• No results found

Flow chart of the detailed outdoor unit failure mode recall function

In document OUTDOOR UNIT (сторінка 32-38)

12-2. FAILURE MODE RECALL FUNCTION

2. Flow chart of the detailed outdoor unit failure mode recall function

Does the left OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds?

Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as the blinking of the left lamp on the indoor unit. 2

Yes (Blinks)

No (OFF) The outdoor unit might be abnormal.

Check if outdoor unit is abnormal according to the following procedures.

Operational procedure

Make sure that the remote controller is set to the failure mode recall function.

With the remote controller headed towards the indoor unit, press TEMP button to adjust the set temperature to 25°C. 1

1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.

The outdoor unit is abnormal.

Check the blinking pattern, and identify the abnormal point by referring to the table of outdoor unit failure mode recall function (12-2.3.).

Make sure to check at least 2 consecutive blinking cycles. 2

Releasing the failure mode recall function

Release the failure mode recall function by the following procedures.

Turn OFF the power supply and turn it ON again.

Press RESET button of the remote controller.

Repair the failure parts.

The outdoor unit is normal.

Release the failure mode recall function accord- ing to the left mentioned procedure.

Deleting the memorized abnormal condition

After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall func- tion" (12-2.1.).

Press OFF/ON (stop/operate) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor unit.

Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted. 3 Release the failure mode recall function according to "Releasing the failure mode recall function" men-

tioned above.

NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.

2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

3 The information regarding whether the connected outdoor unit is a low-standby-

power model or a non-low-standby-power model will also be initialized.

(Default= compatible with a low-standby- power model)

NOTE: It takes up to 1 minute to indicate the outdoor unit abnor- mality.

Even if the left lamp on the indoor unit is not lighting, keep checking at least 1 minute or longer.

33 3. Table of outdoor unit failure mode recall function

NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (12-3.).

Left OPERTAION INDICATOR lamp (Indoor unit)

Abnormal point (Failure mode/protection)

LED indication

(Outdoor P.C. board) Condition Remedy

Indoor/outdoor unit failure mode recall

function

Outdoor unit failure mode recall function

OFF None (Normal)

1-time blink 2.5 seconds OFF

Indoor/outdoor communication, receiving error

Any signals from the inverter P.C.

board cannot be received normally for 3 minutes.

•Refer to 12-5. How to check miswiring and serial signal error.

○ ○

Indoor/outdoor communication, receiving error

Although the inverter P.C. board sends signal "0", signal "1" has been received 30 consecutive times.

•Refer to 12-5. How to check miswiring and serial signal error.

2-time blink 2.5 seconds OFF

Outdoor power system

Overcurrent protection cut-out operates 3 consecutive times within 1 minute after the compressor gets started.

• Reconnect connectors.

• Refer to 12-5. "How to check inverter/

compressor".

• Check stop valve.

○ ○

3-time blink 2.5 seconds OFF

Discharge temperature thermistor

1-time blink every 2.5 seconds

Thermistor shorts or opens during

compressor running. • Refer to 12-5.

"Check of outdoor thermistors".

Defective outdoor thermistors can be identified by checking the blinking pattern of

LED.

○ ○

Defrost thermistor

Fin temperature thermistor 3-time blink 2.5 seconds OFF P.C. board temperature

thermistor

4-time blink 2.5 seconds OFF Ambient temperature

thermistor

2-time blink 2.5 seconds OFF Outdoor heat exchanger

temperature thermistor

4-time blink 2.5 seconds OFF

Overcurrent 11-time blink

2.5 seconds OFF

Large current flows into power module (IC700).

• Reconnect

compressor connector.

• Refer to 12-5. "How to check inverter/

compressor".

• Check stop valve.

Compressor synchronous abnormality (Compressor start-up failure protection)

12-time blink 2.5 seconds OFF

Waveform of compressor current is distorted.

• Reconnect

compressor connector.

• Refer to 12-5. "How to check inverter/

compressor".

5-time blink 2.5 seconds OFF

Discharge temperature

Temperature of discharge temperature thermistor exceeds 116°C, compressor stops.

Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.

