tempera- 2) Controls fan operationture

TH5 Fan operated on the 63LS and

TH5 values.

TH6 Controls defrosting during heating

operation TH9

TH11 TH12 THHSInverter heat sink tem- perature

Controls inverter cooling fan

based on THHS temperature Degrees Celsius

0°C[32°F] :161 kΩ 10°C[50°F] :97 kΩ 20°C[68°F] :60 kΩ 25°C[77°F] :48 kΩ 30°C[86°F] :39 kΩ 40°C[104°F] :25 kΩ THL DCL tem-

perature DCL overheat protection Degrees Celsius

0°C[32°F] :162.2 kΩ 10°C[50°F] :98.3 kΩ 25°C[77°F] :49.1 kΩ 50°C[122°F] :17.6 kΩ 100°C[212°F] :3.3 kΩ Sole-

noid valve

SV1aDischarge-suc- tion

bypass

1) High/low pressure bypass at start-up and stopping, and capacity control during low- load operation

2) High-pressure-rise preven- tion

AC220 - 240V

Open while being powered/

closed while not being pow- ered

Continuity check with a tester

SV4a - SV4d Heat exchanger capacity control

Controls outdoor unit heat ex- changer capacity

SV5b Heat exchanger capacity control

Prevents high-pressure-rise

Controls defrost cycle AC220 - 240V

Closed while being powered/

open while not being pow- ered

SV7 Controls bypass during heating

operation AC220 - 240V

Dead: cooling cycle Live: heating cycle

SV10 Switching when Continuous heat-

ing mode AC220 - 240V

Open while being powered/

closed while not being pow- ered

SV11

SV9 High-pressure-rise prevention AC220 - 240V

Open while being powered/

closed while not being pow- ered

Part

name Symbols

(functions) Notes Usage Specifications Check method

R = 15k0

R = 3460 R = 15

0/80

t 3460 273 t1 2731 exp

R = 17k50

R = 4016 R = 17

25/120

t 4016 273 t1 3231 exp

R = 3.3k100 B = 3970 R =3.3

0/100

t 3970 273 t1 3731 exp

LEV LEV5a,b LEV5b is only on the P450, P500, EP400 - EP500 models.

Evaporating temperature control DC12V

Opening of stepping motor driving valve 0-3000 pulses

Refer to the sec- tion "Continuity Test with a Tes- ter".

Continuity be- tween white and orange.

Continuity be- tween yellow, red, and blue.

4-way

valve 21S4a Changeover between heating and

cooling AC220 - 240V

Dead: cooling cycle Live: heating cycle

Continuity check with a tester

21S4b P450,

P500, EP400- EP500 models only Fan mo-

tor FAN motor 1,2 FAN motor 2 is only on the P450, P500, EP400- EP500 models.

Regulates the heat exchanger ca- pacity by adjusting the operating frequency and operating the pro- peller fan based on the operating pressure.

AC380-460V, 920W

name (functions) Notes Usage Specifications Check method

Yellow White Orange

Red Blue M

3 Major Components, Their Functions and Refrigerant Circuits

3-4 Functions of the Major Components of Indoor Unit

Part

Name Symbol

(functions) Notes Usage Specification Check method

Linear expan- sion valve

LEV 1) Adjusts superheat at the

indoor heat exchanger outlet during cooling 2) Adjusts subcool at the in-

door unit heat exchanger outlet during heating

DC12V

Opening of stepping motor driving valve 0-(1800) pulses

Refer to the section

"Continuity Test with a Tester".

Continuity between white, red, and or- ange.

Continuity between yellow, brown, and blue.

Thermis-

tor TH1

(Suction air tem- perature)

Indoor unit control (Thermo)

0°C [32°F]:15 kΩ 10°C [50°F] :9.7 kΩ 20°C [68°F]:6.4 kΩ 25°C [77°F] :5.3 kΩ 30°C [86°F] :4.3 kΩ 40°C [104°F] :3.1 kΩ

Resistance check

TH2 (Pipe tempera- ture)

1) Indoor unit control (Frost prevention, Hot adjust) 2) LEV control during heat-

ing operation (subcool detection).

