When the External Temperature Interlock function is active, the set temperature will be adjusted as shown below.

■ "Cool" and "Dry" modes

29 30 31 32 33 34 35 36

27 28 26 25 24 23

Temperature (°C)

Time

Set temperature after being adjusted when [Set Temperature Variation Range] is set to [+4°C] (+8°F)

Set temperature Outdoor temperature

Outdoor temperature conditions Set temperature after being adjusted Outdoor temperature ≥

Set temperature + 1.5°C (2.7°F) Set temperature + 1°C (2°F) Outdoor temperature ≥

Set temperature + 4.5°C (8.1°F) Set temperature + 2°C (4°F) Outdoor temperature ≥

Set temperature + 6.5°C (11.7°F) Set temperature + 3°C (6°F) Outdoor temperature ≥

Set temperature + 7.5°C (13.5°F) Set temperature + 4°C (8°F)

■ "Heat" mode

12 13 14 15 16 17 18 19

10 11 9 8 7 6

Temperature (°C)

Time Set temperature after being adjusted when [Set Temperature Variation Range] is set to [+4°C] (+8°F)

Set temperature

Outdoor temperature

Outdoor temperature conditions Set temperature after being adjusted Outdoor temperature ≤

Set temperature - 4.0°C (7.2°F) Set temperature - 1°C (2°F) Outdoor temperature ≤

Set temperature - 6.0°C (10.8°F) Set temperature - 2°C (4°F)

7-2. Night Setback Control

The Night Setback Control function (hereafter abbreviated as Setback Control) prevents indoor condensation by performing heating operation automatically when the room temperature goes outside of the specific range during the night. Click [Functions 3] in the menu bar, and then click [Night Setback Control] to access the Night Setback Control settings screen.

Heating operation starts when a given group is stopped and the room temperature drops below the specified minimum temperature.

Note: The Setback Control function also prevents excessive temperature rise by performing cooling operation automatically when the room temperature goes outside of the specific range. Cooling operation starts when a given group is stopped and the room temperature rises above the specified maximum temperature.

Note: If the room temperature is measured by the return air temperature sensor on the air conditioning unit, the measured value may not be an accurate representation of the temperature in the room, especially when the air conditioning unit is stopped and the room air is stagnant. When this is the case, use an external temperature sensor (PAC-SE40TSA) or remote controller sensor to measure the room temperature.

Note: The Night Setback Control may not be accessible if logged in as a building manager.

Save Settings

Click to send the settings to EB-50.

Refresh Click to import the settings

from EB-50.

Temperature range

Setback Control Usability Setback Control Period

Group No. and group

name Copy

Paste

(1) Select [Use] and set the time period in which Setback Control is performed.

Note: When [00:00 - 00:00] is selected, Setback Control is active for 24 hours.

(2) In the [Temperature range] section, set the maximum and minimum temperatures for each group.

For example, if [Setback Control Period] is set to [01:00 - 05:00] and [Temperature range] is set to [12°C - --°C] ([53.6°F - --°F]), heating operation starts automatically when the room temperature drops below the set temperature 12°C (53°F) between 1:00 and 5:00. When the Setback Control ends at 5:00, the set temperature returns to the original setting, and the operation stops.

Note: The air conditioning units in the heating operation will stop and the set temperature will return to the original setting when the Setback Control period is over or the room temperature rises to the minimum temperature plus 3°C (5.4°F). Likewise, the air conditioning units in the cooling operation will stop and the set temperature will return to the original setting when the Setback Control period is over or the room temperature drops to the maximum temperature minus 3°C (5.4°F).

Heat ON

21°C (69°F) Heat ON

12°C (53°F) Heat OFF

21°C (69°F) Heat OFF

Setback Control period Room temp.

21°C (69°F) Min. temp.

12°C (53°F)

When the temperature drops below the minimum temperature (heating operation) Setback

operation starts.

Setback operation ends.

3°C (5.4°F)

Cool ON

24°C (75°F) Cool ON

28°C (83°F) Cool OFF

24°C (75°F) Cool OFF

Setback Control period Max. temp.

28°C (83°F) Room temp.

24°C (75°F)

When the temperature rises above the maximum temperature (cooling operation) Setback

operation starts.

Setback operation ends.

3°C (5.4°F)

(3) To copy the settings of a group to the settings for other groups, click [Copy] in the row of the group whose settings are to be copied, then click [Paste] in the row of the group to which the copied settings are to be pasted. The rectangular icons next to the selected buttons will appear in yellow-green.