• Check refrigerant circuit and refrigerant amount.

• Refer to 12-5. "Check of LEV".

6-time blink 2.5 seconds OFF

High pressure

Temperature of indoor coil thermistor exceeds 70°C in HEAT mode.

Temperature of defrost thermistor exceeds 70°C in COOL mode.

• Check refrigerant circuit and refrigerant amount.

• Check stop valve.

7-time blink 2.5 seconds OFF

Fin temperature/P.C. board temperature

7-time blink 2.5 seconds OFF

Temperature of fin temperature thermistor on the inverter P.C. board exceeds 75

~ 86°C, or temperature of P.C. board temperature thermistor on the inverter P.C.

board exceeds 72 ~ 85°C.

• Check around outdoor unit.

• Check outdoor unit air passage.

• Refer to 12-5. "Check of outdoor fan motor".

8-time blink 2.5 seconds OFF

Outdoor fan motor

Outdoor fan has stopped 3 times in a row within 30 seconds after outdoor fan startup.

• Refer to 12-5. "Check of outdoor fan motor".

Refer to 12-5. "Check of inverter P.C. board".

9-time blink 2.5 seconds OFF

Nonvolatile memory data 5-time blink 2.5 seconds OFF

Nonvolatile memory data cannot be read properly.

• Replace the inverter

P.C. board.

○ ○

Power module (IC700) 6-time blink 2.5 seconds OFF

The interface short circuit occurs in the output of the power module (IC700).

The compressor winding shorts circuit.

• Refer to 12-5. "How to check inverter/

compressor".

NOTE: Blinking patterns of this mode differ from the ones of TROUBLESHOOTING CHECK TABLE (12-3.).

Left OPETATION INDICATOR lamp (Indoor unit)

Abnormal point (Failure mode/protection)

LED indication

(Outdoor P.C. board) Condition Remedy

Indoor/outdoor unit failure mode recall

function

Outdoor unit failure mode recall function 10-time blink

2.5 seconds OFF

Discharge temperature

Temperature of discharge temperature thermistor has been 50°C or less for 20 minutes.

• Refer to 12-5. "Check of LEV".

• Check refrigerant circuit and refrigerant amount.

11-time blink 2.5 seconds OFF

Bus-bar voltage (DC) 8-time blink 2.5 seconds OFF

Bus-bar voltage of inverter cannot be detected normally.

• Refer to 12-5. "How to check inverter/

compressor".

Each phase current of compressor

9-time blink 2.5 seconds OFF

Each phase current of compressor cannot be detected normally.

14-time blink 2.5 seconds OFF

Stop valve (Closed valve) 14-time blink 2.5 seconds OFF

Closed valve is detected by compressor current.

• Check stop valve.

○ ○

4-way valve/

Pipe temperature

16-time blink 2.5 seconds OFF

The 4-way valve does not work properly.

The indoor coil thermistor detects an abnormal temperature.

• Check the 4-way valve.

• Replace the inverter P.C. board.

16-time blink 2.5 seconds OFF

Outdoor refrigerant system abnormality

1-time blink 2.5 seconds OFF

A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.

• Check for a gas leak in a connecting piping etc.

• Check the stop valve.

• Refer to 12-5.

“Check of outdoor refrigerant circuit”.

○ ○

35

12-3. TROUBLESHOOTING CHECK TABLE

No. Symptom LED indication Abnormal point/ Con-

dition Condition Remedy

1

Outdoor unit does not op- erate.

1-time blink every 2.5 seconds

Outdoor power sys- tem

Overcurrent protection cut-out operates 3 consecutive times

within 1 minute after the compressor gets started. • Reconnect connector of compres- sor.

• Refer to 12-5. "How to check inverter/compressor".

• Check stop valve.

2

Outdoor thermistors Discharge temperature thermistor, fin temperature thermistor, defrost thermistor, P.C. board temperature thermistor, outdoor heat exchanger temperature thermistor or ambient tempera- ture thermistor shorts or opens during compressor running.

• Refer to 12-5. "Check of outdoor thermistors".

3

Outdoor control sys- tem

Nonvolatile memory data cannot be read properly.

