4. ADVANCED SETTINGS 29

4.7 List of parameters

P Parameter def. min. max. unit SPV

type Carel

SPV

Modbus

SPV access note

0 Software version 0 255 I 1 129 U E.g. v3.5 = 35.

1 Set point in automatic mode 22 0 255 °C A 1 1 U

2 Differential in automatic OFF-cooling zone 5 0 255 °C/10 A 2 2 U

3 Differential in automatic OFF-heating zone 5 0 255 °C/10 A 3 3 U

4 Hysteresis for cooling in automatic 10 0 255 °C/10 A 4 4 U

5 Hysteresis for heating in automatic 3 0 255 °C/10 A 5 5 U

6 Thermostat hysteresis (not automatic mode) 5 0 255 °C/10 A 6 6 U

7 Medium speed delta in Auto Fan 7 0 255 °C/10 A 7 7 U

8 Maximum speed delta in Auto Fan 7 0 255 °C/10 A 8 8 U

9 Fan speed hysteresis in Auto Fan 5 0 255 °C/10 A 9 9 U

10 Minimum speed set in HEAT ENABLE 29 0 255 °C A 10 10 U

11 Medium speed set in HEAT ENABLE 33 0 255 °C A 11 11 U

12 Maximum speed set in HEAT ENABLE 37 0 255 °C A 12 12 U

13 HEAT ENABLE/COOL ENABLE hysteresis 10 0 255 °C/10 A 13 13 U

14 COOL ENABLE set point 21 0 255 °C A 14 14 U

15 Use of probe B1 0 0 6 I 105 233 U

16 Use of probe B2 0 0 6 I 106 234 U

17 Use of probe St3 0 0 6 I 107 235 U

18 Increase COOL/DRY set in sleep 10 0 255 °C/10 A 18 18 U

19 Decrease HEAT set in sleep 10 0 255 °C/10 A 19 19 U

20 Limit ADC coeffi cient 6 0 15 I 2 130 U

21 Average ADC coeffi cient 6 0 15 I 3 131 U

22 Select outside compensation probe 0 0 2 I 4 132 U

23 Set point delta for compensation in cooling 0 -99 127 °C/10 A 20 20 U

24 Compensation factor in cooling 0 -20 20 A 21 21 U

25 Set point delta for compensation in heating 0 -99 127 °C/10 A 22 22 U

26 Compensation factor in heating 0 -20 20 A 23 23 U

27 Reserved use 0 0 2 I 5 133 U

28 Display modulating outputs 0 0 3 I 6 134 U

29 Enable continuous fan operation 0 0 1 I 7 135 U

30 Ventilation set point in fan mode (local & AUTO) 15 0 255 °C A 24 24 U

31 Ventilation diff. in fan mode (local & automatic) 20 0 255 °C A 25 25 U

32 FLUSH fan off time 2 0 255 min I 8 136 U

33 FLUSH fan on time 90 0 255 s I 9 137 U

34 FLUSH mode 0 0 3 I 10 138 U

35 Extra fl ush ventilation time 30 0 255 s I 11 139 U

36 Automatic/Comfort Set point 0 0 1 I 12 140 U

37 Select probe to be displayed 0 0 4 I 13 141 U

38 Skip Panel functions 0 0 255 I 14 142 U

39 Set output 4 (see P95 and dipswitch) 5 0 18 I 15 143 U

40 Set output 5 (see P95 and dipswitch) 0 0 18 I 16 144 U

41 Set output 6 3 0 18 I 17 145 U

42 Set output 7 4 0 18 I 18 146 U

43 Select multifunction input DI3 0 0 10 I 19 147 U

44 Select multifunction input DI4 0 0 10 I 20 148 U

45 Select multifunction input DI5 0 0 10 I 21 149 U

46 Heater activation delta with heat enable not active 30 0 255 °C/10 A 26 26 U

47 Max B2 temperature to switch off heaters 40 0 255 °C A 27 27 U

48 Flush time with heaters 20 0 255 s I 22 150 U

49 Fan ON time in DRY 3 0 255 min I 23 151 U

50 Fan OFF time in DRY 15 0 255 min I 24 152 U

51 Valve On time during cycles 0 0 255 min I 25 153 U

52 Max valve Off time during cycles 0 0 255 min I 26 154 U

53 Minimum valve Off time 0 0 255 min I 27 155 U

54 Serial communication mode (0=CAREL, 1=Modbus, 2=LON, use

with LON serial card) 0 0 2 I 28 156 F

