1. SPECIFICATIONS
I.HBC controller 1. SPECIFICATIONS
Model name CMB-WP108V-GA1
Number of branch 8
Power source 1-phase 220-230-240 V
50 Hz 60 Hz
Power input Cooling kW 0.45/0.46/0.47 0.45/0.46/0.47
(220/230/240) Heating kW 0.45/0.46/0.47 0.45/0.46/0.47
Current input Cooling A 2.89/2.83/2.79 2.89/2.83/2.79
(220/230/240) Heating A 2.89/2.83/2.79 2.89/2.83/2.79
Sound pressure level (measured in anechoice room) dB <A> 41
Applicable temperature range of installation site °C (D.B.) 0~32
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor unit PURY-P200~500YLM-A1(-BS)/PURY-EP200~500YLM-A1(-BS) *a
Indoor unit capacity connectable to 1 branch Model P80 or smaller
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81)
External dimension H x W x D mm 300 x 1,520 x 630
in. 11-13/16 x 59-7/8 x 24-13/16
Refrigerant piping diameter
To outdoor unit Connectable outdoor unit capacity
To P200 To P250/300 To P350 To P400 for each To P450/500 for each
High press. Pipe mm (in.)
O.D. 15.88 (5/8)
Brazed 19.05 (3/4)
Brazed 19.05 (3/4)
Brazed 15.88 (5/8)
Brazed 19.05 (3/4)
Brazed
Low press. Pipe mm (in.)
O.D.
19.05 (3/4) Brazed
22.2 (7/8) Brazed
28.58 (1-1/8) Brazed
19.05 (3/4) Brazed
22.2 (7/8) Brazed Water piping
diameter
To Indoor unit
Inlet Pipe mm I.D. 20
Outlet Pipe mm I.D. 20
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 85 (188) [95 (210) with water]
Standard attachment
Document –
Accessory Drain Connection pipe (with flexible hose and insulation)
Optional parts –
Note 1.Works not included:
Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the HBC CONTROLLER at least 5 m away from any indoor units.) 4.Please install the HBC controller in a place where noise will not be an issue.
5.Please attach an expansion vessel (field supply).
6.Please use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework.
Furthermore, when using copper pipework use a non-oxidative brazing method.
Oxidation of the pipework will reduce the pump life.
7.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat.
8.Please install an air purge valve where air will gather in the water circuit.
9.Please install a pressure reducing valve and a strainer on the water supply to the HBC controller.
10.Please refer to the databook or the installation manual for the specified water quality.
11.This unit is not designed for outside installations.
12.Please always make water circulate or pull out the circulation water completely when not using it.
*Please do not use it as a drinking water.
13.Please do not use ground water and well water.
14.When installing the HBC unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.
(Refer to the databook and the installation manual).
*a. Cannot be connected to other than YLM series
0000003552.BOOK 62 ページ 2015年9月15日 火曜日 午後12時11分
1. SPECIFICATIONS
HB C
Model name CMB-WP1016V-GA1
Number of branch 16
Power source 1-phase 220-230-240 V
50 Hz 60 Hz
Power input Cooling kW 0.45/0.46/0.47 0.45/0.46/0.47
(220/230/240) Heating kW 0.45/0.46/0.47 0.45/0.46/0.47
Current input Cooling A 2.89/2.83/2.79 2.89/2.83/2.79
(220/230/240) Heating A 2.89/2.83/2.79 2.89/2.83/2.79
Sound pressure level (measured in anechoice room) dB <A> 41
Applicable temperature range of installation site °C (D.B.) 0~32
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor unit PURY-P200~500YLM-A1(-BS)/PURY-EP200~500YLM-A1(-BS) *a
Indoor unit capacity connectable to 1 branch Model P80 or smaller
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81)
External dimension H x W x D mm 300 x 1,800 x 630
in. 11-13/16 x 70-7/8 x 24-13/16
Refrigerant piping diameter
To outdoor unit Connectable outdoor unit capacity
To P200 To P250/300 To P350 To P400 for each To P450/500 for each
High press. Pipe mm (in.)
O.D. 15.88 (5/8)
Brazed 19.05 (3/4)
Brazed 19.05 (3/4)
Brazed 15.88 (5/8)
Brazed 19.05 (3/4)
Brazed
Low press. Pipe mm (in.)
O.D.
