• No results found

HOW TO DIAGNOSE THE TROUBLE

In document Indoor Unit Outdoor Unit (сторінка 70-97)

The pulse motor circuits are mounted to both indoor and outdoor units. Therefore, diagnose troubles according to the trouble diagnosis procedure as described below. (Refer to the check points in servicing written on the wiring diagrams attached to the indoor/outdoor units.)

Table 11-1

K Precautions when handling the new inverter (3DV Inverter)

CAUTION: HIGH VOLTAGEN

The high voltage circuit is incorporated.

Be careful to do the check service, as the electric shock may be caused in case of touching parts on the P.C. board by hand.

The new inverter (3DV inverter) will be incorporated starting with this unit.

(3DV: 3-shunt Discrete Vector control)

K The control circuitry has an uninsulated construction.

No.

1 2 3 4 5

Troubleshooting Procedure First Confirmation

Primary Judgment

Judgment by Flashing LED of Indoor Unit Self-Diagnosis by Remote Controller Judgment of Trouble by Every Symptom

Page 62 63 63 64 67

No.

6 7 8 9 10

Troubleshooting Procedure How to Check Simply the Main Parts Troubleshooting

How to Diagnose Trouble in Outdoor Unit How to Check Simply the Main Parts How to Simply Judge Whether Outdoor Fan Motor is Good or Bad

Page 72 73 75 76 81

IGBT × 6

FET × 6 MCU

Compressor

Fan motor Shared potential

Driver Driver

Amplifier

Amplifier

Fig. 11-1

CAUTION

A high voltage (equivalent to the supply voltage) is also energized to ground through the sensors, PMV and other low-voltage circuits. The sensor leads and other wires are covered with insulated tubes for protection. Nevertheless, care must be taken to ensure that these wires are not pinched.

Take sufficient care to avoid directly touching any of the circuit parts without first turning off the power.

At times such as when the circuit board is to be replaced, place the circuit board assembly in a vertical position.

Laying the board flat on an electrically conductive object (such as the top panel of the air conditioner's outdoor unit) while a charge is still retained by the electrolytic capacitors of the inverter's main circuit may cause short-circuiting between the electrolytic capacitors and secondary circuit components and result in damage to the components.

Sensor leads

Do NOT lay the circuit board assembly flat.

K Precautions when inspecting the control section of the outdoor unit NOTE :

A large-capacity electrolytic capacitor is used in the outdoor unit controller (inverter). Therefore, if the power supply is turned off, charge (charging voltage DC280 to 380V) remains and discharging takes a lot of time.

After turning off the power source, if touching the charging section before discharging, an electrical shock may be caused. Discharge the electrolytic capacitor completely by using soldering iron, etc.

< Discharging method >

1. Remove the inverter cover (plating) by opening four mounting claws.

2. As shown below, connect the discharge resistance (approx. 100Ω40W) or plug of the soldering iron to voltage between + – terminals of the C14 (“CAUTION HIGH VOLTAGE” is indicated.) electrolytic capacitor (500µF/400V or 760µF/400V) on P.C. board, and then perform discharging.

Fig. 11-2

Discharging position (Discharging period 10 seconds or more)

Plug of soldering iron

Inverter cover

P. C. board (Soldered surface)

Fig. 11-3

– 71 –

11-1. First Confirmation

11-1-1. Confirmation of Power Supply

Confirm that the power breaker operates (ON) normally.

11-1-2. Confirmation of Power Voltage

Confirm that power voltage is AC 220–230–240 ± 10%.

If power voltage is not in this range, the unit may not operate normally.

11-1-3. Operation Which is not a Trouble (Program Operation)

For controlling the air conditioner, the program operations are built in the microcomputer as described in the following table.

If a claim is made for running operation, check whether or not it meets to the contents in the following table.

When it does, we inform you that it is not trouble of equipment, but it is indispensable for controlling and main- taining of air conditioner.

Table 11-1-1 No.

1

2

3

4

5

6

Operation of air conditioner When power breaker is turned “ON”, the operation indicator (Green) of the indoor unit flashes.

Compressor may not operate even if the room temperature is within range of compressor-ON.

