[1] Wiring of main power supply and equipment capacity
Schematic Drawing of Wiring (Example) A: Switch (Breakers for wiring
and current leakage) B: Breakers for current leakage C: Outdoor unit
D: Pull box E: Indoor unit
B C
3N~380–415V L1, L2, L3, N
B A
~220–240V A L, N
PE
PE PE
E
PE PE
E
D
E E
Thickness of wire for main power supply, capacities of the switch and system impedance
Model Minimum wire thickness (mm2)
Breaker for current leakage Local swtich (A) Breaker for wiring (NFB) (A)
Max. Permissive System Impedance
Main cable Branch Ground Capacity Fuse
CAHV-P500YA-HPB 25 - 25 75A 100mA 0.1sec. or less 75 75 75 0.28 Ω
1. Use dedicated power supplies for the unit. Ensure each units are wired individually.
2. Bear in mind ambient conditions (ambient temperature,direct sunlight, rain water,etc.) when proceeding with the wiring and connections.
3. The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter.
Make sure the power-supply voltage does not drop more than 10%.
4. Specific wiring requirements should adhere to the wiring regulations of the region.
5. Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord (design 60245 IEC57).
6. A switch with at least 3 mm contact separation in each pole shall be provided by the Air Conditioner installer.
7. Do not install a phase advancing capacitor on the motor. Doing so may damage the capacitor and result in fire.
The figure in the parentheses indicates the capacity necessary when the "Maximum capacity operation"
setting is selected.
Warning:
• Be sure to use specified wires for connections and ensure no external force is imparted to terminal connections. If connections are not fixed firmly, heating or fire may result.
• Be sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may include some amount of direct current.
Caution:
• Some installation sites may require attachment of an earth leakage breaker for the inverter. If no earth leakage breaker is installed, there is a danger of electric shock.
• Do not use anything other than a breaker and fuse with the correct capacity. Using a fuse or wire of too large capacity may cause malfunction or fire.
Note:
• This device is intended for the connection to a power supply system with a maximum permissible system impedance shown in the above table at the interface point (power service box) of the user’s supply.
• The user must ensure that this device is connected only to a power supply system which fulfils the requirement above.
If necessary, the user can ask the public power supply company for the system impedance at the interface point.
• This equipment complies with IEC 61000-3-12 provided that the short-circuit power SSC is greater than or equal to SSC (*2) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power SSC greater than or equal to SSC (*2).
S
SC(*2)
Model S
SC(MVA)
CAHV-P500YA-HPB 4.11
40
5 - 41 _indd
Types of control cables
Control cable wiring
Remote controller cable
Size 0.3 - 1.25 mm² (Max. 200 m total)
Recommended
cable types CVV
M-NET cable between units *1
Size More than 1.25 mm² (Max. 120 m total)
Recommended
cable types Shielding wire CVVS, CPEVS or MVVS
External input wire size Min. 0.3 mm²
External output wire size 1.25 mm²
*1. Use a CVVS or CPEVS cable (Max. total length of 200 m) if there is a source of electrical interference near by (e.g., factory) or the total length of control wiring exceeds 120 m.
41
5 - 42 _indd
[2] Cable connections
<1> Terminal Block Arrangement
To remove the front panel of the control box, unscrew the four screws and pull the panel forward and then down.
75
L1 L2 L3 N 74 73 72 71 70 66 62 20 19 12 11
262524231615T2T1MBMARBRA
Control terminal block
Power supply terminal block TB2 Cable strap
Power wire Cable from another unit Transmission cable
Cable strap
Power supply terminal block
Important: Power supply cables larger than 60 mm² in diameter are not connectable to the power supply terminal block (TB2). Use a pull box to connect them.
<2> Installing the conduit tube
Punch out the knockout hole for wire routing at the bottom of the front panel with a hammer.
When putting wires through knockout holes without protecting them with a conduit tube, deburr the holes and protect the wires with protective tape.
If damage from animals is a concern, use a conduit tube to narrow the opening.
