• No results found

Liebert iCOM Service Menu Screens

In document with Liebert (сторінка 48-70)

Service menus allow customized settings for site operations. Service Menu screens employ a coding that begins with “S” and is followed by parameters and information, such as settings. Gaining access to most Service Menus requires entering a password; the Service Menu password is 5010; see 4.3.3 - Entering the Password for assistance.

The Liebert iCOM control firmware is being updated constantly. As a result, the Service Menu parameters in this manual may be slightly different from what is shown on a cooling unit’s display.

Figure 43 Setpoints screen

SERVICE MENUS

to select parameter to change level

to open requested menu ESC to unselect

to navigate

+

WELLNESS

SET ALARMS SERVICE

+/-

NETWORK SET UP XDIO

°C / °F

% RH SET

SETPOINTS

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) Min Room Temperature Setpoint Temperature Control Type Temperature Proportional Band Temperature Integration Tiime Temperature Derivative Dewpoint Margin Minimum Control Point Min Percent Cooling Setpoint S101

S102 S103 S104 S105 S106 S107 S108 S109 S110 S111

????

60.0°F Intelligent 7.0°F min sec 4.0°F 50.0°F 10%

UNIT 01

Liebert iCOM Control—Firmware Version XP1.00.010.STD Min Room Temperature Setpoint—Sets the minimum room temperature the unit will attempt to maintain. If the temperature falls below this point, unit will raise the refrigerant temperature to reduce the amount of cooling. Adjustable from 50 to 80°F (10.0 to 26.7°C), the factory default setting is 60°F (15.6°C).

Temperature Control Type—Selects the type of control the system will use to activate cooling. The Liebert iCOM control has three temperature control types: Proportional, PI and Intelligent. The factory default is Intelligent.

Proportional—If Proportional Control is selected, the percent cooling requirement is

determined by the difference between the air temperature sensor reading and the temperature setpoint. As the air temperature rises above the temperature setpoint, the percent cooling required increases proportionally (from 0 to 100%) over half the programmable temperature proportional band. The percent heating requirement (0 to 100%) is determined the same way when the air temperature falls below the setpoint.

PI—If PI Control is selected, the percent cooling requirement is calculated by adding together two individual terms, proportional and integral. The proportional term is calculated in a manner similar to the previously described Proportional control. The integral term (sometimes called reset action) is calculated by measuring how much and for how long the air temperature has been above or below the setpoint. If the actual air temperature is above the setpoint, the percent requirement is slowly but continuously increased until the total is sufficient to bring the return room air back to the setpoint.

Intelligent—If Intelligent Control is selected, the air temperature is controlled at or near the setpoint. The percent temperature adjustment required is calculated based on logic that is programmed into the control. These rules simulate the actions that would be taken by a human operator manually controlling the system.

Temperature Proportional Band—Adjusts the activation points of compressors or rate of change based on the actual sensor values deviation from setpoint. The smaller this number the faster the compressors and valve(s) will increase capacity. Too small of a number may cause the unit to short cycle the compressors or excessively reposition the valve. This parameter is adjustable from 1.8 to 54.0°F (1.0 to 30.0°C). The factory default setting is 7.0°F (3.9°C).

Temperature Integration Time—Temperature integration takes into consideration the amount of time the actual temperature has deviated from the setpoint. The larger this deviation is the longer the unit will wait before corrective action is taken to achieve the setpoint. This parameter is adjustable from 0 to 15 minutes. The factory default is 0.

Temperature Derivative Time—Monitors the rate of change and will reduce or increase the amount of corrective action based on the actual temperature increasing or decreasing toward the temperature setpoint. This parameter is adjustable from 0-900 seconds. The factory default is 0.

Dewpoint Margin—Selects the difference between the room dew point and the refrigerant

temperature control point. This parameter is adjustable from 4.0 to 10.0°F (2.2 to 6.0°C). The factory default setting is 4.0°F (2.2°C).

Minimum Control Point—Sets the minimum supply refrigerant temperature the Liebert XDP will maintain. This parameter is adjustable from 40 to 80°F (4.4 to 27.0°C). The factory default is 55°F (12.8°C).

