HBC controller

In document HYBRID CITY MULTI Databook (сторінка 64-69)

HB C

1. SPECIFICATIONS

I.HBC controller 1. SPECIFICATIONS

Model name CMB-WP108V-GA1

Number of branch 8

Power source 1-phase 220-230-240 V

50 Hz 60 Hz

Power input Cooling kW 0.45/0.46/0.47 0.45/0.46/0.47

(220/230/240) Heating kW 0.45/0.46/0.47 0.45/0.46/0.47

Current input Cooling A 2.89/2.83/2.79 2.89/2.83/2.79

(220/230/240) Heating A 2.89/2.83/2.79 2.89/2.83/2.79

Sound pressure level (measured in anechoice room) dB <A> 41

Applicable temperature range of installation site °C (D.B.) 0~32

External finish Galvanized steel plate

(Lower part drain pan: Pre-coated galvanized sheets + powder coating)

Connectable outdoor unit PURY-P200~500YLM-A1(-BS)/PURY-EP200~500YLM-A1(-BS) *a

Indoor unit capacity connectable to 1 branch Model P80 or smaller

(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81)

External dimension H x W x D mm 300 x 1,520 x 630

in. 11-13/16 x 59-7/8 x 24-13/16

Refrigerant piping diameter

To outdoor unit Connectable outdoor unit capacity

To P200 To P250/300 To P350 To P400 for each To P450/500 for each

High press. Pipe mm (in.)

O.D. 15.88 (5/8)

Brazed 19.05 (3/4)

Brazed 19.05 (3/4)

Brazed 15.88 (5/8)

Brazed 19.05 (3/4)

Brazed

Low press. Pipe mm (in.)

O.D.

19.05 (3/4) Brazed

22.2 (7/8) Brazed

28.58 (1-1/8) Brazed

19.05 (3/4) Brazed

22.2 (7/8) Brazed Water piping

diameter

To Indoor unit

Inlet Pipe mm I.D. 20

Outlet Pipe mm I.D. 20

Field drain pipe size mm (in.) O.D. 32 (1-1/4)

Net weight kg (lbs) 85 (188) [95 (210) with water]

Standard attachment

Document –

Accessory Drain Connection pipe (with flexible hose and insulation)

Optional parts –

Note 1.Works not included:

Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.

2.The equipment is for R410A refrigerant.

3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.

(For use in quiet environments with low background noise, position the HBC CONTROLLER at least 5 m away from any indoor units.) 4.Please install the HBC controller in a place where noise will not be an issue.

5.Please attach an expansion vessel (field supply).

6.Please use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework.

Furthermore, when using copper pipework use a non-oxidative brazing method.

Oxidation of the pipework will reduce the pump life.

7.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat.

8.Please install an air purge valve where air will gather in the water circuit.

9.Please install a pressure reducing valve and a strainer on the water supply to the HBC controller.

10.Please refer to the databook or the installation manual for the specified water quality.

11.This unit is not designed for outside installations.

12.Please always make water circulate or pull out the circulation water completely when not using it.

*Please do not use it as a drinking water.

13.Please do not use ground water and well water.

14.When installing the HBC unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.

(Refer to the databook and the installation manual).

*a. Cannot be connected to other than YLM series

0000003552.BOOK 62 ページ 2015年9月15日 火曜日 午後12時11分

1. SPECIFICATIONS

HB C

Model name CMB-WP1016V-GA1

Number of branch 16

Power source 1-phase 220-230-240 V

50 Hz 60 Hz

Power input Cooling kW 0.45/0.46/0.47 0.45/0.46/0.47

(220/230/240) Heating kW 0.45/0.46/0.47 0.45/0.46/0.47

Current input Cooling A 2.89/2.83/2.79 2.89/2.83/2.79

(220/230/240) Heating A 2.89/2.83/2.79 2.89/2.83/2.79

Sound pressure level (measured in anechoice room) dB <A> 41

Applicable temperature range of installation site °C (D.B.) 0~32

External finish Galvanized steel plate

(Lower part drain pan: Pre-coated galvanized sheets + powder coating)

Connectable outdoor unit PURY-P200~500YLM-A1(-BS)/PURY-EP200~500YLM-A1(-BS) *a

Indoor unit capacity connectable to 1 branch Model P80 or smaller

(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81)

External dimension H x W x D mm 300 x 1,800 x 630

in. 11-13/16 x 70-7/8 x 24-13/16

Refrigerant piping diameter

To outdoor unit Connectable outdoor unit capacity

To P200 To P250/300 To P350 To P400 for each To P450/500 for each

High press. Pipe mm (in.)