•
•
•
Burr Knockout hole
Burr Knockout hole
42
5 - 43 _indd
43 2345761
541
1 23 4
7653
2
5
2
1233 L3L2L1
3 4
4
21
31
6
2
4
1
3 2 1
21
2 1 3
7 2
3 1
3
6
1 2
2
5 6
1 2 3
41
1
2
3
4 1
3 4 5 6
12 34
132 12
1 2
2145
1 63
3 N
2 12
64 21
3 2
3
2 1 3
124
7 6
5 4 5
56454332
2
2
1
1
3
21
11 3
11 4
3 1
11 12
4
1
3
1
2
5
2
1
67
2
222322342
2
21
3
1
7
3
2
6 1
123
4 3
2
1
1
2
1 2 654
13 L3
2
1 2 3 4 1
3 2
L2L1
3 1
3 2
N
THHSIGBT temperature Z21Function setting connector
SymbolExplanationSymbol explanation MAIN BOX and SUB BOX Field- suppliedMAIN BOX
CT12 CT22 CT3 F01 F02 F03 F04 F05 F06
Capacitor (Electrolysis)
AC current sensor SV1 21S4LEV2
CH 63LS TH9〜11 TH14TH1〜4
M MSCompressor motor Thermistor
Crankcase heater (for heating the compressor) Low pressure sensor4-way valveSolenoid valve (Injection circuit) High pressure switch63H1
Fuse Electronic expansion valve (Main circuit) 〈ELB1,2〉 〈51P〉 〈52P〉
〈F2〉 〈MP〉
Earth leakage breaker Overcurrent relay (Pump) Electromagnetic contactor (Pump)
Fuse Pump motor
DCLDC reactor 72CElectromagnetic relay (Inverter main circuit)
Electronic expansion valve (Injection)LEV1 SV2Solenoid valve (Hot gas circuit) 〈H20〉Emergency signal (for extra heater) 〈H21〉Drain pan heaterFan motor 63HSHigh pressure sensor
R1Electrical resistanceR5
C100
Note 10. When cabtyre cable is used for the control cable wiring, use a separate cabtyre cable for the following wiring. Using the same cabtyre cable may cause malfunctions and damage to the unit.
(a) Optional remote controller wiring (b) No-voltage contact input wiring (c) No-voltage contact output wiring (d) Remote water temperature setting
(4 - 20 mA)
Note 9. Use a contact that takes 12 VDC 5 mA for no-voltage contact input. Note 11. The SW1 - SW3 switches indicated with can be set on site. Do not change the other SW1 - SW3 switch settings.
Note 5. The broken lines indicate the optional parts, field-supplied parts, and field work.
Note 4. When switching the capacity setting, remove the short-circuit wire on terminal 23 and 25. Note 6. Make sure to connect a pump interlock contact. A short-circuit may cause abnormal stop or malfunctions. Note 7. One of the following methods can be selected individually for how to input operation signal: to input from the optional remote controller or to input from the no-voltage contact. The preset temperature setting can be switched from the no-voltage contact or by setting time ranges.
Note 8. Leave a space of at least 5 cm between the low voltage external wiring (no-voltage contact input and remote controller wiring) and wiring of 100 V or greater. Do not place them in the same conduit tube or cabtyre cable as this will damage the circuit board. Inverter board
R5
C100
R1
SW1SW2SW3
OFFONOFFONOFFON1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
24 23
T3T4
Representative Water temp. 2
°TH15 t CN406yellow Error reset ※4 Error typeError code (PCB ※3)Operation SW
Error code (PCB ※3) Inverter overheat protection faultHeat exchanger freeze up Incompatible combination of unitsRemote controller signal reception error 2Low-pressure sensor faultOutlet water temperature thermistor error (TH13 SUB Circuit)Inlet water temperature thermistor error (TH12 SUB Circuit)Outlet water temperature thermistor error (TH11 MAIN Circuit)
Air-side heat exchanger refrigerant temperature thermistor error (TH8 SUB Circuit) Shell temperature thermistor error (TH7 SUB Circuit)Compressor inlet temperature thermistor error (TH6 SUB Circuit)Discharge temperature thermistor error (TH5 SUB Circuit)