Min Percent Cooling Setpoint—Selects the lowest percent call for cooling during normal operations. Whenever the unit is not in startup mode or OFF, the percent call for cooling cannot go below this value. The parameter is adjustable from 5 to 30%. The factory default is 15%.

NOTE

This is not a true room temperature setpoint. The Liebert XDP has no heaters; it will try to cool as much as possible. If the Liebert XDP is able to cool the room to this setpoint, it will reduce its cooling action to try to keep the room temperature at or above this setpoint.

Liebert iCOM Control—Firmware Version XP1.00.010.STD Figure 44 Maintenance—Basic Settings screen, page 1 of 7

Maintenance Frequency Per Year—Sets the number of expected maintenance visits in a one year time span.

Max Bonus—Increases the time until the next required maintenance. Service personnel should assign a bonus when a service visit finds all components working optimally.

Max Penalty—Decreases the time until the next maintenance cycle. Service personnel should assign a penalty when a service visit finds excessive wear on components.

Last Maintenance—Date set during the service call. It also indicates to other service personnel the date of the last visit.

Service Engineer—Provides a label for the service representative to list either the company name or representative’s name.

Confirm PM—Confirms that the service representative has completed the preventive maintenance and resets the next maintenance date.

Calculated Next Maintenance—Provides a date to for the next expected maintenance based on the last preventive maintenance performed (Confirm PM), component starts, run hours and the penalty or bonus set in the Liebert iCOM control.

Basic Settings (page 1 of 7) SYSTEM PASSWORD (Actual Level 0) ????

Maintenance Frequency Per Year 1

Max Bonus 0

Max Penalty 0

Last Maintenance 08/25/2011

Service Engineer NOBODY

Confirm PM No

Calculated Next Maintenance 08/2014 S001

S002 S003 S004 S005 S006 S007 S008 S009 S010 S011

to confirm for next/previous unit

then

to select parameter

to change parameter

Liebert iCOM Control—Firmware Version XP1.00.010.STD Figure 45 Maintenance—Pump 1 Settings screen, page 2 of 7

Number of Starts—Shows the number of starts for the unit’s Pump 1.

Run Hours—Shows the number of run hours for the unit’s Pump 1.

Average Run Time—Shows the average run time of the unit’s Pump 1.

Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 1.

Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 1.

Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 1.

Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 1. The unit will always take the value from the worst component for the next maintenance indication.

Pump 1 Settings (page 2 of 7) UNIT 1 S012

S013 S014 S015 S016 S017 S018 S019 S020 S021 S022

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Number of Starts 31

Run Hours 453hrs

Average Run Time 876min

Starts per Day Best 1

Starts per Day Worst 24

Number of Alarms 1

Actual Bonus 0

Liebert iCOM Control—Firmware Version XP1.00.010.STD Figure 46 Maintenance—Pump 2 Settings screen, page 3 of 7

Number of Starts—Shows the number of starts for the unit’s Pump 2.

Run Hours—Shows the number of run hours for the unit’s Pump 2.

Average Run Time—Shows the average run time of the unit’s Pump 2.

Starts per Day Best—Displays the lowest number of starts in a rolling 24 hour period for Pump 2.

Starts per Day Worst—Displays the highest number of starts in a rolling 24 hour period for Pump 2.

Number of Alarms—Displays the number of alarms that have occurred with the unit’s Pump 2 Actual Bonus—Displays the actual calculation of wellness for the unit’s Pump 2. The unit will always take the value from the worst component for the next maintenance indication.

Figure 47 Maintenance screens, pages 4 through 7

Pages 4 through 7 apply only to the Liebert XDC. No Liebert XDP parameters are present.