(The left OPERATION INDICATOR lamp on the indoor unit lights up or blinks 7-time.)

• Replace inverter P.C. board.

4 6-time blink

2.5 seconds OFF

Serial signal The communication fails between the indoor and outdoor unit

for 3 minutes. • Refer to 12-5. "How to check

miswiring and serial signal error.

5 11-time blink

2.5 seconds OFF

Stop valve/

Closed valve

Closed valve is detected by compressor current. • Check stop valve.

6

14-time blink 2.5 seconds OFF

Outdoor unit (Other abnormality)

Outdoor unit is defective. • Refer to 12-2.2. "Flow chart of the detailed outdoor unit failure mode recall function".

7

16-time blink

2.5 seconds OFF 4-way valve/

Pipe temperature The 4-way valve does not work properly.

The indoor coil thermistor detects an abnormal temperature. • Refer to 12-5. "Check of R.V.

coil".

• Replace the inverter P.C. board.

8

17-time blink 2.5 seconds OFF

Outdoor refrigerant system abnormality

A closed valve and air trapped in the refrigerant circuit are detected based on the temperature sensed by the indoor and outdoor thermistors and the current of the compressor.

• Check for a gas leak in a connecting piping etc.

• Check the stop valve.

• Refer to 12-5. “Check of outdoor refrigerant circuit”.

9

'Outdoor unit stops and restarts 3 minutes later' is repeated.

2-time blink 2.5 seconds OFF

Overcurrent protec-

tion Large current flows into power module (IC700). • Reconnect connector of compressor.

• Refer to 12-5. "How to check inverter/compressor".

• Check stop valve.

10

3-time blink 2.5 seconds OFF

Discharge tem- perature overheat protection

Temperature of discharge temperature thermistor exceeds 116°C, compressor stops. Compressor can restart if discharge temperature thermistor reads 100°C or less 3 minutes later.

• Check refrigerant circuit and refrig- erant amount.

• Refer to 12-5. "Check of LEV".

11

4-time blink 2.5 seconds OFF

Fin temperature / P.C. board tem- perature thermistor overheat protection

Temperature of fin temperature thermistor on the heat sink exceeds 75 ~ 86°C or temperature of P.C. board temperature thermistor on the inverter P.C. board exceeds 72 ~ 85°C.

• Check around outdoor unit.

• Check outdoor unit air passage.

• Refer to 12-5. "Check of outdoor fan motor".

12

5-time blink 2.5 seconds OFF

High pressure pro- tection

Indoor coil thermistor exceeds 70°C in HEAT mode. Defrost

thermistor exceeds 70°C in COOL mode. • Check refrigerant circuit and refrig- erant amount.

• Check stop valve.

13

8-time blink 2.5 seconds OFF

Compressor syn- chronous abnormal- ity

The waveform of compressor current is distorted. • Reconnect connector of compressor.

• Refer to 12-5. "How to check inverter/compressor".

14

10-time blink 2.5 seconds OFF

Outdoor fan motor Outdoor fan has stopped 3 times in a row within 30 seconds

after outdoor fan start-up. • Refer to 12-5. "Check of outdoor fan motor.

• Refer to 12-5. "Check of inverter P.C. board.

15 12-time blink

2.5 seconds OFF

Each phase current

of compressor Each phase current of compressor cannot be detected nor-

mally. • Refer to 12-5. "How to check

inverter/compressor".

16

13-time blink 2.5 seconds OFF

Bus-bar voltage (DC)

Bus-bar voltage of inverter cannot be detected normally. • It occurs with following case.

Instantaneous power voltage drop.

(Short time power failure)

• Refer to 12-5. "Check of power supply".

• Refer to 12-5. "How to check in- verter/compressor".

17 Outdoor unit operates.

1-time blink 2.5 seconds OFF

Frequency drop by current protection

When the input current exceeds approximately 10A, compres- sor frequency lowers.

The unit is normal, but check the following.

Check if indoor filters are clogged.

• Check if refrigerant is short.

• Check if indoor/outdoor unit air circulation is short cycled.