TH3 (Gas pipe tem- perature)

LEV control during cooling op- eration (superheat detection) TH4 Outdoor air tem-

perature)*1

Indoor unit control (Thermo)

Temperature sensor (Indoor air temperature)

Indoor unit control (Thermo)

*1. Indicates gas pipe temperature on the PKFY-P VHM-E and PKFY-P VKM-E models.

Yellow White

Red Orange

Brown Blue M

1 273+t R0=15k

R0/80=3460

Rt =15exp{3460( - )}2731

3-5 External Appearance and Refrigerant Circuit Components of BC Controller

1. CMB-P V-G1, GA1, HA1 (1) Front

(2) Rear view <G1 type>

Liquid pipe (Indoor unit side)

Gas pipe (Indoor unit side)

TH12

TH15

TH16 TH11

SVM1 LEV1LEV3 PS1

PS3

Tube in tube heat exchanger Gas/Liquid separator

3 Major Components, Their Functions and Refrigerant Circuits (3) Rear view <GA1 type>

(4) Rear view <HA1 type>

TH12 TH15

TH16

TH11

SVM2

SVM1 LEV1 LEV3

LEV2 PS3 PS1

Tube in tube heat exchanger Gas/Liquid separator

Gas/Liquid separator

LEV3

LEV1

SVM2 SVM2b

SVM1b SVM1 TH15 TH16

TH12 TH11

PS1

PS3

Tube in tube heat exchanger

2. CMB-P V-GB1, HB1 (1) Front

(2) Rear view

Liquid pipe (Indoor unit side)

Gas pipe (Indoor unit side)

TH15 TH12

LEV3

3 Major Components, Their Functions and Refrigerant Circuits

3-6 BC Controller Refrigerant Circuit Diagrams

(1) CMB-P104 - P1016V-G1

TH15 TH12

LEV3

LEV1 TH16

PS3 PS1 TH11

SVM1 Gas/Liquid

separator

Check valve block Solenoid valve block

SVC/SVA/SVB

(2) CMB-P108, P1010, P1013, P1016V-GA1 (main)

(3) CMB-P104, P108V-GB1 (sub)

TH15

HIC-B

HIC-A TH12

LEV3 SVM2

LEV1 LEV2

TH16 PS3

PS1 TH11

SVM1

Solenoid valve block

Check valve block Gas/Liquid

separator

SVC/SVA/SVB

TH15 TH12

HIC-C CP

LEV3

Check valve block Solenoid valve block

SVC/SVA/SVB

3 Major Components, Their Functions and Refrigerant Circuits (4) CMB-P1016V-HA1 (main)

(5) CMB-P1016V-HB1 (sub)

TH15

TH12 LEV3

LEV1 TH16

PS1 PS3

TH11

SVC/SVA/SVB

SVM1

SVM2

HIC-A

HIC-B

SVM1b

SVM2b Gas/Liquid

separator

TH15 TH12

HIC-C CP

LEV3

Check valve block Solenoid valve block

SVC/SVA/SVB

3-7 Functions of the Major Components of BC Controller

(1) G1 type

Part name Symbols

(functions) Part

code Usage Specifications Check method

Pressure

sensor PS1

(High pres- sure side)

1) Detects high pressure 2) LEV control

PS3(Intermedi- ate pres- sure)

1) Detects intermediate pressure

2) LEV control

Thermistor TH11 (Liquid inlet tempera- ture)

LEV control

(Liquid level control)

0°C[32°F] : 15 kΩ 10°C[50°F] :9.7 kΩ 20°C[68°F] :6.4 kΩ 25°C[77°F] :5.3 kΩ 30°C[86°F] :4.3 kΩ 40°C[104°F] :3.1 kΩ TH12(Bypass

outlet tem- perature)