Pump 2 Settings (page 3 of 7) UNIT 1 S023

S024 S025 S026 S027 S028 S029 S030 S031 S032 S033

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Number of Starts 2

Run Hours 0hrs

Average Run Time 0min

Starts per Day Best 1

Starts per Day Worst 24

Number of Alarms 1

Actual Bonus 0

Compressor 1A Settings (page 4 of 7) UNIT 1 S034

S035 S036 S037 S038 S039 S040 S041 S042 S043 S044

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Compressor 1B Settings (page 5 of 7) UNIT 1 S045

S046 S047 S048 S049 S050 S051 S052 S053 S054 S055

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Compressor 2A Settings (page 6 of 7) UNIT 1 S056

S057 S058 S059 S060 S061 S062 S063 S064 S065 S066

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Compressor 2B Settings (page 7 of 7) UNIT 1 S067

S068 S069 S070 S071 S072 S073 S074 S075 S076 S077

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Liebert iCOM Control—Firmware Version XP1.00.010.STD Figure 48 Diagnostics/Service Mode screen, page 1 of 6

Page 1 applies to the Liebert XDC only. No Liebert XDP parameters are present.

Figure 49 Diagnostics/Service Mode screen, page 2 of 6

Manual Mode—Used to place the Liebert iCOM control in manual mode. This is the initial setting necessary to activate any of the following items. When the Liebert iCOM is not in manual mode, each service menu item shows the current status of each parameter.

Pump 1—Starts the unit’s Pump 1.

Pump 2—Starts the unit’s Pump 2.

3P Start Active/Complete—Displays if the startup routine is active, and if it is completed.

3P Actuator Input Request—Shows the % call for cooling.

3P Actuator Position—Sets the position of the actuator 0-100% in manual mode.

3P Actuator Open—Opens the 3P actuator when set to ON in manual mode.

3P Actuator Close—Closes the 3P actuator when set to ON in manual mode Valve Feedback—Opens the valve % in manual mode.

DIAGNOSTICS/SERVICE MODE (page 1 of 6) UNIT 01 S301

S302 S303 S304 S305 S306 S307 S308 S309 S310 S311

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

DIAGNOSTICS/SERVICE MODE (page 2 of 6) UNIT 01 S312

S313 S314 S315 S316 S317 S318 S319 S320 S321 S322

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Manual Mode No

Pump 1 Off

Pump 2 Off

3P Start Completed/Active No No

3P Actuator Input Request 30.00%

3P Actuator Position 30%

3P Actuator Open Off

3P Actuator Close Off

Valve Feedback 30%

Liebert iCOM Control—Firmware Version XP1.00.010.STD Figure 50 Diagnostics/Service Mode screen, page 3 of 6

Page 3 applies to the Liebert XDC only. No Liebert XDP parameters are present.

Figure 51 Diagnostics/Service Mode screen, page 4 of 6

Manual Mode Control Type—Not currently used.

Manual Deviation—Not currently used.

Analog Output Ramp 1—Sets the value of Analog Output 1 value as a percentage. The factory default for the Liebert XDP is the Valve % Open.

Analog Output Ramp 2—Sets the value of Analog Output 2 value as a percentage. The factory default for the Liebert XDP is the Call for Cooling.

Analog Output Ramp 3—Sets the value of Analog Output 3 value as a percentage. The factory default for the Liebert XDP is the CW Temp.

Analog Output Ramp 4—Sets the value of Analog Output 4 value as a percentage. The factory default for the Liebert XDP is the refrigerant temperature.

Alarm Relay—Used to activate the Liebert iCOM’s common alarm relay output.

Warning Relay—Used to activate the Liebert iCOM’s warning relay output.

DIAGNOSTICS/SERVICE MODE (page 3 of 6) UNIT 01 S323

S324 S325 S326 S327 S328 S329 S330 S331 S332 S333

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

DIAGNOSTICS/SERVICE MODE (page 4 of 6) UNIT 01 S334

S335 S336 S337 S338 S339 S340 S341 S342 S343 S344

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Manual Mode Control Type Full

Manual Deviation 12%

Analog Output Ramp 1 30%

Analog Output Ramp 2 0%

Analog Output Ramp 3 60%

Analog Output Ramp 4 58%

Alarm Relay Off

Warning Relay Off

Liebert iCOM Control—Firmware Version XP1.00.010.STD Figure 52 Diagnostics/Service Mode screen, page 5 of 6

Status Remote Shutdown—Displays the status of the unit’s remote shutdown input.