In Dry and ECO mode, FAN (air flow) display does not change even though FAN (air flow select) button is operated.

Increasing of compressor motor speed stops approx. 30 seconds after operation started, and then compressor motor speed increases again approx. 30 seconds after.

In AUTO mode, the operation mode is changed.

In HEAT mode, the compressor motor speed does not increase up to the maxi- mum speed or decreases before the temperature arrives at the set temperature.

Description

The OPERATION lamp of the indoor unit flashes when power source is turned on. If [START/STOP] button is operated once, flashing stops.

(Flashes also in power failure)

The compressor does not operate while compressor restart delay timer (3-minutes timer) operates.

The same phenomenon is found after power source has been turned on because 3-minutes timer operates.

The air flow indication is fixed to [AUTO].

For smooth operation of the compressor, the compres- sor motor speed is restricted to Max. 41 rps for 2 min- utes, and Max.91 rps for 2 minutes to 3 minutes, respec- tively after the operation has started.

After selecting Cool or Heat mode, select an operation mode again if the compressor keeps stop status for 15 minutes.

The compressor motor speed may decrease by high- temp. release control (Release protective operation by temp.-up of the indoor heat exchanger) or current release control.

11-2. Primary Judgment

To diagnose the troubles, use the following methods.

1) Judgment by flashing LED of indoor unit

2) Self-diagnosis by service check remote controller 3) Judgment of trouble by every symptom

Firstly use the method 1) for diagnosis. Then, use the method 2) or 3) to diagnose the details of troubles.

11-3. Judgment by Flashing LED of Indoor Unit

While the indoor unit monitors the operation status of the air conditioner, if the protective circuit operates, the contents of self-diagnosis are displayed with block on the indoor unit indication section.

Table 11-3-1

NOTES :

1. The contents of items B and C and a part of item E are displayed when air conditioner operates.

2. When item B and C, and item B and a part of item E occur concurrently, priority is given to the block of item B.

3. The check codes can be confirmed on the remote controller for servicing.

OPERATION (Green) Flashing display (1 Hz)

OPERATION (Green) TIMER (Yellow) FILTER (Orange) Flashing display (5 Hz) OPERATION (Green) FILTER (Orange) Flashing display (5 Hz) OPERATION (Green) TIMER (Yellow) Flashing display (5 Hz) OPERATION (Green)

Flashing display (5 Hz) Protective circuit operation for indoor P.C. board

Protective circuit operation for connecting cable and serial signal system

Protective circuit operation for outdoor P.C. board

Protective circuit operation for others (including compressor)

Power failure (when power is ON) Indoor indication

lamp flashes.

Which lamp does flash?

Item

A

B

C

D

E

Check

code Block display Description for self-diagnosis

– 73 –

11-4. Self-Diagnosis by Remote Controller (Check Code)

1. If the lamps are indicated as shown B to E in Table 11-3-1, execute the self-diagnosis by the remote controller.

2. When the remote controller is set to the service mode, the indoor controller diagnoses the operation condi- tion and indicates the information of the self-diagnosis on the display of the remote controller with the check codes. If a fault is detected, all lamps on the indoor unit will flash at 5Hz and it will beep for 10 seconds (Beep, Beep, Beep ... ). The timer lamp usually flashes (5Hz) during self-diagnosis.

11-4-1. How to Use Remote Controller in Service Mode

TEMP

Press [CHECK] button with a tip of pencil to set the remote controller to the service mode.

• “ ” is indicated on the display of the remote controller.

Press [ON ] or [OFF ] button

If there is no fault with a code, the indoor unit will beep once (Beep) and the display of the remote controller will change as follows :

• The TIMER indicator of the indoor unit flashes continuously.

(5 times per 1 sec.)

• Check the unit with all 52 check codes ( to ) as shown in Table-11-4-1.

• Press [ON ] or [OFF ] button to change the check code backward.

If there is a fault, the indoor unit will beep for 10 seconds (Beep, Beep, Beep...).

Note the check code on the display of the remote controller.

• 2-digits alphanumeric will be indicated on the display.

• All indicators on the indoor unit will flash.