O.D. 15.88 (5/8)

Brazed 19.05 (3/4)

Brazed 19.05 (3/4)

Brazed 15.88 (5/8)

Brazed 19.05 (3/4)

Brazed

Low press. Pipe mm (in.)

O.D.

19.05 (3/4) Brazed

22.2 (7/8) Brazed

28.58 (1-1/8) Brazed

19.05 (3/4) Brazed

22.2 (7/8) Brazed Water piping

diameter

To Indoor unit

Inlet Pipe mm I.D. 20

Outlet Pipe mm I.D. 20

Field drain pipe size mm (in.) O.D. 32 (1-1/4)

Net weight kg (lbs) 97 (214) [110 (243) with water]

Standard attachment

Document –

Accessory Drain Connection pipe (with flexible hose and insulation)

Optional parts –

Note 1.Works not included:

Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.

2.The equipment is for R410A refrigerant.

3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.

(For use in quiet environments with low background noise, position the HBC CONTROLLER at least 5 m away from any indoor units.) 4.Please install the HBC controller in a place where noise will not be an issue.

5.Please attach an expansion vessel (field supply).

6.Please use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework.

Furthermore, when using copper pipework use a non-oxidative brazing method.

Oxidation of the pipework will reduce the pump life.

7.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat.

8.Please install an air purge valve where air will gather in the water circuit.

9.Please install a pressure reducing valve and a strainer on the water supply to the HBC controller.

10.Please refer to the databook or the installation manual for the specified water quality.

11.This unit is not designed for outside installations.

12.Please always make water circulate or pull out the circulation water completely when not using it.

*Please do not use it as a drinking water.

13.Please do not use ground water and well water.

14.When installing the HBC unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.

(Refer to the databook and the installation manual).

*a. Cannot be connected to other than YLM series

0000003552.BOOK 63 ページ 2015年9月15日 火曜日 午後12時11分

HB C

1. SPECIFICATIONS

Model name CMB-WP108V-GB1

Number of branch 8

Power source 1-phase 220-230-240 V

50 Hz 60 Hz

Power input Cooling kW 0.01/0.01/0.01 0.01/0.01/0.01

(220/230/240) Heating kW 0.01/0.01/0.01 0.01/0.01/0.01

Current input Cooling A 0.05/0.05/0.05 0.05/0.05/0.05

(220/230/240) Heating A 0.05/0.05/0.05 0.05/0.05/0.05

Sound pressure level (measured in anechoice room) dB <A> –

Applicable temperature range of installation site °C (D.B.) 0~32

External finish Galvanized steel plate

(Lower part drain pan: Pre-coated galvanized sheets + powder coating)

Connectable outdoor unit –

Indoor unit capacity connectable to 1 branch Model P80 or smaller

(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81)

External dimension H x W x D mm 300 x 1,520 x 630

in. 11-13/16 x 59-7/8 x 24-13/16

Refrigerant piping diameter

To outdoor unit Connectable outdoor unit capacity

– – – – –

High press. Pipe mm (in.)

O.D. – – – – –

Low press. Pipe mm (in.)

O.D. – – – – –

Water piping diameter

To Indoor unit

Inlet Pipe mm I.D. 20

Outlet Pipe mm I.D. 20

Field drain pipe size mm (in.) O.D. 32 (1-1/4)

Net weight kg (lbs) 43 (95) [48 (106) with water]

Standard attachment

Document –

Accessory Drain Connection pipe (with flexible hose and insulation)

Optional parts –

Note 1.Works not included:

Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.

2.The equipment is for water.

3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.

(For use in quiet environments with low background noise, position the Sub HBC CONTROLLER at least 5 m away from any indoor units.) 4.Please install the Sub HBC controller in a place where noise will not be an issue.

5.Please attach an expansion vessel (field supply).

6.Please use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework.

Furthermore, when using copper pipework use a non-oxidative brazing method.

Oxidation of the pipework will reduce the pump life.

7.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat.

8.Please install an air purge valve where air will gather in the water circuit.

9.Please refer to the databook or the installation manual for the specified water quality.

10.This unit is not designed for outside installations.

11.Please always make water circulate or pull out the circulation water completely when not using it.

*Please do not use it as a drinking water.

12.Please do not use ground water and well water.

13.When installing the Sub HBC unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.

(Refer to the databook and the installation manual).