Status Fan Failure—Displays the status of the dry contact to communicate fan failure at a module.

(The dry contacts are not used to communicate a fan failure alarm when using CANbus.) Status Diff Press Switch 1—Displays the status of the differential pressure switch.

Status Customer Input 1—Displays the status of the customer input 1 alarm.

Status Condensation Detect—Displays the status of the dry contact to communicate condensate detection at a module.

Status Unit Ready—Shows unit status when a secondary device, such as a fire detection system, is employed.

Figure 53 Diagnostics/Service Mode screen, page 6 of 6

Page 6 applies to the Liebert XDC only. No Liebert XDP parameters are present.

DIAGNOSTICS/SERVICE MODE (page 5 of 6) UNIT 01 S345

S346 S347 S348 S349 S350 S351 S352 S353 S354 S355

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Status Remote Shutdown o–o On

Status Fan Failure o/o Ok

Status Diff Press Switch 1 o/o Act

Status Customer Input 1 o/o Ok

Status Condensation Detect o/o Ok

Status Unit Ready o–o On

DIAGNOSTICS/SERVICE MODE (page 6 of 6) UNIT 01 S356

S357 S358 S359 S360 S361 S362 S363 S364 S365 S366

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Liebert iCOM Control—Firmware Version XP1.00.010.STD Figure 54 Set Alarms screen, page 1 of 7

High Room Air Temperature—Sets the threshold for a high room air temperature alarm. The range for the high room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).

Low Room Air Temperature—Sets the threshold for a low room air temperature alarm. The range for the low room air temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 55°F (12.8°C).

High Room Dewpoint—Sets the threshold for a return high dew point alarm. The range for the high room dew point alarm is from 33.8 to 95°F (1 to 35°C); the default is 65°F (18.3°C).

High Refrigerant Temperature—Sets the threshold for a high a refrigerant temperature alarm.

The range for the high supply refrigerant temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 80°F (26.7°C).

High Chilled Water Temperature—Sets the threshold chilled water temperature for a supply high chilled water temperature alarm. The range for the high supply refrigerant temperature alarm is from 33.8 to 95°F (1 to 35°C); the default is 60°F (15.6°C).

SET ALARMS (page 1 of 7) UNIT 01

S201 S202 S203 S204 S205 S206 S207 S208 S209 S210 S211

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

High Room Air Temperature 88.0°F

Low Room Air Temperature 55.0°F

High Room Dewpoint 65.0°F

High Refrigerant Temperature 80.0°F

High Chilled Water Temperature 60.0°F

Liebert iCOM Control—Firmware Version XP1.00.010.STD Figure 55 Set Alarms screen, page 2 of 7

Customer Input 1—Selects the device and operation of the customer input. Each event reflects a different alarm and possible action to the unit. Selectable options are:

Call Service C-Input Water Smoke

Customer Input 1 active when—Selects whether the Customer Input 1 input is normally closed or normally open.

WARNING ACTIVATES ALARM RELAY—Sets the alarm relay (K3) to activate when a warning occurs.

Reset Disabled Alarms—Resets disabled events.

The Set Alarm Screens (Figure 56 through 60) permit setting the operation of an active alarm. Each event can be enabled or disabled and can be set to operate as an alarm, warning or message. The delay is the time the control waits before reporting the event.

Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes the red LED on the display.

Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event viewer / front display and flashes the red LED on the display.

Message: Shows the event in the event viewer and on the front display.

SET ALARMS (page 2 of 7) UNIT 01

S212 S213 S214 S215 S216 S217 S218 S219 S220 S221 S222

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) ????