LEV control (Superheat)

TH15(Bypass in- let tempera- ture)

LEV control (Superheat)

TH16 (Liquid re- frigerant tempera- ture)

LEV control (Subcool)

Solenoid

valve SVM1 Opens during cooling and de-

frost modes AC220-240V

Open while being powered/

closed while not being pow- ered

Continuity check with a tester

SVA Provides refrigerant to indoor

unit in cooling operation

SVB Provides refrigerant to indoor

unit in heating operation

SVC Provides refrigerant to indoor

unit in cooling operation

LEV LEV1 1) Liquid level control

2) Pressure differential con- trol

DC12V

Opening of a valve driven by a stepping motor

0-2000 pulses

Same as indoor LEV LEV3

Pressure 0~4.15 MPa [601psi]

Vout 0.5~3.5V 0.071V/0.098 MPa [14psi]

Pressure [MPa]

=1.38 x Vout [V]-0.69 Pressure [psi]

=(1.38 x Vout [V] - 0.69) x 145 GND (Black) Vout (White) Vcc (DC5V) (Red) Con-nector

PS1

1 1 2 3

2 3

R = 15k0 R = 3460 R = 15

0/80

t 3460 273 t1 2731 exp

3 Major Components, Their Functions and Refrigerant Circuits (2) GA1 type

Part name Symbols

(functions) Part

code Usage Specifications Check method

Pressure

sensor PS1

(High pres- sure side)

1) Detects high pressure 2) LEV control

PS3(Intermedi- ate pres- sure)

1) Detects intermediate pressure

2) LEV control

Thermistor TH11 (Liquid inlet tempera- ture)

LEV control

(Liquid level control)

0°C[32°F] : 15 kΩ 10°C[50°F] :9.7 kΩ 20°C[68°F] :6.4 kΩ 25°C[77°F] :5.3 kΩ 30°C[86°F] :4.3 kΩ 40°C[104°F] :3.1 kΩ TH12(Bypass

outlet tem- perature)

LEV control (Superheat)

TH15(Bypass in- let tempera- ture)

LEV control (Superheat)

TH16 (Liquid re- frigerant tempera- ture)

LEV control (Subcool)

Solenoid

valve SVM1 Opens during cooling and de-

frost modes AC220-240V

Open while being powered/

closed while not being pow- ered

Continuity check with a tester SVM2 Pressure differential control

SVA Provides refrigerant to indoor

unit in cooling operation

SVB Provides refrigerant to indoor

unit in heating operation

SVC Provides refrigerant to indoor

unit in cooling operation

LEV LEV1 1) Liquid level control

2) Pressure differential con- 3) Subcool controltrol

DC12V

Opening of a valve driven by a stepping motor

41 - 3000 pulses

Same as indoor LEV

LEV3 DC12V

Opening of a valve driven by a stepping motor

0 - 2000 pulses

Pressure 0~4.15 MPa [601psi]

Vout 0.5~3.5V 0.071V/0.098 MPa [14psi]

Pressure [MPa]

=1.38 x Vout [V]-0.69 Pressure [psi]

=(1.38 x Vout [V] - 0.69) x 145 GND (Black) Vout (White) Vcc (DC5V) (Red) Con-nector

PS1

1 1 2 3

2 3

R = 15k0 R = 3460 R = 15

0/80

t 3460 273 t1 2731 exp

(3) GB1 type

Part name Symbols

(functions) Part

code Usage Specifications Check method

Thermistor TH12 (Bypass outlet tem- perature)

LEV control (Superheat)

0°C[32°F] : 15 kΩ 10°C[50°F] :9.7 kΩ 20°C[68°F] :6.4 kΩ 25°C[77°F] :5.3 kΩ 30°C[86°F] :4.3 kΩ 40°C[104°F] :3.1 kΩ TH15(Bypass in-

let tempera- ture)