Control terminal block ② Control terminal block ①
Control board
Fan Inverter board Noise filter No-Voltage contact input
Option (COP priority/ Capacity priority)
H21 N
X21
H20 X20 X21
Drain pan heater
Emergency signal (for extra heater)
X20
X08
X09
(ON/OFF)
CN142C
Anti freeze Demand
Capacity mode
Mode change 2 Mode change 1
(ON/OFF)
Pump interlock Fan mode No-voltage contact output
SV2
Pump operation command output
7372717574
CN510 blueCN511
RunRun/Stop yellowCN512
tTH14TH2 CN422 black TO SUB BOX TB3
CN63LSredCN405blue
X01
CN402green
X02
CN404black
X03
CN401
CN502 CN501
CH pump error CN142B
blue
SV1
° 21S4
51P 52P ELB2
M 3〜
(−) MP 70 L2
(+)
CN801 yellow
Capacity (frequency) control input 4〜
20 mA
N
LED2: CPU in operation
Transmission cable for multiple unit control Measurement terminal for maintenance (M-NET)
M (+)
TH3 (−)
Representative
Water temp. 1 T2
72C
T1 CN63HS
LEV1 15 PL
16
1920
CNLVCblue 1112 L1
52P
Outdoor temp. 1 Shell Ref temp. 1
(ON/OFF) TB2
Flow switch
CN142D blue
LED1 LED3: Lit while energized blackCNAC2
M (0)
LEV2 ENTER
Optional remote controller connecting terminal (Non-polarized)
SWP2
Unit address setting SWP3
(0)SWU1 UP
(1) SWP1
SWU2 DOWN
SWU3 BA OFF
Water outlet temp. 1
LOCAL
SWS1SWS2 L3
CN142A black
CN408
CN2
F06AC250V3.15 A T
CN4CN332 blue
10' digit
Water inlet temp. 1
1' digit TB1
X06
(Normal/Error)
CN421black (Normal/Error) 62
X07 (Hot water/ Heating)
66
X04
CNLVA
° CN407red
°°°°°°ttttttt 63H1
red CNAC
F2
REMOTE
63LS 63HS ELB1
X05
To SUB BOX TB4L1
AB
CN102
L2
MAMB
TH9TH4
CN3A
TH1TH10TH11 blue
Error display output
RA
RB Control power circuit
Suction Ref temp. 1 Discharge Ref temp. 1
L3
Operation display output (Heating Eco/ Heating)
Water temp. setting Analog input 4〜
20 mA
(coercion/ by ordinary)
Air hex Ref temp. 1
CNTYP1black
Z21
power supply 3N
〜
50Hz 380/400/415V
DC12V power supply 3N〜 50Hz 380/400/415V
Note 1. Single-dotted lines indicate field wiring. Note 3. The symbols of the field connecting terminals are as follows. : Terminal block : Connection by cutting the short circuit wire : Bullet terminal (field supply: male φ3.96)
Note 2. Faston terminals have a locking function. Press the tab in the middle of the terminals to remove them. Check that the terminals are securely locked in place after insertion. ※6 ※6 ※9 27
5251
48474645 50
44 49
43
41 42
403938373635 −( )−( )−( )−( ) −( )−( ) Model setting errorDiscrete address, system error 262524 High-pressure sensor fault ※9 ※9※9※9※8 Communication error between the MAIN and SUB units Representative water temperature thermistor error (TH14, TH15) ACCT・DCCT sensor fault/Circuit faultVacuum protection faultShell temperature fault8 9Serial communication error 10 11 Open phase (T phase)12 Power supply fault13 Power supply frequency fault14 Active filter fault15 Inverter bus voltage fault16 17 Inverter overload protection fault18 IPM error (inclusive)/overcurrent relay trip19 Cooling fan fault20 21 22 23 Air-side heat exchanger refrigerant temperature thermistor error (TH4 MAIN Circuit)Shell temperature thermistor error (TH3 MAIN Circuit)Compressor inlet temperature thermistor error (TH2 MAIN Circuit)Discharge temperature thermistor error (TH1 MAIN Circuit)
