• No results found

Electrical Components and Wiring Diagrams

In document Service Handbook (сторінка 104-136)

4 Electrical Components and Wiring Diagrams

4 Electrical Components and Wiring Diagrams

4-1 Outdoor Unit Circuit Board Arrangement

4-1-1 Outdoor Unit Control Box

(1) PURY-P200, P250, P300, P350, P400, P450, P500YLM-A(1) PURY-EP200, EP250, EP300, EP350, EP400, EP450YLM-A

1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the water- proof and dust proof properties of the control box and may result in damage to its internal components.

2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter- minals to remove them.

3) Control box houses high temperature parts. Be well careful even after turning off the power source.

4) Perform the service after disconnecting the outdoor unit fan board connector (CNINV) and the inverter board con- nector (CN1). Before plugging in or unplugging connectors, check that the outdoor unit fan is not rotating and that the voltage between FT-P and FT-N on the INV board is 20 VDC or less.The capacitor may collect a charge and cause an electric shock when the outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.

5) To connect wiring to TB7, check that the voltage is 20 VDC or below.

6) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1) back to the inverter board after servicing.

7) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.

Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the capacitor voltage (inverter main circuit) has dropped to 20 V DC or less. It takes about 10 minutes to discharge electricity after the power supply is turned off.

8) When the power is on, the compressor or heater is energized even while the compressor is stopped. Before turning on the power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor. Check the compressor for a ground fault. If the insulation resistance is 1.0 MΩ or below, connect all power supply wires to the compressor and turn on the power to the outdoor unit. It is energized to evaporate the liquid refrigerant that has accumulated in the compressor.

<HIGH VOLTAGE WARNING>

Control box houses high-voltage parts.

When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.

Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the voltage of the capacitor in the main circuit has dropped to 20 VDC or less.

FAN board Control board Electromagnetic relay

(DCL)

Rush current protection resistor (R1, R5) Note 2)

M-NET board

INV board Note 1)

Ground terminal Terminal block

for power supply (TB1)

Terminal block for transmission line (TB3, TB7) Capacitor

(C100)

Electromagnetic contactor (72C)

Noise filter

(2) PURY-EP500YLM-A

Capacitor Board INV board

Control board

M-NET board

Terminal block for transmission line (TB3, TB7)

Terminal block for power supply (TB1)

Noise filter Fan board

Ground terminal

DC Reactor

4 Electrical Components and Wiring Diagrams 1) Exercise caution not to damage the bottom and the front panel of the control box. Damage to these parts affect the water-

proof and dust proof properties of the control box and may result in damage to its internal components.

2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter- minals to remove them.

3) Control box houses high temperature parts. Be well careful even after turning off the power source.

4) Perform the service after disconnecting the outdoor unit fan board connector (CNINV) and the inverter board con- nector (CN1). Before plugging in or unplugging connectors, check that the outdoor unit fan is not rotating and that the voltage between SC-P and SC-N on the capacitor board is 20 VDC or less. The capacitor may collect a charge and cause an electric shock when the outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.

5) To connect wiring to TB7, check that the voltage is 20 VDC or below.

6) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1) back to the inverter board after servicing.

7) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.

Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the capacitor voltage (inverter main circuit) has dropped to 20 V DC or less. It takes about 10 minutes to discharge electricity after the power supply is turned off.

8) When the power is on, the compressor or heater is energized even while the compressor is stopped. Before turning on the power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor. Check the compressor for a ground fault. If the insulation resistance is 1.0 MΩ or below, connect all power supply wires to the compressor and turn on the power to the outdoor unit. It is energized to evaporate the liquid refrigerant that has accumulated in the compressor.

4-1-2 Fan Box

(1) PURY-P450, P500YLM-A(1) PURY-EP400, EP450, EP500YLM-A

1. Handle the fan box with care. If the front or the bottom panel becomes damaged, water or dust may enter the fan box, dam- aging its internal parts.

2. Perform the service after disconnecting the fan board connector (CNINV) and the connect board connector (CN103).

Before plugging in or unplugging connectors, check that the outdoor unit fan is not rotating and that the voltage be- tween FT-P and FT-N on the INV board or between SC-P and SC-N on the capacitor board is 20 VDC or less. The ca- pacitor may collect a charge and cause an electric shock when the outdoor unit fan rotates in windy conditions.

3. Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN103) back to the connect board after servicing.

FAN board

Connect board

Note 1)

4 Electrical Components and Wiring Diagrams

4-2 Outdoor Unit Circuit Board Components

4-2-1 Control Board

*For information about the display of SW4 function settings, refer to the following page(s). [5-1-1 Outdoor Unit Switch Func- tions and Factory Settings](page 127)

CN801

Pressure switch connection

Actuator drive

signal output LEV

drive signal output

SWU1,2 Address switch LED1Service LED

LED3Function setting display Lit :ON Unlit:OFF LED2Normal/Error indicator SWP1SW4 setting (SW6-10:OFF) Effective/Ineffective switching SW4~6 Dip switches

CN40Centralized control power supply ON CN51 12 VDC output

Compressor ON/OFF signal output

Error signal output CN41

Centralized control power supply OFF External signal input (contact input)

F01250 VAC 3.15A T CNRYB 72 drive signal output

Sensor input CN2/2A

Serial communication signal input GND

CN4 5 VDC output GND

Serial communication GND

16 VDC

GND(FAN INV board 1) 17 VDC

17 VDC GND(INV board) CN332

18 VDC output GND(FAN INV board 2)

CNVCC2 12 VDC output 5 VDC output GND CNAC2

L1 phase L2 phase

CNPS 12 VDC output GND 5 VDC output Power supply detection input Power supply ON/OFF signal output Centralized control

transmission signal input/output (30 VDC) Power input signal for the centralized control system (30 VDC) Indoor-outdoor

transmission line signal input/output (30 VDC) CNAC L1 phase

N phase CNDC Bus voltage input P

N

CN110 Power supply detection signal input GND

CN62

4-2-2 M-NET Board (Transmission Power Supply Board)

Power supply output for centralized control system Indoor/outdoor transmission line input/output CN102

CNS2Transmission line input/output for centralized control system

CNIT 12VDC input GND 5VDC input

Power supply detection output Power supply ON/OFF signal input

LED1Power supply for indoor transmission line

TP1,2 Check pins for indoor/outdoor transmission line TB7Terminal block for

transmission line for centralized control TB3Indoor/outdoor

transmission block

Ground terminal for transmission line Grounding

Grounding

CN04Bus voltage input P

N Grounding

4 Electrical Components and Wiring Diagrams

4-2-3 INV Board

(1) PURY-P200, P250, P300, P350, P400, P450, P500YLM-A(1) PURY-EP200, EP250, EP300, EP350, EP400, EP450YLM-A

1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.

Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity after the power supply is turned off.

2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter- minals to remove them.

3) Control box houses high temperature parts. Be well careful even after turning off the power source.

4) Perform the service after disconnecting the outdoor unit fan board connector (CNINV) and the inverter board con- nector (CN1). Before plugging in or unplugging connectors, check that the outdoor unit fan is not rotating and that the voltage between FT-P and FT-N on the INV board is 20 VDC or less. The capacitor may collect a charge and cause an electric shock when the outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.

5) To connect wiring to TB7, check that the voltage is 20 VDC or below.

6) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1) back to the inverter board after servicing.

7) When the power is turned on, the compressor is energized even while it is not operating. Before turning on the power, discon- nect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor.

Check the compressor for a ground fault. If the insulation resistance is 1.0 MΩ or below, connect all power supply wires to the compressor and turn on the power to the outdoor unit. The liquid refrigerant in the compressor will evaporate by energizing the compressor.

(2) PURY-EP500YLM-A

1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.

Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity after the power supply is turned off.

2) Faston terminals have a locking function. Make sure the cable heads are securely locked in place. Press the tab on the ter- minals to remove them.

3) Control box houses high temperature parts. Be well careful even after turning off the power source.

4) Perform the service after disconnecting the outdoor unit fan board connector (CNINV) and the inverter board con- nector (CN1). Before plugging in or unplugging connectors, check that the outdoor unit fan is not rotating and that the voltage between SC-P and SC-N on the capacitor board is 20 VDC or less. The capacitor may collect a charge and cause an electric shock when the outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.