(4) Click [Save Settings] to send the settings to the EB-50.

7-3. Interlock control

Click [Functions 3] in the menu bar, and then click [Interlock control] to access the Interlock Control settings screen. Set the interlocking conditions and actions, and then click [Save Settings] to send the settings to the EB-50.

Note: A separate license is required to use the Interlock Control function. Make sure that the required license has properly been registered on the Registration of Optional Functions screen. (Refer to chapter 10 for details.) Note: The Interlock Control settings may not be accessible if logged in as a building manager.

Note: Interlock Control is not effective when [External Input Setting] is set to [ON/OFF (Level signal)]. (See section 4-2- 3).

Note: If a group is deleted on the group settings screen, be sure to delete the Interlock Control settings in which the group is selected as the input units or the output units.

Delete all steps

Click to delete all Interlock Control settings.

Save Settings Click to send the settings to

EB-50.

Execute/Stop Execution Click to enable/disable the

Interlock Control.

Refresh Click to import the settings

from EB-50.

Enable/Disable Click to enable/disable each

Interlock Control setting.

Input state 1

Scroll bar

Slide to show different Interlock Control settings between No.1 and No.150.

Select Input Units Click to display the screen to

select input units.

Input state 2

Edit buttons Status bar

Shows the settings status of 150 settings (Green:

Settings have been made;

Red: Incomplete settings exist.)

Select Output Units Click to display the screen to select output units.

Input Category

Output Unit Type

Action

Click to set the interlocking actions.

Up to 150 Interlock Control settings from No.1 through No.150 can be set. The Interlock Control verifies the state changes in an ascending order of No.1 to No.150 every three to five seconds. When the interlocking conditions are met, the interlocking action commands will be issued to the output units.

By making the interlocking condition settings (input category, input states, and input units) and interlocking action settings (output unit type, actions, and output units) for each Interlock Control setting, the operation of the output units can be interlocked with the operation of the input units.

Caution:

Before using the Interlock Control function, you must agree to the following.

1. This function must not be used for disaster prevention or security purposes unless a backup device is provided in case of failure of this function. (This function should never be used in the way that would put people's lives at risk.)

2. The interlocking action settings that are not supported by the interlocked output units must not be made

Shown below are four examples of Interlocked operations.

Example 1: Interlocked operation of indoor unit and card key via a DIDO controller

UP

EB-50

Indoor unit

Card key 1 The card key status is input

through the contact.

DIDO controller (PAC-YG66DCA) 2 Signal indicating the card

key has been removed

3 Signal to stop the indoor unit

Example 2: Interlocked operation of operation mode between indoor units

UP

EB-50

Indoor unit #1 (conference room No.1)

Remote controller

Indoor unit #2 (conference room No.2) 3 Signal to change the

operation mode for the indoor unit #2 to fan mode

2 Signal indicating the operation mode for the

indoor unit #1 has changed to fan mode 1 The operation mode has changed from heating to fan mode.

Example 3: Interlocked operation of indoor unit and window through the free contact on an indoor unit

UP

EB-50

Indoor unit Window

2 Signal indicating the window has been opened

3 Signal to stop the indoor unit

1 The open/close status of the window is input to the free contact.

Example 4: Interlocked operation of indoor unit, lighting, and card key through the free contact on an indoor unit

UP

EB-50

Card key 2 Signal indicating the card

key has been removed

1 The card key status is input to the free contact.

7-3-1. Making the interlocking condition settings

(1) Setting an Input Category and Input States

Select an Input Category and Input States 1 and 2, referring to the table below.

Table 7-1 Interlocking condition settings Input Category Input

unit icon Input State 1 Input State 2

Group (On/Off)

All Groups On All Groups Off

One or more Groups On One or more Groups Off

Group (Mode)

All groups in the mode All groups out of the mode One or more groups in the mode One or more groups out of the mode

Air conditioning unit group: *1 *2 *3 Cool, Dry, Fan, Heat, Auto, Setback LOSSNAY unit group:

Bypass, Heat Recovery, Auto Group

(Error/Normal)

All units in error

All units in normal operation One or more units in error

One or more units in normal operation

Free Input Points (On/Off)

All Units On All Units Off

One or more Units On One or more Units Off

*1 The operation modes for Air To Water (PWFY) unit groups are not available for selection.

*2 If the selected operation mode is not available on the input unit, interlocking conditions will not be fulfilled.

*3 The Setback mode can be selected on the EB-50GU-A, but not on the EB-50GU-J.