19.05 (3/4) Brazed
22.2 (7/8) Brazed
28.58 (1-1/8) Brazed
19.05 (3/4) Brazed
22.2 (7/8) Brazed Water piping
diameter
To Indoor unit
Inlet Pipe mm I.D. 20
Outlet Pipe mm I.D. 20
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 97 (214) [110 (243) with water]
Standard attachment
Document –
Accessory Drain Connection pipe (with flexible hose and insulation)
Optional parts –
Note 1.Works not included:
Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2.The equipment is for R410A refrigerant.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the HBC CONTROLLER at least 5 m away from any indoor units.) 4.Please install the HBC controller in a place where noise will not be an issue.
5.Please attach an expansion vessel (field supply).
6.Please use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework.
Furthermore, when using copper pipework use a non-oxidative brazing method.
Oxidation of the pipework will reduce the pump life.
7.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat.
8.Please install an air purge valve where air will gather in the water circuit.
9.Please install a pressure reducing valve and a strainer on the water supply to the HBC controller.
10.Please refer to the databook or the installation manual for the specified water quality.
11.This unit is not designed for outside installations.
12.Please always make water circulate or pull out the circulation water completely when not using it.
*Please do not use it as a drinking water.
13.Please do not use ground water and well water.
14.When installing the HBC unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.
(Refer to the databook and the installation manual).
*a. Cannot be connected to other than YLM series
0000003552.BOOK 63 ページ 2015年9月15日 火曜日 午後12時11分
HB C
1. SPECIFICATIONS
Model name CMB-WP108V-GB1
Number of branch 8
Power source 1-phase 220-230-240 V
50 Hz 60 Hz
Power input Cooling kW 0.01/0.01/0.01 0.01/0.01/0.01
(220/230/240) Heating kW 0.01/0.01/0.01 0.01/0.01/0.01
Current input Cooling A 0.05/0.05/0.05 0.05/0.05/0.05
(220/230/240) Heating A 0.05/0.05/0.05 0.05/0.05/0.05
Sound pressure level (measured in anechoice room) dB <A> –
Applicable temperature range of installation site °C (D.B.) 0~32
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor unit –
Indoor unit capacity connectable to 1 branch Model P80 or smaller
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81)
External dimension H x W x D mm 300 x 1,520 x 630
in. 11-13/16 x 59-7/8 x 24-13/16
Refrigerant piping diameter
To outdoor unit Connectable outdoor unit capacity
– – – – –
High press. Pipe mm (in.)
O.D. – – – – –
Low press. Pipe mm (in.)
O.D. – – – – –
Water piping diameter
To Indoor unit
Inlet Pipe mm I.D. 20
Outlet Pipe mm I.D. 20
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 43 (95) [48 (106) with water]
Standard attachment
Document –
Accessory Drain Connection pipe (with flexible hose and insulation)
Optional parts –
Note 1.Works not included:
Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2.The equipment is for water.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the Sub HBC CONTROLLER at least 5 m away from any indoor units.) 4.Please install the Sub HBC controller in a place where noise will not be an issue.
5.Please attach an expansion vessel (field supply).
6.Please use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework.
Furthermore, when using copper pipework use a non-oxidative brazing method.
Oxidation of the pipework will reduce the pump life.
7.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat.
8.Please install an air purge valve where air will gather in the water circuit.
9.Please refer to the databook or the installation manual for the specified water quality.
10.This unit is not designed for outside installations.
11.Please always make water circulate or pull out the circulation water completely when not using it.
*Please do not use it as a drinking water.
12.Please do not use ground water and well water.
13.When installing the Sub HBC unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.
(Refer to the databook and the installation manual).
14.Can't use singleness. (MAIN HBC CONTROLLER is necessary) 0000003552.BOOK 64 ページ 2015年9月15日 火曜日 午後12時11分
1. SPECIFICATIONS
HB C
Model name CMB-WP1016V-GB1
Number of branch 16
Power source 1-phase 220-230-240 V
50 Hz 60 Hz
Power input Cooling kW 0.01/0.01/0.01 0.01/0.01/0.01
(220/230/240) Heating kW 0.01/0.01/0.01 0.01/0.01/0.01
Current input Cooling A 0.05/0.05/0.05 0.05/0.05/0.05
(220/230/240) Heating A 0.05/0.05/0.05 0.05/0.05/0.05
Sound pressure level (measured in anechoice room) dB <A> –
Applicable temperature range of installation site °C (D.B.) 0~32
External finish Galvanized steel plate
(Lower part drain pan: Pre-coated galvanized sheets + powder coating)
Connectable outdoor unit –
Indoor unit capacity connectable to 1 branch Model P80 or smaller
(Use optional joint pipe combing 2 branches when the total unit capacity exceeds P81)
External dimension H x W x D mm 300 x 1,520 x 630
in. 11-13/16 x 59-7/8 x 24-13/16
Refrigerant piping diameter
To outdoor unit Connectable outdoor unit capacity
– – – – –
High press. Pipe mm (in.)