55 Enable cool & heat symbols in AUTOMATIC 0 0 1 I 29 157 U

56 Polarity of cooling/heating digital input 1 0 1 I 30 158 U

ENGL ISH constructor

P Parameter def. min. max. unit SPV

type Carel

SPV

Modbus

SPV access note

62 Offset for probe B2 in COOL/DRY 0 -99 127 °C/10 A 32 32 U

63 Offset for probe B2 in HEAT 0 -99 127 °C/10 A 33 33 U

64 Offset for probe St3 in COOL/DRY 0 -99 127 °C/10 A 34 34 U

65 Offset for probe St3 in HEAT 0 -99 127 °C/10 A 35 35 U

66 CAN Master/Slave 0 0 1 I 32 160 * F

67 CANbus serial address 1 1 125 I 33 161 * F

68 Hydronic algorithm logic 0 0 7 I 34 162 * F

69 Local network address 1 0 207 I 35 163 F

70 Dependency of hydronic algorithms (on Slaves) 0 0 7 I 36 164 * F

71 Serial address of Slave 1 0 0 207 I 37 165 * F

72 Serial address of Slave 2 0 0 207 I 38 166 * F

73 Serial address of Slave 3 0 0 207 I 39 167 * F

74 Serial address of Slave 4 0 0 207 I 40 168 * F

75 Serial address of Slave 5 0 0 207 I 41 169 * F

76 Serial address of Slave 6 0 0 207 I 42 170 * F

77 Serial address of Slave 7 0 0 207 I 43 171 * F

78 Serial address of Slave 8 0 0 207 I 44 172 * F

79 Serial address of Slave 9 0 0 207 I 45 173 * F

80 Serial address of Slave 10 0 0 207 I 46 174 * F

81 Dependency of hydronic algorithms on Slave 1 0 0 7 I 47 175 * F

82 Dependency of hydronic algorithms on Slave 2 0 0 7 I 48 176 * F

83 Dependency of hydronic algorithms on Slave 3 0 0 7 I 49 177 * F

84 Dependency of hydronic algorithms on Slave 4 0 0 7 I 50 178 * F

85 Dependency of hydronic algorithms on Slave 5 0 0 7 I 51 179 * F

86 Dependency of hydronic algorithms on Slave 6 0 0 7 I 52 180 * F

87 Dependency of hydronic algorithms on Slave 7 0 0 7 I 53 181 * F

88 Dependency of hydronic algorithms on Slave 8 0 0 7 I 54 182 * F

89 Dependency of hydronic algorithms on Slave 9 0 0 7 I 55 183 * F

90 Dependency of hydronic algorithms on Slave 10 0 0 7 I 56 184 * F

91 Load defaults 0 0 255 I 57 185 F value= 44

92 Factory password 0 0 255 I 58 186 U value= 66

93 Occupancy mode 0 0 3 I 59 187 U

94 Occupancy time 15 1 255 min I 60 188 U

95 Disable output setting from dipswitch 0 0 1 I 61 189 U

96 Reserved use 62

97 Maximum valve travel time (2 windings) 120 1 255 s I 63 191 U

98 Reserved use I 64 192 U

99 Minimum P+I output variation for valve movement 5% 0 100 % I 65 193 U

100 Maximum valve inactivity time (for unblocking) 4 0 255 hours I 66 194 U

101 Forced movement for antistick function 20 0 100 % max

travel I 67 195 U

102 Reserved use I 68 196

103 Reserved use I 69 197

104 Reserved use °C/10 A 36 36

105 Reserved use °C/10 A 37 37

106 Reserved use °C A 38 38

107 Bumpless transfer 1 0 3 I 104 232 U

108 Integral time 0 0 255 s *10 I 99 227 U

109 Dead band 2 0 255 °C/10 A 42 42 U

110 Reserved use °C/10 A 43 43

111 ON/OFF heater control offset from set point (ON/OFF manage-

ment with hysteresis) 30 0 255 °C/10 A 44 44 U

112 Heating set point hysteresis for heater control 5 0 255 °C/10 A 45 45 U

113 Reserved use °C/10 A 46 46

114 Cold valve proportional band 0 0 255 °C/10 A 39 39 U

115 Hot valve proportional band 0 0 255 °C/10 A 40 40 U

116 Modulating heater proportional band 0 0 255 °C/10 A 41 41 U