Communication error between the MAIN and SUB units (Simple multiple unit control) Address overlap Remote controller signal reception error 1 Remote controller signal transmission error Incorrect setting of No.-of-connected-unit
Error reset ※4 28 29 30 34333231※9※5
No. SWS1 THHS sensor/Circuit faultOutside temperature thermistor error (TH9)Unreset errors1 Power faliure2 Discharge temperature fault3 Water supply cutoff (Flow switch)4 High pressure fault5Compressor flooding 6 7Open phase
No.Error typeRemoteUnit side (PCB) Operation SWSWS1
RemoteUnit side (PCB) ※7 Inlet water temperature thermistor error (TH10 MAIN Circuit) TB2 TB1
72C
DCL
Inside of the control box (front view)
CAHV-P500YA-HPB ELECTRICAL WIRING DIAGRAM
※3. If an error occurs, a 4-digit error code, as explained in the table on the right, will blink on the board and remote controller display. ([Error code] and [Error source address] appear alternately on the remote controller display.) ※6. Depending on the system configuration, the unit may come to an abnormal stop when the communication error lasts for 10 minutes or longer. In this case, the error needs to be reset by setting either SWS1 on the unit (PCB) or remote operation switch. ※7. This error code will appear when multiple errors occur that are reset in different ways and when one or more of these errors have not been reset. This error can be reset by turning off and then back on the unit's power. ※8. Remove the cause of the error before resetting the error. Resuming operation without removing the cause may burst the heat exchanger. ※9. [Error code] and [Detail code] appear alternately. Refer to the Installation Manual for detail codes.※4. Definition of symbols in the "Error reset" column ・・・ Errors that can be reset regardless of the switch settings ・・・ Errors that can be reset if the remote reset setting on the unit is set to "Enable" (factory setting) Errors that cannot be reset if the remote reset setting on the unit is set to "Disable" ・・・ Errors that cannot be reset ・・・ Errors that will be automatically reset after the cause of the error is removed ※5. Power failure can be detected only when the switch setting "Automatic recovery after power failure" on the unit is set to "Disable." (The default setting is "Enable.")Error Codes
Control Board Current water temperature ※2
CNDCPink
C5
Z5 C3 C2F02 R01R02
F01 R03
Z1Z2 R34
C30 C32 C34 C36 black
F03 F04AC250V6.3A T blackwhite L
F01, F02, F03AC250V6.3 A T
DSA R35 CT3
white
R33 SC-L3
R30 redwhite
D1R04 R32
R06
CN2 C31
CN18Vblue U
Z4
C17
CN4red TB21CN1B
L1 CN1A
red
Noise Filter TB22
CN3 green
TB24
Fan motor (Heat exchanger) N
C33 TB23
IPM
FAN BoardF05DC700V4A T *3
M 3〜 black U
red DiodeBridge
2 72C
1 black SC-P2 C7C8 CT12L2
R5 U
LED1: Normal operation + red
C35
DCL SC-L2
SC-P1 SC-U
CN1 black
C37
CN5Vyellow C1
C9C10
CN6
4
C100 LED1: Normal operation (lit) / Error (blink)
LED3: CPU in operation R1 CN4 CN2 SC-V
UIGBT CT22
U
CNINV SC-WSC-L1
W
CN21blue U
CNVDC
CN4 blue
C631 ゜ LED2: Error
R630 R631CN22red t Z3
CN5 R31
C6 CNTYPblack
C1 RSH1 THHSt
FT-PP N ゜
FT-N C4
+ INV Board
+
C630 +++ ++ +
3 red L3
THBOX −+
V CN52Cred
MS 3〜
UW
V
redwhiteblack Motor(Compressor)
CNTYP2
SW2-10: OFF SW3-9: OFF SW3-10: OFF SW3-7: OFFSW3-6: OFFSW3-5: OFFSW3-8: OFF High pressure/Low pressure
Display setting Preset water temperatureControl board displayControl board SW setting ※1 ※1. Select a display by setting the switches. ※2. The current water temperature is displayed according to the preset water temperature method.