(5 times per 1 sec.)

Press [START/STOP] button to release the service mode.

• The display of the remote controller returns to as it was before service mode was engaged.

Time shortening method.

1. Press SET button while pushing CHECK button.

2. Press [START/STOP] button.

1 2

3 4

Alphanumeric characters are used for the check codes.

is 5. is 6.

is A. is B.

is C. is D.

P R E S E T

ONE -T OUC H

QUIE T

S WING

T IME R ON

F IL TE R

C HK C L OC K

OF F C L R

S L E E P S E T

F IX Hi-P OWE R E C O P UR E C OMF OR T

S L E E P MODE TE MP

F A N

TOSHIBA

• • •

Fig. 11-4-1

Check code Check

code

Judgment and action

1. Check the room temp. sensor.

2. When the room temp. sensor is normal, check P.C. board.

1. Check heat exchanger sensor.

2. When heat exchanger sensor is normal, check P.C. board.

1. Check the motor.

2. When the motor is normal, check P.C. board.

Replace P.C. board.

1. When the outdoor unit never operate:

1) Check connecting cable, and correct if defective wiring.

2) Check 25A fuse of inverter P.C. board.

3) Check 3.15A of inverter P.C.

board.

2. To display [Other] block during operation, check compressor thermo. operation and supply gas (check gas leak also).

3. Unit operates normally during check.

If return serial signal does not stop between indoor terminal board 2 and 3, replace inverter P.C. board.

If signal stops between indoor terminal board 2 and 3, replace indoor P.C. board.

11-4-2. Caution at Servicing

1. After servicing, press the START/STOP button to return to the normal mode.

2. After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power supply again so that memory in the microcomputer returns the initial status.

However, the check codes are not deleted even if the power supply is turned off because they are stored in the fixed memory.

3. After servicing, press [CLR] button under check mode status and then send the check code “7F” to the indoor unit. The error code stored in memory is cleared.

Table 11-4-1

Block distinction Operation of diagnosis function Block

Indoor P.C.

board etc.

Not displayed

Connecting cable and serial signal

Cause of operation

Short-circuit or discon- nection of the room temperature sensor (TA sensor).

Being out of place, disconnection, short- circuit, or migration of heat exchanger sensor (TC sensor)

Lock of indoor fan or trouble on the indoor fan circuit

Trouble on other indoor P.C. boards

Return serial signal is not sent to indoor side from operation started.

1) Defective wiring of connecting cable 2) Operation of compres-

sor thermo Gas shortage Gas leak

Air conditioner

status Operation continues.

Operation continues.

All off

Operation continues.

Operation continues.

Remarks

Displayed when error is detected.

Displayed when error is detected.

Displayed when error is detected.

Displayed when error is detected.

Flashes when trouble is detected on Return serial signal, and normal status when signal is reset.

– 75 –

Check code Check

code

Block distinction

Judgment and action

Even if trying operation again, all operations stop immediately. : Replace P.C. board.

1. Even if connecting lead wire of compressor is removed, position-detect circuit error occurred. : Replace P.C. board.

2. Measure resistance between wires of compressor, and perform short-circuit. : Replace compressor.

Even if trying operation again, all operations stop immediately. : Replace P.C. board.

1. Check sensors (TE, TS).

2. Check P.C. board.

1. Check discharge temp. sensor (TD).

2. Check P.C. board

Position-detect error, over-current protective operation of outdoor fan drive system, fan lock, etc. : Replace P.C. board or fan motor.

1. Check outdoor temp. sensor (TO).

2. Check P.C. board.

When 20 seconds passed after start-up, position-detect circuit error occurred. : Replace compressor.

Trouble on P.M.V.

1. Repeat Start and Stop with interval of approx. 10 to 40 minutes. (Code is not displayed during operation.)

Supply gas.

(Check also gas leak).

2. Unit operates normally during check.

If return serial signal does not stop between indoor terminal block 2 and 3, replace inverter P.C. board.

If signal stops between indoor terminal block 2 and 3, replace indoor P.C. board.