Note: If the Input Category is set to [Group (On/Off)] and the Input State 1 is set to [All Groups On], the interlocking action commands will be issued to the output units when the state on the input units changes to [All Groups On]

from another state [All Groups Off], [One or more Groups On], or [One or more Groups Off].

Note: Free contact is available for use on R410A- and R407C-compatible indoor units with software Ver. 33 or later. The software version can be confirmed with the Maintenance Tool.

Note: When [External Input Setting] is set to [Emergency Stop (Level signal)] (see section 4-2-3) or when the indoor unit is stopped due to the Peak Cut control (see section 5-2), only the Interlock Control of free contact and DIDO controller (PAC-YG66DCA) will be performed, but other Interlock Control will not be.

(2) Selecting the input units

Click [Select Input Units] to display one of the following screens, depending on the selected Input Category.

(A) When [Group (On/Off)], [Group (Mode)], or [Group (Error/Normal)] is selected as the Input Category The [Select Input Groups] screen will appear.

Select the group numbers of the input unit groups. The selected group numbers will appear with a yellow-green background.

Click again to deselect. The deselected group numbers will appear with a light-gray background.

To deselect all selected groups, click [Reset selections].

To select a block of groups, click [Select a Block]. Select a block name and press [OK]. The groups that are registered to the block will appear with a yellow-green background.

Note: If the Input Category is set to [Group (On/Off)] or [Group (Error/Normal)], air conditioning unit groups, LOSSNAY unit groups, Air To Water (PWFY) unit groups, and general equipment (connected via DIDO controller PAC-YG66DCA) groups can be selected.

If the input category is set to [Group (Mode)], air conditioning unit groups and LOSSNAY unit groups can be selected.

Note: Different types of groups (air conditioning unit groups, LOSSNAY unit groups, or general equipment (connected via DIDO controller PAC-YG66DCA) groups) cannot be simultaneously selected.

(B) When [Free Input Points (On/Off)] is selected as the Input Category The [Select Addresses of Input Units] screen will appear.

Select the addresses of the indoor units to which the general equipment is connected, and select contact points for each indoor unit.

The selected unit address will appear with a red frame.

The unit addresses whose contact points have been set will appear with a yellow-green background.

7-3-2. Making the interlocking action settings

(1) Setting an Output Unit Type and Actions

Select an Output Unit Type and set the Actions, referring to the table below.

Table 7-2 Interlocking action settings Output Unit

Type Output

unit icon

Actions

Setting item Setting options

Group

ON/OFF ON, OFF

Mode *1 *2

Air conditioning unit group: *3 Cool, Dry, Fan, Heat, Auto, Setback

LOSSNAY unit group:

Bypass, Heat Recovery, Auto Set Temp. *1 *4 Desired temperature

Air direction *1 Mid3, Mid2, Mid1, Mid0, Horizontal, Swing, Auto Fan speed *1 Low, Mid2, Mid1, High, Auto

Prohibit Remote Controller

Operation (ON/OFF) Permit, Prohibit Prohibit Remote Controller

Operation (Mode) Permit, Prohibit Prohibit Remote Controller

Operation (Set Temp.) Permit, Prohibit Free Output

Points ON/OFF ON, OFF

*1 The available setting options vary, depending on the connected indoor unit model.

Make the interlocking action settings that are available for the output units.

*2 The operation modes for Air To Water (PWFY) unit are not available for selection.

*3 The Setback mode can be selected on the EB-50GU-A, but not on the EB-50GU-J.

*4 The set temperature for Air To Water (PWFY) unit cannot be set.

The screen display under Action will vary, depending on the selected Output Unit Type.

(A) When [Group] is selected as the Output Unit Type Click [Edit] under Action. The [Set up Actions]

screen will appear.

Set the interlocking actions to be taken when the interlocking conditions are met.

Note: The current operation status will be maintained for the setting items that were not changed.

Note: The set temperature cannot be set unless the operation mode has been set.

Note: If the selected operation mode is not available on the interlocked output units, the Interlock Control will not be performed.

Note: To prevent malfunctions of the air conditioning units, be sure to set the set temperature to a temperature within the normal operating temperature range, although there may be rare cases in which it is possible to set the set temperature to a temperature outside the normal operating temperature range (depending on the model of the air conditioning units that are connected to a system).

Note: Signals for Swing and Auto of Air direction setting and Auto of Fan speed setting will not be output unless these functions are available on the interlocked output units.