18

3-time blink 2.5 seconds OFF

Frequency drop by high pressure pro- tection

Temperature of indoor coil thermistor exceeds 55°C in HEAT mode, compressor frequency lowers.

19

Frequency drop by defrosting in COOL mode

Indoor coil thermistor reads 8°C or less in COOL mode, com- pressor frequency lowers.

4-time blink 2.5 seconds OFF

Frequency drop by discharge tempera- ture protection

Temperature of discharge temperature thermistor exceeds

111°C, compressor frequency lowers. • Check refrigerant circuit and refrig- erant amount.

• Refer to 12-5. "Check of LEV".

• Refer to 12-5. "Check of outdoor thermistors".

20

5-time blink 2.5 seconds OFF

Outside temperature thermistor protec- tion

When the outside temperature thermistor shorts or opens,

protective operation without that thermistor is performed. • Refer to 12-5. Check of outdoor thermistors.

No. Symptom LED indication Abnormal point/ Con-

dition Condition Remedy

21

Outdoor unit operates.

7-time blink 2.5 seconds OFF

Low discharge tem- perature protection

Temperature of discharge temperature thermistor has been

50°C or less for 20 minutes. • Refer to 12-5. "Check of LEV".

• Check refrigerant circuit and refrig- erant amount.

22

8-time blink 2.5 seconds OFF

PAM protection PAM: Pulse Ampli- tude Modulation

The overcurrent flows into PFC (Power factor correction:

IC820) or the bus-bar voltage reaches 394 V or more, PAM stops and restarts.

This is not malfunction. PAM pro- tection will be activated in the fol- lowing cases:

1 Instantaneous power voltage drop. (Short time power failure) 2 When the power supply voltage

is high.

23

9-time blink 2.5 seconds OFF

Inverter check mode The connector of compressor is disconnected, inverter check

mode starts. • Check if the connector of the com-

pressor is correctly connected.

Refer to 12-5. "How to check inverter/compressor".

NOTE: 1. The location of LED is illustrated at the right figure. Refer to 12-6.1.

2. LED is lighted during normal operation.

The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF.

(Example) When the blinking frequency is “2”.

ON

OFF 2.5-second OFF 2.5-second OFF

0.5-second ON 0.5-second ON LED

Blinking → Inverter P.C. board

37

12-4. TROUBLE CRITERION OF MAIN PARTS

Part name Check method and criterion Figure

Defrost thermistor (RT61) Fin temperature

thermistor (RT64) Ambient temperature thermistor (RT65) Outdoor heat exchanger temperature thermistor (RT68)

Measure the resistance with a tester.

Refer to 12-6. “Test point diagram and voltage”, 1. “Inverter P.C.

board”, for the chart of thermistor.

Discharge temperature thermistor (RT62)

Measure the resistance with a tester. Before measurement, hold the thermistor with your hands to warm it up.

Refer to 12-6. “Test point diagram and voltage”, 1. “Inverter P.C.

board”, for the chart of thermistor.

Compressor

Measure the resistance between terminals using a tester.

(Temperature: -10 ~ 40°C)

Normal (Ω)

MUZ-BT20/25/35VG MUZ-BT50VG U-V

U-W V-W

1.59 ~ 2.16 0.82 ~ 1.11

W

V U

WHT RED BLK

Outdoor fan motor

Measure the resistance between lead wires using a tester.

(Temperature: -10 ~ 40°C)

Color of lead wire Normal (Ω)

MUZ-BT20/25/35VG MUZ-BT50VG RED – BLK

BLK – WHT WHT – RED

32 ~ 43 15 ~ 20

W

V U

WHT RED BLK

R. V. coil (21S4)

Measure the resistance using a tester. (Temperature: -10 ~ 40°C) Normal (kΩ)

1.41 ~ 2.00

Expansion valve coil (LEV)

Measure the resistance using a tester. (Temperature: -10 ~ 40°C) Color of lead wire Normal (Ω)

RED – ORN

37 ~ 54 RED – WHT

RED – BLU

RED – YLW

RED (+12V)

YLW BLU

WHT ORN

LEV

In document OUTDOOR UNIT (сторінка 32-38)