SW3-5: ONSW3-6: OFF SW3-5: ONSW3-6: ON 51075104 51065105
1303
11030403 1104 4102 4106 4115 4121 5101 5102 5103
4220,4225 4230,4235 4240,4245 4250,4255 4260,4265
A000 A-P0 AC61 AFSA AHP1AdSH A471 68326830 683166066603 6607 7113,71177105 71306834 71026608
5114,5115 6600650051185117 5301,5305
5113511251115110511051095108 KC79B437H01
43
5 - 44 _indd
321321221112
2
2 1
3 2
5 4 2 1 4 3 1
2 4 3 2
3 1 1 1
5 4 2 3 1
2 1
541
1 23 4
2
5
2
12323 3 4 4
21
6 1
3 2 1
21
7 2
3 1
3
6
1 2
5 6
412
4 1
3 4 5 6
12 34
1
132
1 2
3
1221
32
7 5
34341234564623121 3 123456
2 1 3
N
L1
1 13
1
2
2 23
7
3
6 1
21
5
4
2345761
2
3
L3L2L1
1 2 1
N
2 1 3
2
L3L2
2
321
312
1
THHSIGBT temperature Z21Function setting connector
SymbolExplanationSymbol explanation SUB BOX
CT12 CT22 CT3 F01 F02 F03 F04 F05 F06
Capacitor (Electrolysis)
AC current sensor SV1 21S4LEV2
CH 63LS TH12,13TH5〜8
M MSCompressor motor Thermistor
Crankcase heater (for heating the compressor) Low pressure sensor4-way valveSolenoid valve (Injection circuit) High pressure switch63H1
Fuse Electronic expansion valve (Main circuit)
DCLDC reactor 72C
Electronic expansion valve (Injection)LEV1 SV2Solenoid valve (Hot gas circuit)
Fan motor 63HSHigh pressure sensor
R1Electrical resistanceR5
C100 72C
R1 C100
SW1SW2SW3
OFFONOFFONOFFON1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10 ※9 27
5251
48474645 50
44 49
43
41 42
403938373635 −( )−( )−( )−( ) −( )−( ) 262524
※9 ※9※9※9
※8
8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
28 29 30 34333231※9※51 2 3 4 5 6 7
※7 ※6※6
CAHV-P500YA-HPB ELECTRICAL WIRING DIAGRAM
M-NET board TB1DCLInside of the control box (front view) Inverter board Control board Noise filter
Fan Inverter board
TH13TH12TH5 ttt°°°°tt°
TH6TH763LS 63HS CN63HSCN63LSredCN401
CN407red
CNS2 yellow CN102 red CNIT
B S TP2
A A/M1B/M2
TB3 TP1
Transmission power board
red CN04 Transmission power circuit TB7
LED1: Power feeding 72C
Water inlet temp. 2
Discharge Ref temp. 2
Shell Ref temp. 2
Suction Ref temp. 2
Water outlet temp. 2
CN402green
MM CNLVACNLVCblueCN404blackTH8 t°Air hex Ref temp. 2
X01
X02 CN502 CN501
CHSV1 21S4
CNDCPink
X03 CN801
yellow
To MAIN BOXMA
LEV2LEV1
CN2
To MAIN BOX TB2
Control Board DOWNUP ENTER
SWP1 SWP2SWP3 BA OFF LOCAL
SWU3SWU1SWU2 SWS1SWS2 blackCNAC2
X07
(1)(5) Unit adrress setting
(0)
CN102 yellowCNS2 CNITred
CNTYP1black
Z21 SV2
MB
CN4CN332 blue
F06AC250V3.15A T
red CNAC
TB4
LED2: CPU in operation
63H1 REMOTE Control power circuit
LED1
blue CN511
※2 Error Codes Display setting
CN52C red
C5
Z5 C3 C2F02 R01R02
F01 R03
Z1Z2 R34
C30 C32 C34 C36 black
F03 F04AC250V6.3A T blackwhite L
F01, F02, F03AC250V6.3A T
DSA R35 CT3
R05 white
R33 SC-L3
R30 redwhite
D1R04 R32
R06
CN2 C31
CN18Vblue U
Z4
CN5 red
C17
CN4red TB21CN1B
L1 CN1A
red
Noise Filter TB22
CN3 green
TB24Fan motor (Heat exchanger) N
C33 TB23
IPM
FAN Board F05DC700V4A T M 3〜 black U
red DiodeBridge
2 72C
1 black SC-P2 C7C8 CT12 L2
R5 U
LED1: Normal operation + red
C35
DCL SC-L2
SC-P1 SC-U
CN1 black
C37
CN5Vyellow C1
C9C10
CN6
4
C100 LED1: Normal operation (lit)/ Error (blink)
LED3: CPU in operation R1 CN4 CN2 SC-VU
IGBT CT22
U
CNINV SC-WSC-L1
W
CN21blue U
CNVDC CN4blue
C631 ゜ LED2: Error
R630 R631
CN22red t Z3
CN5 R31C6
CNTYPblack
C1 RSH1 THHSt
FT-PP N ゜
FT-N C4
+ INV Board
+C630 +++ ++ +
3 red L3
THBOX −+
V W
V UMS 3〜
whiteredblack
CNTYP2
Motor(Compressor)
MAIN BOX and SUB BOX Current water temperature ※2 High pressure/Low pressure Preset water temperatureControl board displayControl board SW setting ※1 SW2-10: OFF SW3-9: OFF SW3-10: OFF SW3-7: OFFSW3-6: OFFSW3-5: OFFSW3-8: OFF
SW3-5: ONSW3-6: OFF SW3-5: ONSW3-6: ON