Customer Input 1 Water Alarm

Customer Input 1 active when Closed

WARNING ACTIVATES ALARM RELAY Yes

Reset Disabled Alarms No

Liebert iCOM Control—Firmware Version XP1.00.010.STD Figure 56 Set Alarms screen, page 3 of 7

HIGH TEMP SENSOR A—Enables or disables the High Temperature Sensor A event, which occurs when the reading from Sensor A is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOW TEMP SENSOR A—Enables or disables the Low Temperature Sensor A event, which occurs when the reading from Sensor A is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

HIGH TEMP SENSOR B—Enables or disables the High Temperature Sensor B event, which occurs when the reading from Sensor B is above the user-specified alarm setpoint. Sets how the event is reported as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOW TEMP SENSOR B—Enables or disables the Low Temperature Sensor B event, which occurs when the reading from Sensor B is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

HIGH DEWPOINT—Enables or disables the High Dewpoint event, which occurs when the

calculated dew point at Sensor A or Sensor B is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

SENSOR A FAILURE—Enables or disables the Sensor A Failure event, which occurs when the control no longer senses a signal from Sensor A. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

SENSOR B FAILURE—Enables or disables the Sensor B Failure event, which occurs when the control no longer senses a signal from Sensor B. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

HIGH CHILLED WATER TEMP—Enables or disables the High Chilled Water Temp event, which occurs when the reading from Supply Chilled Water Sensor is above the user-specified alarm setpoint.

Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

SUPPLY CW SENSOR FAILURE—Enables or disables the Supply CW Sensor Failure Failure event, which occurs when the control no longer senses a signal from Supply CW Sensor. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

SET ALARMS (page 3 of 7) UNIT 01

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) HIGH TEMP SENSOR A LOW TEMP SENSOR A HIGH TEMP SENSOR B LOW TEMP SENSOR B HIGH DEWPOINT SENSOR A FAILURE SENSOR B FAILURE

HIGH CHILLED WATER TEMP SUPPLY CW SENSOR FAILURE S223

S224 S225 S226 S227 S228 S229 S230 S231 S232 S233 S234 S235

DELAY 30 30 30 30 30

30

????

TYPE ALM ALM ALM ALM ALM ALM ALM ALM ALM EN-DIS

ENABLE

ENABLE

ENABLE

ENABLE

ENABLE

ENABLE

ENABLE

ENABLE

ENABLE

Liebert iCOM Control—Firmware Version XP1.00.010.STD Figure 57 Set Alarms screen, page 4 of 7

HIGH REFRIGERANT TEMP—Enables or disables the High Refrigerant Temp event, which occurs when the reading from supply refrigerant temperature sensor is above the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOW REFRIGERANT TEMP—Enables or disables the Low Refrigerant Temp event, which occurs when the reading from supply refrigerant temperature sensor is below the user-specified alarm setpoint. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

SUPPLY REFRIGERANT SENSOR—Enables or disables the Supply Refrigerant Sensor event, which occurs when the control no longer senses a signal from the Supply Refrigerant Sensor. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOSS OF FLOW PUMP 1—Enables or disables the Loss of Flow Pump 1 event, which occurs when Pump 1 is commanded to run and the differential pressure switch does not sense differential

pressure. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

LOSS OF FLOW PUMP 2—Enables or disables the Loss of Flow Pump 2 event, which occurs when Pump 2 is commanded to run and the differential pressure switch does not sense differential

pressure. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

PUMP SHORT CYCLE—Enables or disables the Pump Short Cycle event, which occurs when flow is not established by either pump for 30 minutes. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

CONTROL VALVE FAILURE—Enables or disables the Control Valve Failure event, which occurs when the chilled water control valve has been commanded by the control to open or close and no change is detected by the valve position signal. Sets how the event is reported: as an alarm, a warning or a message. Specifies how long the control waits before reporting the event.

SET ALARMS (page 4 of 7) UNIT 01

to confirm for next/previous unit

then

to select parameter to change parameter

PASSWORD (Actual Level 0) HIGH REFRIGERANT TEMP LOW REFRIGERANT TEMP

SUPPLY REFRIGERANT SENSOR LOSS OF FLOW PUMP 1

LOSS OF FLOW PUMP 2 PUMP SHORT CYCLE

CONTROL VALVE FAILURE S236

S237 S238 S239 S240 S241 S242 S243 S244 S245 S246 S247 S248

DELAY 30 30

????

TYPE ALM ALM ALM ALM ALM ALM

ALM EN-DIS

ENABLE ENABLE ENABLE ENABLE ENABLE ENABLE

ENABLE

In document with Liebert (сторінка 48-70)