117 Fan speed enabled 0 0 1 I 100 228 U

118 Reserved use I 101 229 U

119 Reserved use I 102 230

120 Reserved use °C A 47 47

121 Reserved use °C A 48 48

122 Reserved use min I 103 231

123 Reserved use I 108 236

124 Presence of humidity-temperature probe sch_th 0 0 1 I 109 237

125 Reserved use °C/10 A 49 49

Tab. 4.u

* Only for CANbus hydronic systems, not use for Modbus® or Plantvisor systems.

ENGL ISH constructor

variables only accessible

from serial link def. min. max. unit SPV type

Carel SPV

Modbus SPV notes

probe B1 0 °C/10 A 70 70 read-only

probe BT 0 °C/10 A 71 71 read-only

Probe B2 0 °C/10 A 72 72 read-only

probe B3 0 °C/10 A 73 73 read-only

control probe 0 °C/10 A 74 74 read-only

virtual probe (probe set

by CANbus/supervisor) 0 °C/10 A 75 75 do not use with Plant-

Visor and Modbus®

control set point °C/10 A 76 76 read-only

mode (see Table 4.z) 0 0 6 I 70 198 see Table 4.z

fan (see Table 4.z) 0 0 3 I 71 199 see Table 4.z

Reserved use I 72 200

ON/OFF 0 0 1 I 73 201

Ind /zone (control probe

(1=B1; 0= BT) 1 0 1 I 74 202

internal use do not modify from supervisor

continuous fan operation 0 0 1 I 75 203 read/write

master alarms 0 I 76 204 read-only

slave alarms 0 I 77 205 read-only

lock panel keypad 0 I 78 206

for CANbus hydronic systems only, do not use with Modbus®

and PlantVisor general fl ags 1 (see Table

4.z) I 79 207 see Table 4.z

general fl ags 2 (see Table

4.z) I 80 208 read-only see Table

4.z digital inputs (see Table

4.z) and heating/cooling request

I 81 209 read-only see Table 4.z

sleep/econ 0 0 1 I 82 210

set point set 22 8 32 °C I 83 211

comfort control 0 -3 3 °C I 84 212

general fl ags 3 (see

Table 4.z) I 85 213 read-only

Reserved use I 86 214

enable control virtual

probe when=1 0 0 1 I 87 215

for CANbus hydronic systems only, do not use with Modbus®

and PlantVisor

general fl ags 6 I 88 216

reserved use I 89 217

reserved use I 90 218

reserved use I 91 219

global alarm 0 0 1 D 1 - read-only

reserved use I 92 220

reserved use % A 77 77

modulating valve % A 78 78 read-only

modulating heater % A 79 79 read-only

humidity probe H % rH A 80 80 read-only

temperature probe H °C/10 A 81 81 read-only

reserved use I 93 221

reserved use I 94 222

Tab. 4.v

mode

0 automatic

1 automatic + heater

2 cooling

3 dry

4 fan

5 heating

6 heating + heater fan

0 auto

1 minimum

2 medium

3 maximum

general fl ags 1 1 heater available

2 reserved use

4 reserved use

8 remote control 16 broadcasting active 32 reserved use 64 lock function 128 hydronic active general fl ags 2

1 enable cooling active 2 enable heating active 4 comfort function activated

8 economy

16 reserved use 32 reserved use 64 reserved use 128 reserved use general fl ags 3

1 reserved use

2 reserved use

4 reserved use

8 display set/probe fl ag generali 6

1 User present (see occupancy, used by Easy Way system)

digital inputs

1 value of input 1 (remote ON/OFF) 2 value of input 2 (heating/cooling) 4 value of input 3 (multifunction) 8 value of input 4 (multifunction) 16 value of input 5 (multifunction) 32 heating request

64 cooling request

128 occupied status (see occupancy)

ENGL ISH hydronic syst.