1. Trouble on compressor 2. Trouble on wiring of compressor

(Missed phase)

1. Check dischage temp. sensor (TD).

2. Gas leakage 3. Trouble on P.M.V.

1. Check power voltage.

(220–230–240 V +10%) 2. Overload operation of refrigera-

tion cycle

Check installation condition (Short-circuit of outdoor diffuser).

1. Check 4-way valve operation.

Block Outdoor P.C.

board

Not displayed Outdoor P.C.

board

Others (including compressor)

Operation of diagnosis function Cause of operation

Inverter over-current protective circuit operates. (Short time) Position-detect circuit error or short-circuit between windings of compressor

Current-detect circuit error

Being out of place, disconnection or short- circuit of the outdoor heat exchanger sensor (TE) or suction temp.

sensor (Ts)

Disconnection or short- circuit of discharge temp. sensor Outdoor fan drive system error

Outdoor heat exchanger temp. sensor error Compressor drive output error, Compressor error (lock, missing, etc.), Break down

Return serial signal has been sent when operation started, but it is not sent from halfway.

1) Compressor thermo.

operation Gas shortage Gas leak

2) Instantaneous power failure

Compressor does not rotate.

(Current protective circuit does not operate when a specified time passed after compressor had been activated.) Discharge temp.

exceeded 117°C

Break down of compressor

4-way valve inverse error (TC sensor value lowered during heating operation.)

Air conditioner

status All off

All off

All off

All off

All off

All off

Operation continues All off

Operation continues

All off

All off

All off

Operation continues

Remarks Displayed when error is detected.

Displayed when error is detected.

Displayed when error is detected.

Displayed when error is detected.

Displayed when error is detected.

Displayed when error is detected.

——

Displayed when error is detected.

Flashes when trouble is detected on return serial signal, and normal status when signal is reset.

Displayed when error is detected.

Displayed when error is detected.

Displayed when error is detected.

——

11-5. Judgment of Trouble by Every Symptom

11-5-1. Indoor Unit (Including Remote Controller) (1) Power is not turned on (Does not operate entirely)

<Primary check>

1. Is the supply voltage normal?

2. Is the normal voltage provided to the outdoor unit?

3. Is the crossover cable connected properly?

4. Is the fuse (F01) blown?

• Be sure to disconnect the motor connector CN31 after shut off the power supply, or it will be a cause of damage of the motor.

(2) Power is not turned on though Indoor P.C. board is replaced

<Confirmation procedure>

NO

Turn off power supply once, and 5 second later, turn it on again.

Is OPERATION indicator flashing?

Is it possible to turn on power supply by pushing

[START/STOP] button on remote controller?

Is voltage (DC12V or 5V) indicated on rear of

indoor control board normal?

Does transmission mark on remote controller flash

normally,and is its signal transmitted properly?

Item by symptoms Operation Check Item Considerable principle cause

Measures

Parts (R01, C01, C02, R02, C03, D01, D02, D03, D04,

Remote controller is defective.

Refer to (5) “Troubleshooting for remote controller”.

Parts of a power supply circuit defective.

Unit operates normally.

Replace main P.C. board Is fuse (F01)

of indoor control board blown?

NO

NO NO

NO YES

YES

YES YES

YES

YES

NO NO

To item of

“Power supply is not turned on”.

Turn on power supply.

Does OPERATION indicator flash? Is wired correctly to white and

black lead wires of terminal block? Correct wiring.

T101) are defective.

Microcomputer is defective.

YES

( RAS-10,13 Series )

• Be sure to disconnect the motor connector CN31 after shut off the power supply, or it will be a cause of damage of the motor.

(2) Power is not turned on though Indoor P.C. board is replaced

<Confirmation procedure>

NO

Turn off power supply once, and 5 second later, turn it on again.

Is OPERATION indicator flashing?

Is it possible to turn on power supply by pushing

[START/STOP] button on remote controller?

Is voltage (DC12V or 5V) indicated on rear of

indoor control board normal?

Does transmission mark on remote controller flash

normally,and is its signal transmitted properly?

Is DC310–340V supplied between

CN10 1 – 3 ?

Does fan motor connector between CN10 1 –

3 short-circuit?