5) To connect wiring to TB7, check that the voltage is 20 VDC or below.

6) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1) back to the inverter board after servicing.

7) When the power is on, the compressor or heater is energized even while the compressor is stopped. Before turning on the power, disconnect all power supply wires from the compressor terminal block, and measure the insulation resistance of the compressor. Check the compressor for a ground fault. If the insulation resistance is 1.0 MΩ or below, connect all power supply wires to the compressor and turn on the power to the outdoor unit. It is energized to evaporate the liquid refrigerant that has accumulated in the compressor.

CNCT4A Electric current sensor (DC) output (CT3)

CT-3Electric current sensor (DC bus current)

SC-L1 input(L1)

SC-L2 input(L2)

SC-L3 input(L3)

SC-BDC bus current input

IGBT(Rear)

CT-1Electric current sensor(U)

CT-2Electric current sensor(W)

F1Fuse 250 VAC 3.15A

CN10Gate power supply input +-

SW001

ON: No-load operation OFF: Normal operation OFF: Fixed CNTYP INV board Type CN5VGND

5 VDC output CNTHDCL thermistor input CNCT4B Electric current sensor (DC) input (CT-3)

CN43GND(Fan board) Serial communication signal input SC-NBus voltage output(N) FT001

Neutral point output(P) CNRYInrush current limiting

relay input SC-LDC bus current input

SC-PBus voltage output(P) R001Oversurrent

detection resistor FT-R21

Bus voltage output(P)

LED5Lit: Power is supplied to the relay drive Unlit: Power is not supplied to the relay drive

LED4Microcomputer in operation LED1Lit: Inverter operation Blinking: Inverter error CN1Bus voltage output

NP

CN2Serial communication signal output GND17 VDC input 17 VDC input GND

SC-UInverter output(U)

SC-VInverter output(V) SC-W Inverter output(W)

4 Electrical Components and Wiring Diagrams

4-2-4 Fan Board

1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.

Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity after the power supply is turned off.

2) Control box houses high temperature parts. Be well careful even after turning off the power source.

3) Perform the service after disconnecting the outdoor unit fan board connector (CNINV) and the inverter board con- nector (CN1). Before plugging in or unplugging connectors, check that the outdoor unit fan is not rotating and that the voltage between FT-P and FT-N on the INV board or between SC-P and SC-N on the capacitor board is 20 VDC or less. The capacitor may collect a charge and cause an electric shock when the outdoor unit fan rotates in windy con- ditions. Refer to the wiring nameplate for details.

4) To connect wiring to TB7, check that the voltage is 20 VDC or below.

5) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN1) back to the inverter board after servicing.

LED1Lit: Inverter operation Blinking: Inverter error LED4Microcomputer in operation (Lit)

RSH02

4-2-5 Noise Filter

(1) PURY-P200, P250, P300, P350, P400, P450, P500YLM-A(1) PURY-EP200, EP250, EP300, EP350, EP400, EP450YLM-A

CN4Output

(Rectified L2-N current) P

N

CN5Output

(Rectified L2-N current) P

N

TB21Input/output(L1) TB22

Input/output(L2) TB23

Input/output(L3) TB24 Input(N) CN1BInput

L3 L2 CN1AInput

N L1 Grounding F1,F2,F3,F4 Fuse250VAC 6.3A

CN3Output L1 N Grounding CN2 Surge absorber circuit

Surge absorber circuit Short circuit Short circuit

4 Electrical Components and Wiring Diagrams (2) PURY-EP500YLM-A

CN1A Input

①N③L1

CN3 Output

①L1

③N

CN2①Surge absorber circuit

③Surge absorber circuit

⑤Short circuit

⑥Short circuit CN4

Output

①L2③N

⑤L3

F1 Fuse 250VAC 6.3A

F2 Fuse 250VAC 6.3A

F3

Fuse250VAC 6.3A

TB21 Input/output L1

TB22 Input/output L2

Grounding Grounding

Grounding

CN1B

①L3④L2

TB23 Input/output L3

TB24 Input/output N

CAUTION FOR HIGH VOLTAGE

CAUTION FOR HIGH VOLTAGE

4-2-6 Capacitor Board

(1) PURY-EP500YLM-A

1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.

Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity after the power supply is turned off.

2) Control box houses high temperature parts. Be well careful even after turning off the power source.

3) Perform the service after disconnecting the fan board connector (CNINV) and the connector board connector (CN103). Before plugging in or unplugging connectors, check that the outdoor unit fan is not rotating and that the voltage between SC-P and SC-N on the capacitor board is 20 VDC or less. The capacitor may collect a charge and cause an electric shock when the outdoor unit fan rotates in windy conditions. Refer to the wiring nameplate for details.

4) To connect wiring to TB7, check that the voltage is 20 VDC or below.

5) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN103) back to the connector board after servicing.

CN106 Bus voltage input N

P

CN103 Output

(Rectified L3-N current) P

N

CN107 Output (L3-N rectifier) P N

CN104 Output (L3-N rectifier) P N

SC-NBus voltage input(N) SC-PBus voltage input(P)

note.1

note.1

C101〜C108 Smoothing capacitor R301〜R304

Rush current protection resistor CN102

Power supply detection signal output GND

CN101 Input(L2) Input(N) Input(L3)

4 Electrical Components and Wiring Diagrams

4-2-7 Connect Board

(1) PURY-P450, P500YLM-A(1)

PURY-EP400, EP450, EP500YLM-A

1) When opening or closing the front panel of the control box, do not let it come into contact with any of the internal components.

Before inspecting the inside of the control box, turn off the power, keep the unit off for at least 10 minutes, and confirm that the capacitor voltage (inverter main circuit) has dropped to 20 VDC or less. It takes about 10 minutes to discharge electricity after the power supply is turned off.

2) Control box houses high temperature parts. Be well careful even after turning off the power source.

3) Perform the service after disconnecting the fan board connector (CNINV) and the connector board connector (CN103). Before plugging in or unplugging connectors, check that the outdoor unit fan is not rotating and that the voltage between FT-P and FT-N on the INV board or between SC-P and SC-N on the capacitor board is 20 VDC or less.

The capacitor may collect a charge and cause an electric shock when the outdoor unit fan rotates in windy condi- tions. Refer to the wiring nameplate for details.

4) To connect wiring to TB7, check that the voltage is 20 VDC or below.

5) Reconnect the connector (CNINV) back to the fan board and reconnect the connector (CN103) back to the connector board after servicing.

1

4-3 Outdoor Unit Electrical Wiring Diagrams

(1) PURY-P200, P250, P300, P350, P400YLM-A(1) PURY-EP200, EP250, EP300, EP350YLM-A

Linear expansion valve (for the control of evaporating temperature)

RSH01/02,RSH1For current detection

C30~C37Capacitor (inverter main circuit) LChoke coil (for high frequency noise reduction) SV4a,b,dHeat exchanger capacity control

R1,5ResistorFor inrush current prevention Subcooled liquid refrigerant temperaturePipe temperatureOutdoor unit heat exchanger capacity control

SV5b

SV1a

21S4aSymbol<Symbol explanation> 63H1 63HS1 63LS 72C CT12,CT22,CT3 LEV5aDCL

Solenoid valve For opening/closing the bypass circuit under the O/S

4-way valve(Cooling/Heating switching)Explanation

Pressure sensor Pressure switch

High pressure protection for the outdoor unit Discharge pressure Low pressure

Magnetic relay(inverter main circuit) Current sensor(AC) DC reactor Z25THHSTH7TH6TH5TH4TH3TB7TB3TB1SV7,SV9 Thermistor

Discharge pipe temperature ACC inlet pipe temperature OA temperature IPM temperature Function setting connector

Power supply Indoor/Outdoor transmission cable Central control transmission cable

Terminal block For opening/closing the bypass circuit

*1.Single-dotted lines indicate wiring not supplied with the unit.

*2.Dot-dash lines indicate the control box boundaries. *3.Refer to the Data book for connecting input/output signal connectors. *4.Daisy-chain terminals (TB3) on the outdoor units in the same refrigerant system together

.