O.D. – – – – –
Low press. Pipe mm (in.)
O.D. – – – – –
Water piping diameter
To Indoor unit
Inlet Pipe mm I.D. 20
Outlet Pipe mm I.D. 20
Field drain pipe size mm (in.) O.D. 32 (1-1/4)
Net weight kg (lbs) 51 (113) [60 (133) with water]
Standard attachment
Document –
Accessory Drain Connection pipe (with flexible hose and insulation)
Optional parts –
Note 1.Works not included:
Installation/foundation work, electrical connection work, duct work, insulation work, power source switch, and other items are not specified in this specifications.
2.The equipment is for water.
3.Install this product in a location where noise (refrigerant noise) emitted by the unit will not disturb the neighbors.
(For use in quiet environments with low background noise, position the Sub HBC CONTROLLER at least 5 m away from any indoor units.) 4.Please install the Sub HBC controller in a place where noise will not be an issue.
5.Please attach an expansion vessel (field supply).
6.Please use copper or plastic pipes for the water circuit. Do not use steel or stainless steel pipework.
Furthermore, when using copper pipework use a non-oxidative brazing method.
Oxidation of the pipework will reduce the pump life.
7.When blazing the pipes, be sure to blaze, after covering a wet cloth to the insulation pipes of the units in order to prevent it from burning and shrinking by heat.
8.Please install an air purge valve where air will gather in the water circuit.
9.Please refer to the databook or the installation manual for the specified water quality.
10.This unit is not designed for outside installations.
11.Please always make water circulate or pull out the circulation water completely when not using it.
*Please do not use it as a drinking water.
12.Please do not use ground water and well water.
13.When installing the Sub HBC unit in an environment which may drop below 0 °C, please add antifreeze to the circulating water.
(Refer to the databook and the installation manual).
14.Can't use singleness. (MAIN HBC CONTROLLER is necessary) 0000003552.BOOK 65 ページ 2015年9月15日 火曜日 午後12時11分
HB C
2. EXTERNAL DIMENSIONS
2. EXTERNAL DIMENSIONS
Cutting point Drain hose I.D.32(1-1/4") (Accessory)
Band(Accessory) Drain piping VP-25 Connection
Connection pipe to SUB HBC Connection pipe from SUB HBC Connection pipe from SUB HBC Connection pipe to SUB HBC
Connection pipe from indoor unit Connection pipe to indoor unit
Connection pipe from MAIN HBC ø15.88<Brazed> Water pipe(Inlet) Water pipe(EXP.Tank)
X
Y Z
(Lifting bolt pitch) Control box
(Lifting bolt pitch)
12345678
ø19.05(use attachment pipe) [Field supply] ø19.05(use attachment pipe) [Field supply]
(High pressure) Connection pipe of outdoor unit ø19.05<Brazed>
(Low pressure) Connection pipe of outdoor unit ø22.2<Brazed> [Field supply]ø25.4(use attachment pipe) [Field supply]ø25.4(use attachment pipe) [Field supply]ø25.4(use attachment pipe) [Field supply]ø25.4(use attachment pipe) [Field supply]ø19.05(use attachment pipe)[Field supply]ø19.05(use attachment pipe)
Detail of X section
Detail of Z section
Detail of Y section Service space Service space
Access door 450
□
Access door 450
□
<Accessories> ·Drain hose I.D.32(1-1/4")···1pc. ·Hose band···1pc. ·Tie band···1pc. ·Wrench···1pc. Note1.Suspension bolt(ø10),washer(M10),and nut(M10) prepare in the field. 2.Take notice of service space as follows. (Please give attention not to occupy service space by letting ducts and pipes through.) 412 7070X7=490 447
70 70X7=490
74 148 153 180 84
154 73
103 151
181
43 61 63 63
540 90
157 216 224 272 286 1321 1391 1520
1379
543
3
300
200
44 276
31
ø31
12
30
14
100 120
200 (700)
250
160300160 Service space
Service space