Item by symptoms Operation Check Item Considerable principle cause

Measures

Parts (R04, R05, DB01, C01, C03, IC01 and T01) are defective.

Remote controller is defective.

Refer to (5) “Troubleshooting for remote controller”.

Parts of a power supply circuit defective.

Unit operates normally.

Replace main P.C. board

Replace fan motor.

Is fuse (F01) of indoor control

board blown?

Microcomputer is defective.

NO NO

NO

NO NO

NO

YES

YES YES

YES YES

YES YES

YES YES

NO NO

To item of

“Power supply is not turned on”.

Turn on power supply.

Does OPERATION indicator flash? Is wired correctly to white and

black lead wires of terminal block? Correct wiring.

( RAS-16 Series )

– 77 –

Rdvised

Turn off power supply once, and turn it on again.

Start to operate indoor unit in cooling operation at airflow level “LOW”.

YES

(3) Only the indoor motor fan does not operate

<Primary check>

1. Is it possible to detect the power supply voltage (AC220–240V) between Q and R on the terminal block?

2. Does the indoor fan motor operate in cooling operation?

(In heating operation, the indoor fan motor does not operate for approximately 10 minutes after it is turned on, to prevent a cold air from blowing in.)

Control P.C. board failure

Change airflow level to “HIGH”.

When rotating the cross-flow fan by hand

at the operation stop condition, is the rotation signal (DC+12V 0V) detected between

2 (Purple lead) and 3 (Blue lead) of the motor

connector (CN33) (1 pulse / 1 revolutio).

Dose AC120V or ligher voltage apply to between red and black lead

of the motor?

Is it possible to change airflow level

to “HIGH”? Stop the operation Does fan motor

continue to operate?

Does indoor fan operate?

Fan motor operates normally.

Replace main P.C. board.

Replace YES

YES

YES

Motor circuit (D301, IC31, Q301 12V power circuit (T101) failure.

Replace the fan motor.

YES

NO

NO

Replace the P.C. board.

NO

NO

NO

Turn OFF the power Change airflow level

to “HIGH”.

Change airflow level to “HIGH”.

Is it possible to YES

rotate cross-flow fan by hand properly?

NO Turn OFF the power

bearing.

( RAS-10,13 Series )

Turn off power supply once, and turn it on again.

Start to operate indoor unit in cooling operation at airflow level “LOW”.

Turn off indoor unit and remove connector from motor.

Then start to operate indoor unit with remote controller.

Turn off indoor unit and remove connector from motor.

Then push START/STOP button on remote controller to stop flashing lamp on indoor unit.

Change airflow level to “HIGH”.

Turn off indoor unit and rotate cross-flow fan by hand when the unit is on standby.

At this time, is it possible to detect DC 1V or more between 5 + and 3

of motor connector (CN31).

Start to operate the indoor unit in except heating operation.

At this time, is it possible to detect DC 1V or more between 5 + and 3 of motor connector (CN31)?

(Check this condition within 15 seconds after

starting unit.) Start to operate the

indoor unit in except heating operation.

At this time, is it possible to detect DC 1V or more between

5 + and 3 – of motor connector (CN31)?

Is it possible to detect DC 1V or more between

5 + and 3 – of motor connector (CN31).

Is it possible to detect DC 310–340V between 1 + and 3 – of motor

connector (CN31).

(Motor connection condition) Is it possible to detect DC 15V

between 4 + and 3 – of motor connector (CN31).

Is it possible to detect DC 15V between 4 +

and 3 – of motor connector (CN31).

Is it possible to change airflow level

to “HIGH”?

Is it possible to rotate cross-flow fan by

hand properly?

Does fan motor continue to operate?

Does indoor fan operate?

Fan motor operates normally.

Peplace indoor fan motor.

Peplace main P.C. board.

Peplace bearing.

YES

YES

YES

YES YES

YES

YES

YES

YES

YES

NO

NO

YES

NO NO

NO

NO

NO

NO NO

NO

NO ( RAS-16 Series )

– 79 –

Revised-1

In document Indoor Unit Outdoor Unit (сторінка 70-97)