With respect to the air direction and fan speed, if the number of settable air directions and fan speeds vary among the connected unit models, the signals that are rounded up to the settable range may be output.

Note: When the interlocking conditions are met, it will take some time to issue the interlocking action

commands to the output units. This may delay the state change verification, which is usually performed every three to five seconds.

(B) When [Free Output Points] is selected as the Output Unit Type Select [ON] or [OFF] under Action to turn on or

off the output units.

(2) Selecting the output units

Click [Select Output Units] to display one of the following screens, depending on the selected Output Unit Type.

(A) When [Group] is selected as the Output Unit Type The [Select Output Groups] screen will appear.

Select the group numbers of the output unit groups. The selected group numbers will appear with a yellow-green background.

Click again to deselect. The deselected group numbers will appear with a light-gray background.

To deselect all selected groups, click [Reset selections].

To select a block of groups, click [Select a Block]. Select a block name and press [OK]. The groups that are registered to the block will appear with a yellow-green background.

Note: If the Output Unit Type is set to [Group], air conditioning unit groups, LOSSNAY unit groups, Air To Water (PWFY) unit groups, and general equipment (connected via DIDO controller PAC-YG66DCA) groups are available for selection.

Note: Different types of groups (air conditioning unit groups, LOSSNAY unit groups, Air To Water (PWFY) unit groups, or general equipment (connected via DIDO controller PAC-YG66DCA) groups) cannot be simultaneously selected.

(B) When [Free Output Points] is selected as the Output Unit Type The [Select Addresses of Output Units] screen will

appear.

Select the addresses of the indoor units to which the general equipment is connected, and select contact points for each indoor unit.

The selected unit address will appear with a red frame.

The unit addresses whose contact points have been set will appear with a yellow-green background.

7-3-3. Disabling/Enabling Interlock Control settings

Use the Enable/Disable button to enable or disable each Interlock Control setting.

No actions will be taken for the Interlock Control setting that is set to [Disable].

7-3-4. Temporarily disabling the Interlock Control

Click the [Stop Execution] button to temporarily disable the Interlock Control. Click [Execute] to resume the Interlock Control.

Note: State change that occurs while [Stop Execution] is selected will be ignored.

7-3-5. Editing Interlock Control settings

Use the Edit buttons to edit each row of Interlock Control setting.

Button name Function

Delete all steps Deletes all Interlock Control settings.

Insert a step Inserts a blank row of Interlock Control setting above the row that is displayed, and moves all rows down by one.

If interlocking conditions are entered in the last row, no more rows can be inserted.

Delete a step Deletes the row of Interlock Control setting that is displayed, and moves up the rows below by one.

Clear the display Clears the row of Interlock Control setting that is displayed.

Copy To copy the settings of a row to the settings for other rows, display the row whose settings are to be copied and click [Copy], then display the row to which the copied settings are to be pasted and click [Paste].

Paste

7-4. AHC Port Name Settings

On the AHC Port Name Settings screen, enter the names of the input and output ports of the Advanced HVAC CONTROLLER (AHC).

The names that are entered on this screen will appear on the AHC List screen, accessible via the Web Browser for System Maintenance Engineer.

Click [Functions 3] in the menu bar, and then click [AHC Port Name Settings] to access the AHC Port Name Settings screen.

Note: The AHC port name settings may not be accessible if logged in as a building manager.

Important: The AHC port name settings must be made after all units have been started up.

The settings that have been saved while one or more units are starting up may be lost.

Save Settings

Click to send the settings to EB-50.

Refresh Click to import the settings

from EB-50.

Unit address

Digital Output (1–9)

Analog Input (1–8)

Extended Output (1–4)

Analog Output (1–2)

Extended Input (1–4)

Output Port Name

Digital Input (1–15) Input Port Name

(1) In the [Input Port Name] field, enter the input port name in 20 characters or less.

Note: Digital Input (DI) 1–15, Extended Input (EI) 1–4, and Analog Input (AI) 1–8 will appear regardless of whether the ports are used or not.

Note: The following characters cannot be used in the [Input Port Name] field: <, >, +, &, ", or ' (2) In the [Output Port Name] field, enter the output port name in 20 characters or less.

Note: Digital Output (DO) 1–9, Extended Output (EO) 1–4, and Analog Output (AO) 1–2 will appear regardless of whether the ports are used or not.

Note: The following characters cannot be used in the [Output Port Name] field: <, >, +, &, ", or ' (3) Click [Save Settings] to send the settings to the EB-50.