14.Can't use singleness. (MAIN HBC CONTROLLER is necessary) 0000003552.BOOK 64 ページ 2015年9月15日 火曜日 午後12時11分

1. SPECIFICATIONS

HB C

Model name CMB-WP1016V-GB1

Number of branch 16

Power source 1-phase 220-230-240 V

50 Hz 60 Hz

Power input Cooling kW 0.01/0.01/0.01 0.01/0.01/0.01

(220/230/240) Heating kW 0.01/0.01/0.01 0.01/0.01/0.01

Current input Cooling A 0.05/0.05/0.05 0.05/0.05/0.05

(220/230/240) Heating A 0.05/0.05/0.05 0.05/0.05/0.05

Sound pressure level (measured in anechoice room) dB <A> –

Applicable temperature range of installation site °C (D.B.) 0~32

External finish Galvanized steel plate

(Lower part drain pan: Pre-coated galvanized sheets + powder coating)

Connectable outdoor unit –

Indoor unit capacity connectable to 1 branch Model P80 or smaller

(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81)

External dimension H x W x D mm 300 x 1,520 x 630

in. 11-13/16 x 59-7/8 x 24-13/16

Refrigerant piping diameter

To outdoor unit Connectable outdoor unit capacity

– – – – –

High press. Pipe mm (in.)

O.D. – – – – –

Low press. Pipe mm (in.)

O.D. – – – – –

Water piping diameter

To Indoor unit

Inlet Pipe mm I.D. 20

Outlet Pipe mm I.D. 20

Field drain pipe size mm (in.) O.D. 32 (1-1/4)

Net weight kg (lbs) 51 (113) [60 (133) with water]

Standard attachment

Document –

Accessory Drain Connection pipe (with flexible hose and insulation)

Optional parts –

Note 1.Works not included:

Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.

2.The equipment is for water.

3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.

(For use in quiet environments with low background noise, position the Sub HBC CONTROLLER at least 5 m away from any indoor units.) 4.Please install the Sub HBC controller in a place where noise will not be an issue.

5.Please attach an expansion vessel (field supply).

6.Please use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework.

Furthermore, when using copper pipework use a non-oxidative brazing method.

Oxidation of the pipework will reduce the pump life.

7.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat.

8.Please install an air purge valve where air will gather in the water circuit.

9.Please refer to the databook or the installation manual for the specified water quality.

10.This unit is not designed for outside installations.

11.Please always make water circulate or pull out the circulation water completely when not using it.

*Please do not use it as a drinking water.

12.Please do not use ground water and well water.

13.When installing the Sub HBC unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.

(Refer to the databook and the installation manual).

14.Can't use singleness. (MAIN HBC CONTROLLER is necessary) 0000003552.BOOK 65 ページ 2015年9月15日 火曜日 午後12時11分

HB C

2. EXTERNAL DIMENSIONS

2. EXTERNAL DIMENSIONS

Cutting point Drain hose I.D.32(1-1/4") (Accessory)

Band(Accessory) Drain piping VP-25 Connection

Connection pipe to SUB HBC Connection pipe from SUB HBC Connection pipe from SUB HBC Connection pipe to SUB HBC

Connection pipe from indoor unit Connection pipe to indoor unit

Connection pipe from MAIN HBC ø15.88<Brazed> Water pipe(Inlet) Water pipe(EXP.Tank)

X

Y Z

(Lifting bolt pitch) Control box

(Lifting bolt pitch)

12345678

ø19.05(use attachment pipe) [Field supply] ø19.05(use attachment pipe) [Field supply]

(High pressure) Connection pipe of outdoor unit ø19.05<Brazed>

(Low pressure) Connection pipe of outdoor unit ø22.2<Brazed> [Field supply]ø25.4(use attachment pipe) [Field supply]ø25.4(use attachment pipe) [Field supply]ø25.4(use attachment pipe) [Field supply]ø25.4(use attachment pipe) [Field supply]ø19.05(use attachment pipe)[Field supply]ø19.05(use attachment pipe)

Detail of X section

Detail of Z section

Detail of Y section Service space Service space

Access door 450

Access door 450

<Accessories> ·Drain hose I.D.32(1-1/4")···1pc. ·Hose band···1pc. ·Tie band···1pc. ·Wrench···1pc. Note1.Suspension bolt(ø10),washer(M10),and nut(M10) prepare in the field. 2.Take notice of service space as follows. (Please give attention not to occupy service space by letting ducts and pipes through.) 412 7070X7=490 447

70 70X7=490

74 148 153 180 84

154 73

103 151

181

43 61 63 63

540 90

157 216 224 272 286 1321 1391 1520

1379

543

3

300

200

44 276

31

ø31

12

30

14

100 120

200 (700)

250

160300160 Service space

Service space