*5.Faston terminals have a locking function. Make sure the terminals are securely locked in place after insertion. Press the tab on the terminals to removed them. *6.Control box houses high-voltage parts. Before inspecting the inside of the control box,turn of

f the power,keep the unit off for at least 10 minutes, and confirm that the voltage between FT-P and FT-N on INV Board has dropped to DC20V or less. SV10,SV11

For opening/closing the defrost circuit

TH9,TH11Heat exchanger outlet pipe temperature

*7.Difference of appliance. P200/250/300/350/400Model name *7 do not existappliance EP200/250/300/350*7 exist

F121 DC700V 4A TC151,C152 RSH01/02 12 L3N

red CNPS

1 321 TP1TP2

TB3

23 TB7 M1M2M1M2S

1 51234

12

12

132 346 36

1 531

2 2

CN82 blue

1

3 4

CN83 black

L1L2

31

Fan motor (Heat exchanger)

U V WCNINV

7 14 34

CN4 black

1

13

231 3

SW001

14 CN2 1 12

1 3 31432

23 1 1

CNSNR TH4

4 1

1 1

CN211green 23123321

U

5

2

54321 1 32 1 23

123

1 CN6

21 2

yellow CNPOW

1

654 X10 X12

ON X08

Unit address setting

CT12

CN5 red

D1R4 -Z5

1 +

3 1

6 white 12 34

3

green CN62 CN990 green

CN213 green

CNTYP4

F4 AC250V 6.3A

T

R5 CN201

Z25 TH5TH6

SWU2

LED1 SW610

Control Board TH3 CN40

63HS1 CN41

TH7 15

234 1 SW4

LED3

5

LEV5a 33 SET UP(SW6-10) SC-V CT22

SC-U V

CN4 blue

red

M OFF t black

CN506red

CNTYP2black

6

yellow CN3K

*3

Compressor ON/OFF output Error detection output

TB21

DC12VCN51

SV5b CN1A U

CN2

blue CN3N

1 3

+ 3

4 TB1CN1B

TB7 Power selecting connector

CNVDC 1

IPM 2 5

6 L3N

DCL black

72C white

red 26

ON OFF M-NET powersupply circuit

12 M-NET Board

Indoor/Outdoor transmission cable

INV BoardredTB23TB24

L2L1

+

ON

1's digit

THHS CN102

C31,C33, C35,C37

14

1

1 W

10's digit

OFFLED2:Normal operation(Lit) / Error(Blink) CNS2 yellow

CNDC red

red

MS 3~

2

2

C100 *5 LED1:Power supply to

Indoor/Outdoor transmission line

+ black

Central control transmission cable

*6 SC-L1

ONOFF FT-N

R30,R32, R34

Motor(Compressor)

red CN3S

1

CN04 red

CN43 yellow

1 SC-P2 P

CN61 green

CN202red

C30,C32, C34,C36

6 N

CN1

LED1:Normal operation(Lit) / Error(Blink)

*4

SC-W SC-L3

2 CNRYB

P63H1 4

1 SW510

5 CN3D

1

CPU power supply circuit

black CNAC2

1 *3

ONOFF 10

SWU1 white

CN212red SC-L2

62 CN80 CNTYP5green

LED4:CPU in operation

LED1:Normal operation(Lit) / Error(Blink)

CN801red 5 °IPM4

SC-P1 FT-P

blackred DB1 CT3

C1

CNTYP black

black TB22

SWP1 RSH1

R6 C11

FAN Board 63LS

ZNR1 U L

Noise Filter

2

CN507 black CN508 blue

3 3

3 6 6

4

CN3 green

SV9

Function setting

LED1 Display setting/ Function setting

72C Noise filter Noise filter

67 red

Surge absorber

12 1 1

CNLVA 1

F01 AC250V 3.15A

T

MS 3~

whiteblack

1

CNIT red

L1L2L3N

R31,R33, R35

3

4 1

R1,R5 X05 X13X06 X14

3 3

5 51 1

6 6CN505 CN509 yellow

13CNAC

CN81 green

12

534 4

4 CN2 SV1a SV4bSV4d SV4a21S4a

Power Source 3N~ 50/60Hz 380/400/415V

TH11

CNTYP1black12TH9 5 X09

SV7*7

3 1CN504SV11

3 1CN503SV10 X03 yellowgreen X04 CN110black 12

Power failure detection circuit

UZNR400 1

In document Service Handbook (сторінка 104-136)