Note 1. Single-dotted lines indicate field wiring. Note 3. The SW1 - SW3 switches indicated with can be set on site. Do not change the other SW1 - SW3 switch settings. ※1. Select a display by setting the switches. ※2. The current water temperature is displayed according to the preset water temperature method.Note 2. Faston terminals have a locking function. Press the tab in the middle of the terminals to remove them. Check that the terminals are securely locked in place after insertion. 10' digit 1' digit LED3: Lit while energized ※3. If an error occurs, a 4-digit error code, as explained in the table on the right, will blink on the board and remote controller display. ([Error code] and [Error source address] appear alternately on the remote controller display.) ※4. Definition of symbols in the "Error reset" column ・・・ Errors that can be reset regardless of the switch settings ・・・ Errors that can be reset if the remote reset setting on the unit is set to "Enable" (factory setting) Errors that cannot be reset if the remote reset setting on the unit is set to "Disable" ・・・ Errors that cannot be reset ・・・ Errors that will be automatically reset after the cause of the error is removed ※6. Depending on the system configuration, the unit may come to an abnormal stop when the communication error lasts for 10 minutes or longer. In this case, the error needs to be reset by setting either SWS1 on the unit (PCB) or remote operation switch. ※7. This error code will appear when multiple errors occur that are reset in different ways and when one or more of these errors have not been reset. This error can be reset by turning off and then back on the unit's power. ※8. Remove the cause of the error before resetting the error. Resuming operation without removing the cause may burst the heat exchanger. ※9. [Error code] and [Detail code] appear alternately. Refer to the Installation Manual for detail codes.※5. Power failure can be detected only when the switch setting "Automatic recovery after power failure" on the unit is set to "Disable." (The default setting is "Enable.")
Operation SW
Error code (PCB ※3) Error reset ※4 SWS1
No.Error typeRemoteUnit side (PCB) Operation SW Error code (PCB ※3) Error reset ※4 SWS1
No.Error typeRemoteUnit side (PCB) Inverter overheat protection faultHeat exchanger freeze up Shell temperature thermistor error (TH7 SUB Circuit)Compressor inlet temperature thermistor error (TH6 SUB Circuit)Discharge temperature thermistor error (TH5 SUB Circuit)
Vacuum protection fault
Shell temperature faultSerial communication error Open phase (T phase) Power supply fault Power supply frequency fault Active filter fault Inverter bus voltage fault Inverter overload protection fault IPM error (inclusive)/overcurrent relay trip Cooling fan fault Air-side heat exchanger refrigerant temperature thermistor error (TH4 MAIN Circuit)Shell temperature thermistor error (TH3 MAIN Circuit)Compressor inlet temperature thermistor error (TH2 MAIN Circuit)Discharge temperature thermistor error (TH1 MAIN Circuit)
Unreset errors Power faliure Discharge temperature fault Water supply cutoff (Flow switch) High pressure faultCompressor flooding Open phase Incompatible combination of unitsRemote controller signal reception error 2Low-pressure sensor faultOutlet water temperature thermistor error (TH13 SUB Circuit)Inlet water temperature thermistor error (TH12 SUB Circuit)Outlet water temperature thermistor error (TH11 MAIN Circuit)
Air-side heat exchanger refrigerant temperature thermistor error (TH8 SUB Circuit) Model setting errorDiscrete address, system errorHigh-pressure sensor fault Communication error between the MAIN and SUB unitsRepresentative water temperature thermistor error (TH14, TH15) ACCT・DCCT sensor fault/Circuit fault Communication error between the MAIN and SUB units (Simple multiple unit control) Address overlap Remote controller signal reception error 1 Remote controller signal transmission error Incorrect setting of No.-of-connected-unitTHHS sensor/Circuit faultOutside temperature thermistor error (TH9) Inlet water temperature thermistor error (TH10 MAIN Circuit)
Electromagnetic relay (Inverter main circuit) R5 68326830 683166066603 6607 7113,71177105 71306834 71026608
5114,5115 6600650051185117 5301,5305
5113511251115110511051095108 51075104 51065105130311030403 1104 4102 4106 4115 4121 5101 5102 5103
4220,4225 4230,4235 4240,4245 4250,4255 4260,4265
A000 A-P0 AC61 AFSA AHP1AdSH A471 KC79B438H01