LEV control (Superheat)

Solenoid

valve SVA Provides refrigerant to indoor

unit in cooling operation AC220-240V

Open while being powered/

closed while not being pow- ered

Continuity check with a tester

SVB Provides refrigerant to indoor

unit in heating operation

SVC Provides refrigerant to indoor

unit in cooling operation

LEV LEV3 Pressure differential control DC12V

Opening of a valve driven by a stepping motor

0-2000 pulses

Same as indoor LEV

R = 15k0

R = 3460 R = 15

0/80

t 3460 273 t1 2731 exp

3 Major Components, Their Functions and Refrigerant Circuits (4) HA1 type

Part name Symbols

(functions) Part

code Usage Specifications Check method

Pressure

sensor PS1

(High pres- sure side)

1) Detects high pressure 2) LEV control

PS3(Intermedi- ate pres- sure)

1) Detects intermediate pressure

2) LEV control

Thermistor TH11 (Liquid inlet tempera- ture)

LEV control

(Liquid level control)

0°C[32°F] : 15 kΩ 10°C[50°F] :9.7 kΩ 20°C[68°F] :6.4 kΩ 25°C[77°F] :5.3 kΩ 30°C[86°F] :4.3 kΩ 40°C[104°F] :3.1 kΩ TH12(Bypass

outlet tem- perature)

LEV control (Superheat)

TH15(Bypass in- let tempera- ture)

LEV control (Superheat)

TH16 (Liquid re- frigerant tempera- ture)

LEV control (Subcool)

Solenoid

valve SVM1 Opens during cooling and de-

frost modes AC220-240V

Open while being powered/

closed while not being pow- ered

Continuity check with a tester

SVM1b Opens during cooling and de-

frost modes

SVM2 Pressure differential control SVM2b Pressure differential control

SVA Provides refrigerant to indoor

unit in cooling operation

SVB Provides refrigerant to indoor

unit in heating operation

SVC Provides refrigerant to indoor

unit in cooling operation

LEV LEV1 1) Liquid level control

2) Pressure differential con- 3) Subcool controltrol

DC12V

Opening of a valve driven by a stepping motor

41 - 3000 pulses

Same as indoor LEV

LEV3 DC12V

Opening of a valve driven by a stepping motor

0 - 2000 pulses

Pressure 0~4.15 MPa [601psi]

Vout 0.5~3.5V 0.071V/0.098 MPa [14psi]

Pressure [MPa]

=1.38 x Vout [V]-0.69 Pressure [psi]

=(1.38 x Vout [V] - 0.69) x 145 GND (Black) Vout (White) Vcc (DC5V) (Red) Con-nector

PS1

1 1 2 3

2 3

R = 15k0 R = 3460 R = 15

0/80

t 3460 273 t1 2731 exp

(5) HB1 type

Part name Symbols

(functions) Part

code Usage Specifications Check method

Thermistor TH12 (Bypass outlet tem- perature)

LEV control (Superheat)

0°C[32°F] : 15 kΩ 10°C[50°F] :9.7 kΩ 20°C[68°F] :6.4 kΩ 25°C[77°F] :5.3 kΩ 30°C[86°F] :4.3 kΩ 40°C[104°F] :3.1 kΩ TH15(Bypass in-

let tempera- ture)

LEV control (Superheat)

Solenoid

valve SVA Provides refrigerant to indoor

unit in cooling operation AC220-240V

Open while being powered/

closed while not being pow- ered

Continuity check with a tester

SVB Provides refrigerant to indoor

unit in heating operation

SVC Provides refrigerant to indoor

unit in cooling operation

LEV LEV3 Pressure differential control DC12V

Opening of a valve driven by a stepping motor

0-2000 pulses

Same as indoor LEV

R = 15k0

R = 3460 R = 15

0/80

t 3460 273 t1 2731 exp